• Title/Summary/Keyword: Gas-Insulated Transformer

Search Result 52, Processing Time 0.023 seconds

A comparative study of the PD pattern analysis based on PRPD and CAPD for the diagnosis of Gas Insulated Transformer (GITr(Gas Insulated Transformer) 내부에 발생되는 PD 신호의 패턴분석을 위한 PRPD와 CAPD 적용 결과 비교)

  • Jung, Seung-Yong;Lim, Yun-Sok;Koo, Ja-Youn;Chang, Yong-Moo;Kang, Chang-Won;Lee, Yung-Sang
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2060-2062
    • /
    • 2005
  • Partial Discharge (PD) phenomena occurred by different nature of insulating defects has been regarded as a random process by which Phase Resolved Partial Discharge Analysis (PRPDA) has been proposed and then commercially accepted for the diagnosis of the power apparatus since more than three decades. Moreover, for the same purpose, a novel approach based on the Chaotic Analysis(CAPD) has been proposed since 2000, in which PD phenomena is suggested to be considered as a deterministic dynamical process. In this work for the diagnosis of GITr, four different types of specimen were fabricated as a model of the possible defects that might possibly cause its sudden failures such as turn to turn insulation, inter coil insulation, free moving particle and protrusion. For this purpose, these defects are introduced into the GITr mock-up and experimental investigations have been carried out in order to analyze the related PD patterns by means of both PRPDA and CAPD respectively and then their comparisons are made systematically.

  • PDF

The Analysis of Insulation Properties with Electron Collision Processes on SF6 Mixture Gases (전자충돌과정을 통한 SF6 혼합기체의 절연특성 분석)

  • So, Soon-Youl
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.59 no.2
    • /
    • pp.197-201
    • /
    • 2010
  • $SF_6$ gas would be used in power transformer, GIS (Gas insulated switchgear) and so on because of its electrically superior insulation and chemically stable structure. Recently, the reduction of $SF_6$ is required to avoid global warming and the researches on the dilution of $SF_6$ with other gases have been carried out. $SF_6$ mixture gases with $N_2$ and $C_xF_y$ have drawn attention to the synergy effect. However, in order to understand the mechanism of the synergy effect, it is important to analyze and evaluate properties of mixture gases quantitatively. In this paper, we investigated the mechanism of synergy effect from electron collision processes and electron energy distribution by solving Boltzmann equation with propagator method. Three kinds of gases for dilution of $SF_6$ ($SF_6/N_2$, $SF_6/CF$4 and $SF_6/C_4F_8$) are considered in this simulation. On the properties of $SF_6/N_2$ mixture gas, the variation of reduced electric field was shown highly within 0%~40% mixtures of $SF_6$. And the more low-level electron energy has been distributed, the higher insulation capability has appeared.

EMTP Analysis for Ferroresonsnce of Gas Insulated Switchgear (가스절연개폐장치(GIS) 철공진(Ferroresonance) EMTP해석)

  • Chung, Y.H.;Lee, D.S.;Kim, J.B.;Lee, H.S.
    • Proceedings of the KIEE Conference
    • /
    • 2008.11a
    • /
    • pp.366-367
    • /
    • 2008
  • This paper deal with the study of the phenomenon of Ferroresonance in the 170kV Gas Insulated Switchgear(GIS). The Electromagnetic Transient Program(EMTP) was used to simulate the phenomenon of Ferroresonance and conducted the study of the transient over-voltage. An example power system, used in this study, have an accident that the ferroresonance phenomenon happens at MOFVT(Voltage Transformer). The simulation results notices that the secondary part of VT has to be connected by ferroresonance suppressor when the circuit breaker connected with grading capacitor is switched off.

  • PDF

The Lightning Current Parameters that Impact on the Surge Analysis of the EHV Gas Insulated Substation by EMTP

  • Shim Eung-Bo;Han Sang-Ok
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.5C no.1
    • /
    • pp.1-7
    • /
    • 2005
  • This paper describes the lightning surge analysis model of extra high voltage GIS using EMTP. Various lightning current parameters were investigated in order to confirm the impact on the lightning surge analysis such as lightning current amplitude, waveform, size of GIS, tower footing resistance and surge arresters. The multi-story tower model and EMTP/TACS model were introduced for the simulation of dynamic arc characteristics. The margin between the maximum overvoltage and BIL of the GIS was about 10 percent and the margin between the maximum overvoltage and BIL of the transformer was 21 percent.

A Study on the UHF PD Sensor and Novel Pattern Analysis Technology for Diagnosis of the High Power Apparatus (초고압 전력기기 진단을 위한 UHF PD 센서 및 패턴분석 기술에 관한 연구)

  • 강원종;이창준;강윤식;이희철;박종화
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.2
    • /
    • pp.83-90
    • /
    • 2004
  • This paper describes investigations of the UHF(Ultra High Frequency) PD(Partial Discharge) measuring technology designed for monitoring of PD in high power apparatus. Based on the spiral antenna theory, the hole type sensor for GIS with metal flange spacer and injection type sensor for oil filled transformer are developed. The experimental results show measurement characteristics of the PD sensor for several artificial defects in gas-insulated system(GIS) and oil transformer. Moreover, we proposed the new $\phi$-f-q method for the purpose of condition assessment of high power apparatus.

The Analysis of $SF_6/N_2$ Plasma Properties Under the Atmosphere Pressure ($SF_6/N_2$ 혼합기체의 대기압 플라즈마 특성 분석)

  • So, Soon-Youl;Lee, Jin
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.58 no.4
    • /
    • pp.516-520
    • /
    • 2009
  • Atmosphere Plasmas of Gas Discharge (APGD) have been used in plasma sources for material processing such as etching, deposition, surface modification, etc. This study is to investigate and understand the fundamental plasma discharge properties. Especially, $SF_6/N_2$ mixed gas would be used in power transformer, GIS (Gas insulated switchgear) and so on. In this paper, we developed a one dimensional fluid simulation model with capacitively coupled plasma chamber at the atmosphere pressure (760 [Torr]). 38 kinds of $SF_6/N_2$ plasma particles which are an electron, two positive ions (${SF_5}^+$, ${N_2}^+$), five negative ions (${SF_6}^-$, ${SF_5}^-$, ${SF_4}^-$, ${F_2}^-$, ${F_1}^-$), thirty excitation and vibrational particles for $N_2$ were considered in this computation. The $N_2$ gases of 20%, 50%, 80% were mixed in $SF_6$ gas. As the amount of $N_2$ gas was increased, the properties of electro-negative plasma moved toward the electro-positive plasma.

Temperature Rise Prediction of GIS Bus Bar Considering Thermal Flow (열유동을 고려한 GIS 모선의 온도상승 예측)

  • Kim, Joong-Kyoung;Oh, Yeon-Ho;Lee, Ji-Yeon;Hahn, Sung-Chin
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.4
    • /
    • pp.742-747
    • /
    • 2009
  • Many works on the temperature distribution of power apparatus have usually done by coupled magneto-thermal analysis. Such a method can not consider the internal gas or oil flow in the power apparatus such as gas insulated switchgear, GIS bus bar, and power transformer. Moreover it can not show the internal temperature distribution of the power apparatus exactly. This paper proposes a coupled magneto-thermal-flow analysis considering Navier-Stokes equations. The convection heat transfer coefficient is calculated analytically by applying Nusselt number for natural convection and is applied to the boundary condition of proposed method. Temperature distribution of the GIS bus bar model considering thermal flow is obtained by the proposed method and shows good agreement with the experimental data.

Lightning protection in an 154kV GIS connected by oil-filled cables (O.F. Cable에 연결된 154kV GIS의 뇌보호)

  • 정태호
    • 전기의세계
    • /
    • v.29 no.5
    • /
    • pp.315-320
    • /
    • 1980
  • It has been appeared and widely used today SF6 Gas Insulated Substation(Hereafter called GIS) for the power supply to the densely populated area due to the superior insulation withstand ability of SF6 Gas. And to maximize the compact effect of this substation, it is normal practice to connect underground cables. If it is possible to elieminate the redundant lightning arresters using the physical characterestics of travelling waves in underground cables, economical advantages can be obtained together with easy maintenances. It is presented in this paper the possiblity of eliminating the transformer protection lightning arresters under some conditions for the 154kV GIS's (BIL:750kV) which Korea Electric Co. plans to construct using the general purpose digital computer program.

  • PDF

A Comparison of Signal Processing Techniques in Optical Current Sensor for GIS

  • Kim, Young-Min;Park, Jung-Hwan;Jee, Seung-Wook;Lee, Kwang-Sik;Kim, Jung-Bae;Park, Won-Zoo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.9
    • /
    • pp.103-109
    • /
    • 2006
  • This research is contents about output characteristic of optic current sensor that use faraday effect. optic current sensor used in an experiment is consisted of three parts.(1) Source of light used laser diode of 1310[nm].(2) Sensor section manufactured circularly according to gas insulated switchgear. And $9/125[{\mu}m]$ standard single mode optical fiber for communication was installed winding 20 [turn] on sensor section core surroundings of diameter 31 [cm].(3) Electrical signal of PD(Photo detector) is collected using NI company's 16bit DAQ board via terminal block. Collected data analyzed by different three signal processing methods. NI company's $Labview^{TM}$ was used to signal processing software. As a result, In signal processing of optic current sensor, we could know that noise greatly more influences the error generation than fluctuation of light intensity. also, 1 class CT(current transformer) manufacture that have error rate less than 1[%] was available by removing these