• Title/Summary/Keyword: HFPD

Search Result 28, Processing Time 0.024 seconds

Considerations on the TF Anal,ysis using Partial Discharge Pulse Characteristics in Oil (유중 부분방전 펄스 특성을 이용한 TF 분석에 대한 고찰)

  • Kim, Jeong-Tae
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.11
    • /
    • pp.508-514
    • /
    • 2005
  • In this paper, it was investigated the characteristics of PD(partial discharge) pulse shapes in oil and the possibility of TF(Time-Frequency) analysis for the discrimination of air corona in on-site PD measurement of oil transformers. For the purpose, single and multiple discharges combined with oil discharges and air corona were generated and measured by use of artificial models through the HFPD pulse detector and the oscilloscope. PD pulse shapes were different according to the type of defects, especially including air corona- pulses. Also, through the TF analysis, data clusters could be classified each other in the TF Map, even in the case of multiple discharges. Therefore, it is known that TF analysis could be aprlied for the improvement of on-site PD measurement in oil transformers.

Dignosis of XLPE Cable Long-Term Used in Nuclear Power Plant (원자력발전소 장기사용 XLPE 케이블 성능측정)

  • Lim, Woo-Sang;Joo, Kwang-Ho;Ha, Che-Wung
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.804-805
    • /
    • 2011
  • 국내 원자력발전소의 고압 케이블의 체계적인 열화 진단 및 수명예측을 위한 사전작업으로 원자력발전소에서 불리한 환경 하에서 장기간 사용된 후 철거된 XLPE 전력 케이블을 대상으로 성능 측정을 수행하였다. 측정 방법으로는 VLF(Very Low Frequency) Tan${\delta}$ 방법 및 상용주파 부분방전시험을 택하였다. 또한 고주파변류기(HFCT)를 사용하는 부분방전 측정방법(HFPD)에 VLF 내압기를 적용할 수 있는지 확인하였다.

  • PDF

A Study of the Noise Discrimination by use of Different Sensors and Pulse Analysis Algorithms in Measuring Partial Discharge (부분방정 측정에서 센서 및 펄스 분석 알고리즘에 따른 노이즈 제거 연구)

  • Kim, Ji-Hong;Koo, Ja-Yoon;Kim, Jeong-Tae
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.4
    • /
    • pp.183-188
    • /
    • 2006
  • Abstract - In order to investigate the possibility of separating PD(partial discharge) and noises through the pulse analysis by use of a HFCT, pulse shapes measured by a resistive sensor and a HFCT were analyzed and adequate PA(pulse analysis) algorithms were studied. For the purpose, the HFPD detection and PA system has been developed. Also void discharges and air corona were adopted as the artificial defect and noises, respectively. As a result, it is possible to separate partial discharges and noises through the PA method using the $100kHz{\sim}20MHz$ frequency range HFCT. It is expected to apply the developed system to on-site PD measurements for the electric equipments.

A Study on the PD Pulse Analysis and Noise Discrimination Method according to various sensors (센서에 따른 부분방전 펄스 분석 및 노이즈 제거 기법에 대한 연구)

  • Kim, Jeong-Tae;Rhee, Wook
    • Proceedings of the KIEE Conference
    • /
    • 2006.07c
    • /
    • pp.1469-1471
    • /
    • 2006
  • It is very important to discriminate noises such as air corona in measuring on-site partial discharges (PD). Therefore, in order to investigate the possibility of separating PD(partial discharge) and noises through the pulse analysis, pulse shapes measured by a resistive sensor and a HFCT were analyzed and PA(pulse analysis) were performed. For the purpose, the HFPD detection and PA system has been developed. Also void discharges and air corona were adopted as the artificial defect and noises, respectively.

  • PDF

Considerations on the TF Map using Partial Discharge Pulse Characteristics (부분방전 펄스특성을 이용한 TF Map에 대한 고찰)

  • Kim, Jeong-Tae;Kim, Nam-Joon;Chang, Yong-Moo;Kim, Ji-Hong;Koo, Ja-Yoon
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2126-2128
    • /
    • 2005
  • In this paper, it was investigated the applicability of TF analysis for the discrimination of air corona in on-site PD measurement. For the purpose, single and multiple discharges combined with oil discharges and air corona were generated and measured by use of artificial models and HFPD pulse detector. Through the TF analysis, data clusters could be classified each other in the TF Map, even in the case of multiple discharges. Therefore, it is known that TF analysis could be applied for the improvement of on-site PD measurement.

  • PDF

Partial Discharge Measurement for 154kV XLPE Cable Line (154kV XLPE 케이블 실선로 부분방전 검출)

  • Kim, C.S.;Lee, J.S.;Kim, J.C.;Park, C.G.;Seok, K.H.;Kim, W.N.
    • Proceedings of the KIEE Conference
    • /
    • 2004.11a
    • /
    • pp.23-25
    • /
    • 2004
  • HFPD(High Frequency Partial Discharge) measurement has been widely performed to diagnose cable system in the world. Shin-Yeongdeungpo 345kV XLPE line was successfully diagnosed by PD measurement methode last year. Moreover, aged power cable lines which were installed 15 years ago have been tested from this year. In this paper, the result of PD diagnosis for aged 154kV cable line is reported. The PD pattern from TMJ which was monitored by PD measurement system for several days showed typical void pattern. The joint was replaced and voids between semi-conductor layer and insulating layer in the joint was founded.

  • PDF

Filter Test for Partial Discharge Detection of Underground Distribution Cables (지중배전케이블의 PD 검출용 필터 시험 연구)

  • Lee, Yong-Sung;Kim, Jung-Yoon;Lee, Kwan-Woo;Choi, Yong-Sung;Park, Dae-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.07a
    • /
    • pp.215-216
    • /
    • 2005
  • To decrease and remove of much noises that is detected in PD (partial discharge) measuring test. we forced on detection of those. We made W-LC filter for measuring PD. which adapted that to field test. We tested after design laboratory circumstances like field line. and then the phase change properties of detected signal in UHF sensor were measured by Lemke Probe and oscilloscope (TDS-3054. Tektronix). Eventually we checked decrement of noises from experimental result. Also from experimental result at the joint box of 22.9[kV] distribution line. we obtained reasonable data which enable noises to decrease. Hereafter those results will be adapted at ultra-high voltage for trouble prevention and on-line cable watch. diagnosis of those.

  • PDF

An adoption of the HFPD measuring system using directional coupler sensors to XLPE cable & accessories (방향성센서를 이용한 고주파 부분방전 측정시스템의 XLPE 케이블 및 접속함 적용)

  • Yu, In-Kee;Kim, Ki-Young;Jeong, Young-Woo
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1674-1676
    • /
    • 2002
  • In this paper, High Frequency PD measuring system using directional coupler sensors(DCS) is introduced. Especially the principles of the DCS and characteristics of the system are introduced. Evaluation of this system was carried by an adoption to the test circuit of 345kV XLPE $2000mm^2$ cable and EB-A, EB-G, PIJ, PNJ. In the test a PD measurement was carried out without shieldroom and under the on-line state and in the high frequency range at the remote site from the test object. The test result was satisfactory and this is due to the use of DCS and using a high frequency range and specific filter for radio and TV signal and low pass. This system can be used to the test of a new construction of cable and accessories and measuring of long-term deterioration of cable and accessories. And this will bring us the reliability of a power transmission.

  • PDF