Browse > Article
http://dx.doi.org/10.14346/JKOSOS.2012.27.4.033

Characteristics for Ground Impedance of Counterpoise according to Position of Auxiliary Probe and Frequency  

Gil, Hyoung-Jun (Electrical Safety Research Institute)
Kim, Dong-Woo (Electrical Safety Research Institute)
Publication Information
Journal of the Korean Society of Safety / v.27, no.4, 2012 , pp. 33-37 More about this Journal
Abstract
This paper describes the characteristics for ground impedance of counterpoise according to position of auxiliary probe and frequency using the fall-of-potential method and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position of auxiliary probes. In order to analyze the effects of ground impedance due to the distance of the current probe and frequency, ground impedances were measured in case that the distance of current probe was located from 10[m] to 100[m] and the measuring frequency was ranged in 55 [Hz], 128[Hz], 342[Hz], and 513[Hz]. The results could be help to determine the position of auxiliary probe when the ground impedance was measured at grounding system.
Keywords
ground impedance; counterpoise; position of auxiliary probe; frequency; measuring error;
Citations & Related Records
연도 인용수 순위
  • Reference
1 길형준, 김동우, 김동욱, 이기연, 문현욱, 김향곤, "접지임피던스 측정에 관한 전류보조전극 거리 및 주파수의 영향 분석", 한국조명․전기설비학회 춘계학술대회 논문집, pp. 289-292, 2009.
2 길형준, 김동우, "전위보조전극의 위치변화에 따른 접지저항 측정값의 상대오차분석", 조명․전기설비학회논문지, 23권 2호, pp. 96-102, 2009.
3 김동우, 길형준, 김동욱, 이기연, 문현욱, 김향곤, "건축물의 접지저항 측정용 보조전극 매설 실태 및 매설 위치에 따른 오차율 분석", 대한전기학회 하계학술대회 논문집, pp. 2160-2161, 2009.
4 이복희, 이봉, 이승주, 유재덕, 조성철, "전류인가 위치에 따른 매설지선의 과도접지임피던스 특성", 한국조명․전기설비학회 춘계학술대회 논문집, pp. 328-331, 2009.
5 Hyoung-Jun Gil, Dong-Woo Kim, Dong-Ook Kim, Ki-Yeon Lee and Hyang-Kon Kim, "Effects of Position of Auxiliary Probe on Ground Resistance Measurement Using Fall-of-Potential Method", International Journal of Safety, Vol.7, No.2, pp. 1-6, 2008.
6 길형준, 김동우, 김향곤, "허용폭을 이용한 신개념 접지저항 측정방법 연구", 한국안전학회 춘계학술대회 논문집, pp. 16, 2011.
7 이복희, "접지의 핵심 기초 기술", 도서출판 의제, pp. 65-99, 1999.
8 IEEE Std 81.2-1991, "IEEE Guide for Measurement of Impedance and Safety Characteristics of Large, Extended or Interconnected Grounding Systems", pp. 17-21, 1991.
9 C. Wang, T. Takasima, T. Sakuta and Y. Tsubota, "Grounding Resistance Measurement Using Fall-of-PotentialMethod with Potential Probe Located in Opposite Direction to the Current Probe," IEEE Trans. Power Delivery, Vol.13, No.4, pp. 1128-1135, 1998.   DOI   ScienceOn
10 이상무, 길형준 외, "정보통신단체표준 접지저항 측정기술", 한국정보통신기술협회, pp. 14-50, 2011.