• 제목/요약/키워드: Herts 접촉

검색결과 2건 처리시간 0.017초

Hertz 접촉 문제의 유한 요소 해석 (Finite Element Analysis of Hertzian Contact Problem)

  • 고동선;김형종
    • 산업기술연구
    • /
    • 제28권A호
    • /
    • pp.81-88
    • /
    • 2008
  • Generally, Hertz theory is used to analyze the contact problem of two bodies. It is simple derivation of solution in the contact part. And calculation time is short Moreover, it can mean well that many wear occurs relatively. However, material property becomes plastic deformation when large perpendicular pressure acts on a small contact surface product. In this case, Hertz theory is inapplicable. Therefore this thesis carried the finite element analysis in consideration of material elasticitystrain and the shape of the geometric from contact point. And it compared with Hertz theory that change of the contact surface and contact pressure.

  • PDF

154 kV 복도체 가공송전선로에서 전자력에 의한 소도체간 접촉 (Kissing of Sub-conductors due to Magnetic Forces in a 154 kV Bundled Overhead Transmission Line)

  • 김상범;노희원;김영홍;고광만;박종혁;김상수
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제2권3호
    • /
    • pp.383-389
    • /
    • 2016
  • 국내 154 kV 복도체 가공송전선로를 대상으로 전자력에 의한 소도체간 접촉현상을 실증적으로 재현하고 대처 방안을 제시하였다. 도체에 흐르는 전류의 크기가 클수록, 스페이서의 간격이 클수록 소도체간에 작용하는 전자력은 크게 측정되었다. 스페이서 간격이 68 m일 경우 전류 크기가 2,000 A 일 때부터 소도체는 불안정한 상태가 되어 소도체간 간격이 변화하는 횡방향 진동이 시작되었다. 스페이서 간격이 136 m일 경우 전류 크기가 증가할수록 소도체간 간격은 좁아지다가 2,250 A 일 때 두 소도체는 완전히 접촉하였다. 스페이서 간격에 따른 전자력의 크기를 도식화하고 안전한 스페이서 간격을 제시하였다. 시험선로와 실선로 간에는 접촉현상이 발생하는 조건이 상이한 것으로 나타났으며, 이는 송전선로 가선 과정에서 도체에 가해진 여러 형태의 잔류 응력, 바람 조건 등의 차이 때문으로 판단되었다.