• Title/Summary/Keyword: Gas absorption refrigeration

Search Result 44, Processing Time 0.022 seconds

Study on the Cavitation Damage of Cupronickel(70/30) Tube for Gas Absorption Refrigeration Machine

  • Lim, Uh-Joh;Jeong, Ki-Cheol;Yun, Byoung-Du
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.28 no.2
    • /
    • pp.332-337
    • /
    • 2004
  • The use of gas absorption refrigeration machine has considerably increased because of the shortage of the electric power in the summer and the regulation of freon refrigerant. Gas absorption refrigeration machine consists of a condenser, a heat exchanger. supplying pipes, a radiator etc, This system is likely to be corroded by acid. dissolved oxygen and gases, Cavitation erosion-corrosion by flow velocity of cooling water may happen in absorption refrigeration machine. In these cases. erosion and corrosion occur simultaneously. Then, it makes a serious damage with synergy effect. Therefore, this paper was studied on the cavitation damage of cupronickel(70/30) tube for gas absorption refrigeration machine, In the $30^{\circ}C$ tap water, linear polarization test and anodic polarization test were carried out for copper(C1220T-OL) and cupronickel(70/30) tube. Also, cavitation erosion-corrosion behavior of cupronickel (70/30) tube was considered, The main results are as following: (1) In the linear test, the corrosion current density of cupronickel(70/30) is higher than that of copper. (2) The erosion-corrosion rate of cupronickel(70/30) displayed later tendency than that of copper by vibratory cavitation in cooling water. (3) In cooling water, the progress mechanism of erosion-corrosion rate of copper and cupronickel(70/30) follows a pattern of incubation, acceleration, attenuation and a steady state period.

The Study on Corrosion Characteristics of Heat Exchanger Tube for Gas Absorption Refrigeration & Hot Water System (가스흡수식 냉온수기 열교환기용 세관의 부식특성에 관한 연구)

  • Jeong Ki Cheol
    • Journal of the Korean Institute of Gas
    • /
    • v.6 no.1 s.17
    • /
    • pp.92-97
    • /
    • 2002
  • This paper was studied on corrosion characteristics of gas absorption refrigeration & hot water system using $LiBr-H_2O$ working fluids. In the $62\%$ lithium bromide solution at $60^{\circ}C$, polarization test of Cu, $10\%$ cupronickel($90-10\%$ Cu-Ni) and $30\%$ cupronickel($70-30\%$ Cu-Ni) tube was carried out. And polarization behavior, polarization resistance characteristics, open circuit potential, anodic polarization of heat exchanger tube for gas absorption refrigeration & hot water system were considered. The main results are as following: 1) Polarization resistance of heat exchange tubes appears high in order of $30\%$ cupronickel tube > $10\%$ cupronickel tube > Cu tube. B) Open circuit potential of cupronickel tube is more noble than that of Cu tube, and corrosion current density of cupronickel is controlled than Cu tube. 3) Potential of passive region of $30\%$ cupronickel tube is more wide than that of $10\%$ cupronickel tube, and the passivation critical current of $30\%$ cupronickel tube is lower than that of $10\%$ cupronickel tube.

  • PDF

A Study on the Characteristics of Local Corrosion for Gas Absorption Refrigeration and Hot Water Systems in LiBr-$H_2O$ Working Fluids (LiBr작동유체 중에서 가스흡수식 냉온수기의 국부부식 특성에 관한 연구)

  • Uh- Joh Lim;Ki-Cheol Jeong;Byoung-Du Yun
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.27 no.6
    • /
    • pp.714-720
    • /
    • 2003
  • Due to the electric power shortage in summer season and regulation of freon refrigerant, the application of gas absorption refrigeration and hot water systems are considerably increasing trend. But, this system consists of condenser, heat exchanger, supply pipe and radiator etc. which are easily corroded by acidity and dissolved oxygen and gases. In result, this system occurs scale attachment and corrosion damage like pitting and crevice corrosion. In this study, electrochemical polarization test of heat exchanger tubing material (copper, aluminium brass, 30% cupronickel(30% Cu-Ni)) was carried out in 60% lithium bromide solution at $95^{\circ}C$. As a result of polarization test, corrosion behavior by impressed potential and local corrosion. such as galvanic corrosion, pitting corrosion behavior, of tubing materials was investigated. The main results obtained are as follows: (1) The effect of pitting and crevice corrosion control of 30% cupronickel in 60% LiBr solution at $95^{\circ}C$ is very excellent. (2) Dissimilar metal corrosion of 30% cupronickel coupling to aluminium bronze is the most sensitive. (3) Current density behavior of tube materials by impressed potential is high in order of copper > aluminium brass > 30% cupronickel.

Effects of Charging Conditions on Evaporating Temperature for Diffusion Absorption Refrigerator (확산형 흡수식 냉장고에서 작동매체 충진조건이 증발온도에 미치는 영향)

  • 김선창;김영률;백종현;박승상
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.10
    • /
    • pp.828-834
    • /
    • 2003
  • A diffusion absorption refrigerator is a heat-generated refrigeration system. It uses a three-component working fluid consisting of the refrigerant (ammonia), the absorbent (water) and the auxiliary gas (hydrogen or helium). In this study, experimental investigations have been carried out to examine the effects of charging conditions of working fluids on the evaporating temperature for diffusion absorption refrigerator. Experimental parameters considered in the present experiments are charging concentration, solution charge and system pressure determined by auxiliary gas charged. As a result, in the charging condition of 35% of concentration and 20 kg$_{f}$cm$^2$ of system pressure, the system has the lowest evaporating temperature. It was found that there exists a minimum value of solution charge for the operation of diffusion absorption refrigerator.r.

Analysis of Absorption Refrigeration Cycles to Utilize Treated Sewage (하수처리수이용 흡수식냉동사이클의 해석)

  • Lee, Y.H.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.8 no.2
    • /
    • pp.288-298
    • /
    • 1996
  • The gas-fired absorption refrigeration system to utilize treated sewage is available for environmental protection and energy conservation. Simulation analysis on the double-effect absorption refrigeration cycles with parallel or series flow type has been performed. The working fluid is Lithium Bromide and water solution. The main purpose of this study is evaluating the possibilities of effective utilization of treated sewage as a cooling water for the absorber and condenser. The efficiency of a couple of cycles has been studied and simulation results show that higher coefficient of performance could be obtained for parallel flow type. The other purpose of the present study is to determine the optimum designs and operating conditions based on the operating constraints and the coefficent of performance in the paralledl flow type.

  • PDF

Cycle Analysis of Diffusion Absorption Refrigerator (확산형 흡수식 냉장고의 사이클 해석)

  • 김선창;김영률;백종현;박승상
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.10
    • /
    • pp.817-824
    • /
    • 2002
  • A diffusion absorption refrigerator is a heat-generated refrigeration system. It uses a three-component working fluid consisting of the refrigerant (ammonia), the absorbent (water) and the auxiliary gas (typically hydrogen). This system has no moving parts and the associated noise and vibration. In this study, the operating characteristics of diffusion absorption refrigerator are investigated through cycle modeling and simulation. System parameters considered in this study are the charged concentration of ammonia aqueous solution, the concentration difference between absorber inlet and outlet and the system pressure determined by the amount of auxiliary gas charged. It was found that there exists a critical value of concentration difference that maximizes the refrigerating capacity. And the lower the system pressure, the higher the refrigerating capacity.

The Effect of LiBr Concentration on Corrosion of Absorption Refrigeration Systems Using $LiBr-H_2O$ Working Fluids ($LiBr-H_2O$계 흡수식냉동기의 부식에 미치는 LiBr 농도의 영향)

  • Lim Uh Joh;Jeong Ki Cheol
    • Journal of the Korean Institute of Gas
    • /
    • v.5 no.4 s.16
    • /
    • pp.33-39
    • /
    • 2001
  • This paper was studied on corrosion behavior of absorption refrigeration systems using $LiBr-H_2O$ working fluids. In the various concentration of lithium bromide solution, polarization test of SS 400, Cu(C1220T-OL) and Al-Ni bronze is carried out. And the corrosion behavior of materials forming absorption refrigeration systems is investigated. The main results are as following: 1) As concentration of lithium bromide solution increases, polarization resistance of materials of each kinds is low. And open circuit potential becomes less noble, the corrosion current density is high drained 2) Open circuit potential of SS 400 is less noble than that of Cu and Al-Ni bronze, corrosion current density of SS5 400 is high drained than that of Cu and Al-Ni bronze. 3) Anodic polarization of Cu and Al-Ni bronze in $62\%$ LiBr solution continues the active state. that of Cu and Al-Ni bronze in the natural sea water maintains the active state and the critical current for passivation appears.

  • PDF

Characteristic Analysis of Double Effect Absorption Refrigeration Machine using $H_{2}O/LiBr+HO{(CH_{2})}_{3}OH$ ($H_{2}O/LiBr+HO{(CH_{2})}_{3}OH$를 이용한 2중 효용 흡수식 냉동기 특성해석)

  • 문춘근
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.22 no.6
    • /
    • pp.792-799
    • /
    • 1998
  • Further improvement of existing $H_{2}O/LiBr$ absorption refrigeration machine is absolutely neces-sary to promote the utilization of gas-cooling system Among various methods to improve the per-formance of the absorption refrigeration machine this research has focused on the use of a new working fluid that has better properties than the existing $H_{2}O/LiBr$ working fluid. In the series of the research, $H_{2}O/LiBr+HO{(CH_{2})}_{3}OH$ system was selected as the most promisable candidate. The absorption refrigeration machine is water-cooled double-effect, $H_{2}O/LiBr+HO{(CH_{2})}_{3}OH$ sys-tem with series flow type. In this study we found out the characteristic of new working solution through the cycle simulation and compared the result with that of LiBr solution to evaluate. Theoptimum designs and operating conditions were determined based on the operating constraints and the coefficient of performance. Results demonstrate that new working fluid subsrantially increases COP by as much as 10% and has a wider working range with 8% higher crystallization limits compared to the conventional $H_{2}O/LiBr$.

  • PDF

Characteristic analysis of air-cooled absorption refrigeration machine (공냉식 흡수식 냉동기의 특성 해석)

  • Kwon Oh-Kyung;Moon Choon-Geun;Yang Young-Myung;Yu Sun-Il;Yoon Jung-In
    • 한국가스학회:학술대회논문집
    • /
    • 1998.09a
    • /
    • pp.249-254
    • /
    • 1998
  • This paper describes the study of developing air-cooled absorption system which uses a new working solution instead of LiBr solution to improve the performance of system. The absorption chiller-heater considered was an air-cooled, double-effect, $H_2O/LiBr+HO(CH_2)_3$ system of parallel flow type. In this study, we found out the characteristic of new working solution through the cycle simulation and compared the result that of LiBr solution to evaluate. The new working fluid has a wider working range with $8\%$ higher crystallization limit at the saturated refrigerant pressure of 0.8kPa. The optimum designs and operating conditions of air-cooled absorption system were suggested based on this cycle simulation analysis. It was demonstrated that new working fluid substantially improves the performance of the absorption refrigeration machine and is expected to increase the COP by as much as $5\%$.

  • PDF

Integral Analysis of the Effects of Non-absorbable gases on the Heat Mass Transfer of Laminar Falling Film

  • Kim, Byong-Joo
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.6
    • /
    • pp.56-66
    • /
    • 1998
  • The absorption process of water vapor in a liquid film is an important process in LiBr-Water absorption system. The composition of the gas phase, in which a non-absorbable gas is combined with the absorbate, influences the transport characteristics. In the present work, the absorption processes of water vapor into aqueous solutions of lithium bromide in the presence of non-absorbable gas are investigated. The continuity, momentum, energy and diffusion equations for the solution film and gas are formulated in integral forms and solved numerically. It is found that the mass transfer resistance in gas phase increases with the concentration of non-absorbable gas. However the primary resistance to mass transfer is in the liquid phase. As the concentration of non-absorbable gas in the absorbate increases, the interfacial temperature and concentration of absorbate in solution decrease, which results in the reduction of absorption rate. The reduction of mass transfer rate is found to be significant for the addition of a small amount of non-absorbable gas to the pure vapor, especially at the outlet of tube where the non-absorbable gas accumulates. At higher non-absorbable gas concentration, the decrease of absorption rate seems to be linear to the concentration of non-absorbable gas.

  • PDF