• 제목/요약/키워드: Ground heat exchangers

검색결과 97건 처리시간 0.024초

건물의 냉난방 운전을 고려한 3차원 동적 지중 열교환기 열해석 모델 (Three-dimensional Equivalent Transient Ground Heat Exchanger Thermal Analysis Model by Considering Heating and Cooling Operations in Buildings)

  • 백승효
    • 토지주택연구
    • /
    • 제9권4호
    • /
    • pp.25-32
    • /
    • 2018
  • Application of geothermal energy in buildings has been gaining popularity as it provides the benefits of both heating and cooling a building. Among the various types of geothermal energy systems, ground-coupled heat pump system is the most commonly applied one in South Korea. A ground heat exchanger plays an important role as a heat source in winter and a heat sink in summer. For the stable operation of a ground-coupled heat pump system, a ground heat exchanger should be sized so that it provides sufficient heating and cooling energy. Heating and cooling energies generated in ground heat exchangers mainly depend on the temperature difference between the heating medium in ground heat exchangers and the surrounding ground. In addition, the performance of ground heat exchangers influences the change in ground temperature. Therefore, it is necessary to consider this interrelation between the change in the ground temperature and the performance of ground heat exchanger for an accurate estimation of its performance. However, previous thermal analysis models for ground heat exchangers are not competent enough to allow a complete understanding of this interrelation. Therefore, this study proposes a three-dimensional equivalent, transient ground heat exchanger analysis model. First, a previous thermal analysis model for ground heat exchangers, including an analytical model, a g-function, and a numerical model are analyzed. Next, to overcome the limitations of the previous models, a three-dimensional equivalent, transient ground heat exchanger model is proposed. Finally, this study validated the proposed model with the measurement data of the thermal response test, sandbox test, and TRNSYS DST model. All validation results showed a good agreement. These findings helped us to investigate the thermal performance of ground heat exchangers more accurately than the analytical models, and faster than the numerical models. Furthermore, the proposed model contributes to the design of ground heat exchangers by considering the different operation conditions of buildings.

에너지파일과 에너지슬래브 적용 지열원 열펌프 시스템의 일일 냉방 운전 특성 비교 (Daily Cooling Performance Comparison of a Geothermal Heat Pump System between Energy-Pile and Energy-Slab)

  • 최종민;박용정;강신형
    • 한국지열·수열에너지학회논문집
    • /
    • 제8권3호
    • /
    • pp.29-35
    • /
    • 2012
  • Geothermal heat pump system has been spotlighted as an efficient building energy system, because it has great potentials for reducing energy in building air conditioning and reducing $CO_2$ emissions. However, higher initial cost is a barrier to the promotion of its use. Energy-pile and energy-slab are known as low cost ground heat exchangers comparing with conventional ground heat exchangers, because they utilize building structures as ground heat exchangers. This paper presents the daily cooling performance of a geothermal heat pump system with energy-pile and energy-slab. The energy-piles and the energy-slabs are connected to heat pump units in parallel. The cooling capacity of the system was nearly constant due to the stability of the ground heat exchangers. The stability of the energy-pile was a little higher than that of the energy-stab as a heat sink.

수평형 지중열교환기의 열전달 성능에 관한 연구 (A Study on Heat Transfer Performance of Horizontal Ground Heat Exchanger)

  • 정민호;박성룡;나호상;백영진;윤형기;장기창
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2005년도 춘계학술대회
    • /
    • pp.684-687
    • /
    • 2005
  • Ground source heat pump systems are used for heating, ventilating and air-conditioning systems in commercial buildings, schools, and factories because of low operating and maintenance costs. These systems use the earth as a heat source in heating mode and a heat sink in cooling mode. Ground heat exchangers are classified by a horizontal type and vertical type according to the installation method. A horizontal type means that a heat exchanger is laid in the trench bored in 1.2 to 1.8 m depth. The solar heat and the rainwater are affected by the performance of heat exchanger and causes mutual influence among heat exchangers. In this study, to evaluate the performance of straight type, slinky type, and spiral type of horizontal ground heat exchangers designed on 1 RT scale, test sections are buried on the earth and experimental apparatus is installed. Therefore the performance of these is estimated.

  • PDF

지중 열교환기용 시멘트 그라우트에 관한 연구 (A study on cement-based grout for ground heat exchangers)

  • 이동주;백환조;김경만
    • 산업기술연구
    • /
    • 제31권B호
    • /
    • pp.27-36
    • /
    • 2011
  • In this paper, the applicability of cement grout has been studied as an alternative to bentonite grout for backfill ground heat exchangers. To provide an optimal mixture design, the thermal conductivity of cement grout and bentonite grout with various mixture ratios were experimentally evaluated and compared. Numerical analyses using Fluent(FVM program) were applied to compare the thermal transfer efficiency of the cement grout with that of the bentonite grout used in the construction. Also the effective ground thermal conductivity was measured by In-situ thermal response test. The results showed that the thermal efficiency of the cement grout was better than the bentonite grout. Consequently, the cement grout could be an alternative with more thermal efficiency to bentonite grout for ground heat exchangers.

  • PDF

지중열교환기용 고성능 시멘트 그라우트 개발 (Development of high-performance cement grout for ground heat exchangers)

  • 이동철;양희정;전중규;서신석;최용민
    • 한국지열·수열에너지학회논문집
    • /
    • 제7권1호
    • /
    • pp.10-16
    • /
    • 2011
  • Performance of ground-source heat pumps (GSHPs) is mainly affected by ground heat exchangers which makes up more than 40% of construction cost. Exact construction and grout as backfill are important, because it is difficult to repair after being installed. As grout materials, bentonite grout material and cement material are used In this paper, thermal conductivity according to mix proportion of cement grout has been experimentally studied. Some variables were set to evaluate thermal conductivities according to change in cement content, unit water ratio, mass per volume of fresh mortar, and aggregate types. From the experimental analysis, high performance cement grout has been proposed.

불포화 지반 조건을 고려한 파일 매입형 열교환기의 수치해석 (Numerical Simulation of Ground Heat Exchanger Embedded Pile Considering Unsaturated Soil Condition)

  • 최정찬;이승래
    • 한국지반공학회:학술대회논문집
    • /
    • 한국지반공학회 2010년도 춘계 학술발표회
    • /
    • pp.213-220
    • /
    • 2010
  • This study presents a numerical simulation model of vertical ground heat exchangers, considering unsaturated hydro static ground conditions induced by the ground water table fluctuation. Heat transfer in ground and grout is modeled by a 3-D FEM transient conductive heat transfer model, where heat transfer between circulating fluid and heat exchanging pipe is treated as 1-D quasi steady state forced convective elements. To take into account the unsaturated ground condition, soil thermal conductivity and heat capacity which are dependent on the matric suction are applied to ground elements. Parametric studies considering various ground water table conditions are conducted to investigate the influence of unsaturated hydro static ground condition on the mean heat exchange rate of ground heat exchanger. Simulation results considering water table fluctuation show 60~100% of mean heat exchange rate for a saturated soil condition and 125~208% of that for a dry soil condition. Thus consideration of unsaturated soil condition is substantially recommended for more accurate design and performance evaluation for ground heat exchangers.

  • PDF

수평형 지중 열교환기 시스템의 시공비 및 영향인자 분석 (Analysis of Construction Cost and Influence Factors on Horizontal Ground Heat Exchangers)

  • 윤석;이승래
    • 신재생에너지
    • /
    • 제10권3호
    • /
    • pp.6-13
    • /
    • 2014
  • This paper presents a computational study of thermal performance and construction cost of horizontal ground heat exchangers (GHEs). GLD (ground loop design) simulations of various type of GHEs were carried out. Construction costs were also calculated based on standard estimating, and compared with vertical type GHE system. Besides that, dummy regression analysis was conducted to study the influence of design parameters on the simulation results in horizontal ground heat exchanger system.

제주도에 설치된 지열 열펌프 시스템용 제주형 지중열교환기의 열특성 연구 (A Study on the Thermal Characteristics of Jeju type Ground Heat Exchanger for Ground Source Heat Pump System applied to Jeju Island)

  • 김민준
    • 한국산학기술학회논문지
    • /
    • 제21권2호
    • /
    • pp.32-38
    • /
    • 2020
  • 본 연구는 제주도에 설치된 제주형 지중열교환기의 열적 특성을 분석하기 위해서 시험 방법 및 평가 방법을 정립하고, 열응답시험 (TRT)을 통하여 다양한 지역에 설치된 지중열교환기의 지중온도와 열적 특성을 분석하였다. 제주도는 화산암반층으로 이루어져 지하수의 유동이 잘 발달되어 있으며, 제주형 지중열교환기는 보어홀을 굴착 한 이후에 지하수 수위로 부터 30 m 까지 지중열교환기를 설치할 수 있다. 지중열교환기는 여러개의 파이프가 보어홀 내부에 삽입되는 구조로 되어있다. 제주형 지중열교환기의 특성을 살펴보기 위해 제주도 관내 4곳 (표선, 제주, 남원, 한림)에 설치된 지중열교환기에 대한 시험을 수행하였다. 분석결과 제주형 지중열교환기의 경우 열교환기에 열량을 투입 후 1 ~ 3시간 안에서 지중 순환수 온도가 안정화 되었으며, 열교환기가 설치된 지역에 따라서 투입열량에 따른 지중 순환수 온도 상승이 다르게 나타났다. 한림의 경우 지중열교환기 용량이 73.4 kW (냉방) / 82.8 kW (난방)로 가장 높게 나타났으며, 제주의 경우 34.1 kW (냉방) / 23.3 kW (난방)로 가장 작게 계산되었다.

부하추종형 고효율 지열히트펌프 시스템에 관한 연구 (1) (A Study on the High Efficiency Ground Source Heat Pump System (1))

  • 고득용;김욱중;최상규;장기창
    • 신재생에너지
    • /
    • 제1권4호
    • /
    • pp.30-37
    • /
    • 2005
  • Cycle simulation of Ground Source Heat Pump[GSHP] system was carried out to determine the design specification of basic components such as turbo compressor and heat exchangers. Part load operation characteristics of the designed GSHP system was estimated using the compressor and heat exchanger performance data. A 50RT class turbo compressor for GSHP system is now under development, in which R134a refrigerant is adopted as working fluid. The compressor with variable cascade diffusers is designed to work both in cooling and heating modes so that it can actively keep up with the climate change with high efficiency. The normal running speeds of the compressor are 59000rpm for heating mode and 70000rpm for tooling mode respectively. It has two identical impellers at both ends of the rotor so as to minimize aero-induced thrust force effectively. GSHP system was coupled with a vortical type heat exchanger, and heat gain and heat loss from ground were evaluated per a bore hole. For the optimal integration of the heat pump system, its header for circulating fluid was combined with the ground heat exchangers in parallel and series configuration.

  • PDF

GSHP용 수직형 지중열교환기의 열전달 성능에 관한 연구 (A Study on Heat Transfer Performance of Vertical Ground Heat Exchanger of GSHP(Ground Source Heat Pump))

  • 정민호;장기창;나호상;백영진;박성룡;유성연
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2007년도 춘계학술대회B
    • /
    • pp.2102-2107
    • /
    • 2007
  • GSHP systems are used for air-conditioning systems in commercial buildings, schools, and factories because of low operating and maintenance costs. These systems use the earth as a heat source in heating and a heat sink in cooling mode. Ground heat exchangers are classified by a horizontal and vertical type according to the installation method. Vertical type is usually constructed by placing small diameter high density polyethylene tube in a vertical borehole. Vertical tube sizes range from 20 to 40 mm nominal diameter. Borehole depth range between 100 and 200 m depending on local drilling conditions and available equipment. In this study, to evaluate the performance of single u-tube with bentonite grouting, single u-tube with broken stone grouting and double u-tube bentonite grouting of vertical ground heat exchangers, test sections are buried on the earth and experimental apparatus is installed. Therefore the heat transfer performance and pressure loss of these are estimated.

  • PDF