Properties of On-Line Partial Discharge in Hydrogenerator Stator Windings (수력발전기 고정자 권선의 운전중 부분방전 특성)

  • Kim, Byong-Han;Kim, Hee-Dong
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.4
    • /
    • pp.172-177
    • /
    • 2006
  • During normal machine operation, partial discharge(PD) tests were performed with partial discharge analyzer(PDA) in two hydrogenerators. Six cable couplers were installed in circuit ring bus and endwinding of three phases. PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude$(Q_m)$ were very low in hydrogenerator #1 and #2, respectively. The trend analyses of NQN and $Q_m$ value are available for monitoring of the insulation condition in hydrogenerator stator windings. The insulation condition of stator winding can be assessed. Discharge at conductor surface was discovered in B phase(C2 coupler) of hydrogenerator #1. Internal discharges were generated in A and C phases(C2 coupler) of hydrogenerator #1 and in A, Band C phases(C1 and C2 couplers) of hydrogenerator #2. Slot discharges occurred in A, Band C phases(C1 coupler) of hydrogenerator #1. The stator windings of two hydrogenerators were in good condition.

Partial Discharge Property of Hydrogenerator Stator Windings (수력발전기 고정자 권선에서 부분방전 특성)

  • Kim, Hee-Dong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.05a
    • /
    • pp.86-90
    • /
    • 2000
  • Partial discharge(PD) tests were performed when the hydrogenerator(rated 11kV and 25MVA) was shut down(off-line). Six cable couplers were installed in the ring bus as well as within hydrogenerator terminal box. PD tests were conducted using partial discharge analyzer(PDA) and digital partial discharge detector(PDD). PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude increased with increase of ac voltage. Slot discharges were discovered in three phases(A, B and C) at the rated voltage. PDA and PDD test results are in accordance with the pattern and magnitude of partial discharge. This hydrogenerator stator windings were in good condition.

  • PDF

Assessment of Insulation Condition for Hydro-generator (대용량 수치발전기의 절연진단에 의한 절연상태평가)

  • Lee, Kwang-Ho;Park, Jong-Jin;Kim, Ki-Won;Lee, Eun-Woong
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1810-1812
    • /
    • 2002
  • This test was performed to assess the insulation deterioration condition of the stator winding of Chung-Ju hydrogenerator #4 and Dae-Cheong hydrogenerator #2 which had been in service after being constructed 1980. The insulation diagnostic tests include resistance polarization index(P.I.) AC current, dissipation factor(Tan ${\delta}$) and partial discharges ($Q_{max}$). The results of diagnostic tests were compared to factory test measurements.