• Title/Summary/Keyword: Grounding Electrode

Search Result 154, Processing Time 0.022 seconds

Distribution of Potential Rise as a Function of Shape of Grounding Electrodes

  • Gil, Hyoung-Jun;Choi, Chung-Seog;Kim, Hyang-Kon
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.4
    • /
    • pp.73-79
    • /
    • 2007
  • In order to analyze the potential rise of grounding systems installed in buildings, a hemispherical grounding simulation system was studied. Potential rise was measured and analyzed regarding the shape and distance of the grounding electrodes by using this system. The system was composed of a hemispherical water tank, AC power supply, a movable potentiometer, and test grounding electrodes. The potential rise was measured in real time by the horizontal moving probe of be potentiometer. The test grounding electrodes were fabricated through reducing the grounding electrode installed in real buildings such as the ground rod, grounding grid and so on. The potential rise was displayed in a two-dimensional profile and was analyzed regarding the shapes of the ground electrodes. The potential rise of the grounding grid combined with a ground rod was the lowest of every grounding electrode tested. The proposed results can be applicable to evaluating ground potential rise in grounding systems, and the analytical data can be used to stabilize the electrical installations and prevent electrical disasters.

Presumption for Reduced Scale Model of Mesh Electrod (망상접지전극의 축척모델에 관한 추정)

  • Koh, Hee-Seog;Kim, Ju-Chan;Kim, Sung-Sam;Lee, Chung-Sik;Choi, Jong-Kyu;Ryoo, Hee-Suk
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.330-332
    • /
    • 2002
  • There are a lot errors and little accuracy when calculating the grounding resistance with the transposition methods in the equivalent surface of hemisphere electrode. Therefore we should calculate the grounding resistance by using the mesh factor. In this paper, we would estimated the grounding value of mesh electrode with water tank model & estimation method using the reduced scale ratio of mesh electrode based on the theory of model electrode & proportional factor according to the reduced scale ratio. And also we have confirmed the accuracy of the empirical formula of model electrode by using by regression analysis.

  • PDF

Presumption for Reduced Scale Model of Mesh Electrod (메쉬접지전극의 축척모형에 관한 추정)

  • Koh, Hee-Seog;Kim, Ju-Chan;Lee, Chung-Sik;Choi, Jong-Kyu
    • Proceedings of the KIEE Conference
    • /
    • 2002.06a
    • /
    • pp.29-33
    • /
    • 2002
  • There are a lot of errors and little accuracy when calculating the grounding resistance with the transposition methods in the equivalent surface of hemisphere electrode. Therefore we should calculate the grounding resistance by using the mesh factor, In this paper, we would estimate the grounding value of mesh electrode with water tank model & estimation method using the reduced scale ratio of mesh electrode based on the theory of model electrode & proportional factor according to the reduced scale ratio. And also we have confirmed the accuracy of the empirical formula of model electrode by using the regression analysis.

  • PDF

Transient Grounding Impedance Characteristics of a Copper Rod-type Grounding Electrode used for Electric Distribution Systems Using EDSA Program (EDSA 프로그램을 이용한 배전계통에 사용되는 동봉 접지전극의 과도 접지임피던스 특성)

  • Kim, Kyung-Chul;Oh, Kyung-Hoon;Kim, Min-Sung;Choi, Jong-Kee;Kim, Dong-Myung
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.8
    • /
    • pp.26-32
    • /
    • 2009
  • Grounding insures a reference potential point for electric devices and also provides a law resistance path for fault or transient currents in the earth. The ground impedance as a function of frequency is necessary for determining its performance since fault or transient currents could contain a wide range of frequencies. A copper rod electrode is the most commonly used grounding electrode in electric distribution systems. In this paper, the grounding impedance of copper rods has been measured in frequency raging from 60[Hz] up to 100 [kHz] and an equivalent model of the grounding impedance is identified from the measured values. The grounding impedance under study when a typical lightning surge is injected into the grounding system was simulated numerically and graphically through the use of the EDSA software program.

Study on the Between the Grounding Resistance and Grounding Electrode using Mesh Grounding Electrodes and a Shielding Panel (메쉬접지전극과 차폐패넬을 이용한 접지저항 및 접지전극간의 영향에 관한 연구)

  • Leeg, Chung-sik;Cho, Moon-taek;Na, Seung-kwon
    • Journal of Advanced Navigation Technology
    • /
    • v.19 no.3
    • /
    • pp.230-236
    • /
    • 2015
  • In this paper, the electric potential of electrode surface is investigated by assuming them as two dimensional sets of point current sources. And, the simulated water tank is manufactured as a reduced scale of the earth. Henceforth, the adequate model electrode for test is decided to decrease experimental errors relevant to the limitation of the size of the water tank. The one of important things of this work, the deduction method of the potential interference factor is proposed, which used as the criterion of the potential interference according to the shape of conductors and the laying conditions, when multiple grounding conductors are situated at the same resistance grounding area. Also, the validity of this theory is verified from a numerical simulation of the grounding electrode to be used in experiments, and this study is realized by the verified theory and the simulated experiments.

A study on the characteristic test of the grounding electrodes used in distribution lines (배전용 접지전극의 전극별.공중별 특성시험에 관한 연구)

  • Park, Sang-Man;Park, Jae-Duck;Kang, Moon-Ho;Choi, Jong-Kee;Park, Young-Keun;Shim, Keun-Bo
    • Proceedings of the KIEE Conference
    • /
    • 2005.05b
    • /
    • pp.54-56
    • /
    • 2005
  • On the overhead distribution lines, we generally use a copper rod as a grounding electrode. It is a economical metallic structure. Recently, many new electrodes have been developed and used in the distribution system of KEPCO. Before using new grounding electrode. we need to measure the performance of each electrode for comparative analysis. This report describes the characteristic test of the grounding electrodes used in KEPCO.

  • PDF

Measurement of Grounding Impedances in Large-scale Grounding Electrode Systems (대형접지전극시스템 접지임피던스의 측정)

  • Lee, Kyoung-Hoon;Choi, Jong-Hyuk;Choi, Young-Chul;Lee, Kyu-Sun;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.10a
    • /
    • pp.193-196
    • /
    • 2008
  • In these days, large structures are constructed and bonded with ground grid Because the distances between mesh and auxiliary electrodes are not enough in downtown areas, it is very difficult to measure the ground resistance of large scale grounding electrode systems. Actually the auxiliary electrodes for test are installed in grounding grid. This paper present the experimental results of ground resistance and impedance according to the location of auxiliary electrode. As a result, we get much lower resistances and impedances than real values the auxiliary electrodes are placed in the ground grid. In case that the auxiliary electrodes are located in the ground grid the resistances are very low and reactance only is inductive component.

  • PDF

The Optimization Grounding Analysis for Soil Resistivity (대지저항률에 따른 최적화 접지 해석)

  • Jung, Yeon-Ha;Jang, Tae-Jun;Kwak, Hee-Ro;Roh, Young-Su;Shong, Kil-Mok
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.241-245
    • /
    • 2004
  • The electric safety tends to be more important according to electric facilities's increase and its use in these days. This paper analyzes soil resistivity of two areas in the country using CDEGS(Current Distribution, Electromagnetic Interference, Grounding and Soil Structure, Canada). We designed rod and mesh grounding system and made a comparative study of ground resistance, GPR(Main Electrode Potential Rin), step voltage and touch voltage. Then we could analyz only the safety but also economical efficiency in elocution of grounding. As a result of simulation, ground resistance, GPR(Main Electrode Potential Rise), step voltage and touch voltage became higher in proportion to soil resistivity. Therefore we expect to estimate the propriety of grounding system design through accumulation and analysis of data in consideration of characteristics of soil.

  • PDF

Characteristics of Transient Grounding Impedances of Rod Electrodes (봉상접지극의 임펼스 전류에 대한 과도접지임피던스 특성)

  • Lee, B.H.;Park, J.S.;Yang, J.J.;Lee, S.C.
    • Proceedings of the KIEE Conference
    • /
    • 1997.07e
    • /
    • pp.1645-1647
    • /
    • 1997
  • Electronic circuits are becoming more vulnerable owing to the development of integrated circuit. Computer and info-communication facilities are very sensitive to surges caused by lightning, and they can suffer a malfunction and damage. Recent concern about damage and upset caused by transient overvoltages has focused on surge protection. The most important parameter in surge protection is the transient grounding impedance. In this paper, the transient grounding impedances of a rod electrode have been measured under impulse current waves. Z-t, Z-i and V-i characteristics of the grounding electrode in according to the length of the grounding lead wire were obtained and analyzed.

  • PDF

The Analysis of Structure Grounding Using Reduced Scale Model (축소모델을 이용한 구조체 접지 분석)

  • Gil, Hyoung-Jun;Kim, Hyang-Kon;Han, Woon-Ki;Lee, Ki-Yeon;Choi, Chung-Seog
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2046-2048
    • /
    • 2005
  • This paper deals with ground potential rise of structure grounding electrode when a test current flows through grounding electrode. In order to analyze the potential gradient of ground surface on structure grounding electrode, the reduced scale model has been used. The structures were designed through reducing real buildings and fabricated with four types on a scale of one-one hundred sixty. The supporter was made to put up with weight of structure and could move into vertical, horizontal, rotary direction. When a test current flowed through structure grounding electrodes, ground potential rise was the lowest value at electric cage type(type B). According to resistivity and absorption percentage in concrete attached to structure, the potential distribution of ground surface appeared differently.