• 제목/요약/키워드: High voltage motor stator winding

검색결과 78건 처리시간 0.021초

멀티레벨 인버터 구동 고압유도전동기에서 발생하는 과도과전압 저감을 위한 RC필터의 효과분석 (Analysis on the effect of RC filter to mitigate transient overvoltage on the high voltage induction motor fed by Multi level inverter)

  • 권영목;김재철;김용성;이양진
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2005년도 학술대회 논문집
    • /
    • pp.399-403
    • /
    • 2005
  • In this paper, we analyze on the effect of RC filter to mitigate transient overvoltage on the high voltage induction motor fed by H-bridge cascaded 7-level inverter. The switching surge voltage becomes the major cause to occur the insulation failure by serious voltage stress in the stator winding of high voltage induction motor. The effect of switching surge appears more serious in high voltage induction motor than low voltage induction motor. Consequently, we demonstrated that the RC filter connected to the motor terminals greatly reduces the transient voltage stress md ringing. The results of simulation show the suppression of transient overvoltage at the motor end of a long cable. using EMTP

  • PDF

함침기법에 따른 인버터 구동 유도전동기 고정자 권선의 절연성능 평가 (Evaluation of Insulation Performance for Stator Winding of the Inverter Driven Induction Motor According to Impregnation Methods)

  • 황돈하;강동식;이인우;김동희;이광식
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2006년도 춘계학술대회 논문집
    • /
    • pp.487-492
    • /
    • 2006
  • Inverter driven induction motors with high speed switching and advanced PWM techniques are widely used for variable speed applications. Recently, the insulation failures of stator winding have attracted much concern due to high dv/dt of IGBT PWM inverter output. In this paper, the detailed insulation test results of 26 low-voltage induction motors are presented. Six different types of insulation techniques are applied to 26 motors. The insulation characteristics are analyzed with partial discharge, inception voltage, AC current, and dissipation factor tests. Also, breakdown tests by high voltage pulses are performed. From the above test data the effects due to different wires and insulation techniques on the insulation characteristics of low-voltage induction motors are compared and analyzed. The insulation technique to enhance the insulation strength is suggested from the test results.

  • PDF

고압전동기 모델 코일의 절연상태 분석 (Analysis of Insulation Condition in High Voltage Motor Model Coils)

  • 김희동;공태식;김병래
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 C
    • /
    • pp.1612-1614
    • /
    • 2003
  • 80pF capacitive couplers were connected to six 6.6kV motor model coil terminals. The voltage applied to the coils were 3.81kv, 4.76 kV and 6.6kV, respectively. These stator coils have various types of artificial insulation defects such as large voids, semi-conductive coating damage and strand insulation fault. Digital PD detector(PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in PD were measured with a conventional digital PD detector. Most of the defect mechanism of large motor stator winding can be associated with PD patterns such as internal and slot discharges. PD patterns coincide with PDD and TGA. These instruments have an input bandwidth of 40-400kHz and 0.1-350MHz. Surge testing detects faults in inter-turn winding of high voltage motor model coils.

  • PDF

인버터 스위칭 써지에 의한 저압 유도전동기의 과도전압 분포해석 (Analysis of Overvoltage Distribution in Low-Voltage Induction Motor Due to Inverter Switching Surge)

  • 황돈하;김용주;이인우;배성우;김동희;노채균
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 B
    • /
    • pp.1151-1153
    • /
    • 2003
  • In this paper, switching surge voltage distribution in stator windings of induction motor driven by IGBT PWM inverter is studied. To analyze the irregular voltage of stator winding, equivalent circuit model of inverter-cable-motor was proposed and high frequency parameter is computed by using finite element method (FEM). Electromagnetic transient program (EMTP) analysis of the whole system for induction motor and PWM inverter is proposed. In order to experiment, an induction motor, 380 [V], 50 [HP], with taps from one phase and a switching surge generator was built to consider the voltage distribution.

  • PDF

인버터 구동 유도 전동기 고주파 모델링 (High Frequency Model of Inverter-fed Induction Motor)

  • 흥선기
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 B
    • /
    • pp.795-797
    • /
    • 2001
  • Voltage varing Fate dv/dt which is applied to induction motor usually makes unnegligible leakage current and it flows through stator winding and motor frame. This kind of harmonic leakage current makes effect on power source and cuases electromagnetic trouble because the motor frame has earth. Therefore in this study, a high frequency induction motor model is developed and analyze the motor performance to explain the phenomena. Inverter model is also developed and is combined with the motel model to prepare the basis of the high frequency effects on inverter fed induction motor.

  • PDF

고압 전동기 고정자 권선의 운전중 절연감시 시스템 개발 (Development of On-tine Partial Discharge Monitoring System for High-Voltage Motor Stator Windings)

  • 황돈하;심우용;박도영;강동식;김용주;송상옥;김회동
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.224-226
    • /
    • 2001
  • In this paper, a novel high-voltage motor monitoring system (HVMMS) is proposed. This system monitors the insulation condition of the stator winding by on-line measurements of partial discharge (PD). Sensor, EMC (Epoxy-Mica Coupler) is used for PD measurement PD signals are continuously measured and digitized with a peak-hold A/D converter to build the database of the high-voltage motor's insulation condition. Also, this system can communicate with the central monitoring system via RS-485. This helps more efficient operation and maintenance of the generator.

  • PDF

A Study on the Insulation Characteristics for Stator Windings of IGBT PWM Inverter-Fed Induction Motors

  • Hwang, Don-Ha;Kang, Dong-Sik;Kim, Yong-Joo;Lim, Tae-Hoon;Bae Sung-Woo;Kim Dong-Hee;Ro Chae-Gyun
    • Journal of Power Electronics
    • /
    • 제3권3호
    • /
    • pp.159-166
    • /
    • 2003
  • The winding insulation of low-voltage induction motors in adjustable-speed drive system with voltage-fed Inverters is substantially stressed due to the uneven voltage distribution and excessive voltage stress (dv/dt), which result in the premature insulation breakdown In this paper, the detailed insulation test results of 26 low-voltage induction motors are presented. Six different types of insulation techniques are applied to 26 motors. The insulation characteristics are analyzed with partial discharge, discharge inception voltage, AC current, and dissipation factor tests Also, insulation breakdown tests by high voltage pulses are performed, and the corresponding breakdown voltages obtained.

고압 전동기 고정자 권선의 활선 부분방전 모니터링 기술개발 (Development of On-Line Partial Discharge Monitoring Techniques for Stator Winding of High-Voltage Motors)

  • 황돈하;이주훈;강동식;김용주;이재영;신병철
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 춘계학술대회 논문집 방전 플라즈마 유기절연재료 초전도 자성체연구회
    • /
    • pp.43-46
    • /
    • 2004
  • Recently many research activities on the diagnosis of stator winding insulation of high-voltage motors have been reported. Most of them utilize a trend analysis of partial discharges. In this paper, a novel on-line monitoring system for an insulation diagnosis is proposed. This system displays magnitude and phase angle distribution of partial discharge. The partial discharge activities can be interpreted more precisely by these techniques.

  • PDF

Comparison of Biot-Savart's Law and 3D FEM in the Study of Electromagnetic Forces Acting on End Winding

  • Kim, Ki-Chan
    • Journal of Electrical Engineering and Technology
    • /
    • 제6권3호
    • /
    • pp.369-374
    • /
    • 2011
  • An induction motor operated with high voltage source generally generates high current in starting mode and has a long transient time after being started. This large and sustaining starting current causes the end windings of the stator to have excessive electromagnetic force. This force is the source of vibration and has a negative and serious influence on the insulation of end windings. Therefore, designing the end winding part with an appropriate support system is needed. To design the support ring enclosing the end windings, we analyze the distribution of electromagnetic force on the end windings by applying the Biot-Savart's law and the 3D finite element method (FEM), and comparing two simulation methods. Finally, we verify the safety of the support structure of the end winding part using stress analysis, which is analyzed with the electromagnetic forces from the 3D FEM simulation.

병렬결선방식을 이용한 인휠 전동기 특성해석 (Characteristic Analysis of In-Wheel Motor with Parallel Winding)

  • 김태형;이동희;안진우;하병길;강병주
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 추계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.96-98
    • /
    • 2008
  • This paper present in-wheel BLDC motor using parallel winding. The voltage of proposed motor is higher than Y-connection three phase BLDC motor in order to separated connection. When the stator resistance and inductance are stable, maximum phase current and maximum torque is increased by high injected voltage. The proposed motor is verified from experimental result of the 2[kW] in-wheel motor on electric vehicle drive.

  • PDF