Characteristic analysis of air-cooled absorption refrigeration machine

공냉식 흡수식 냉동기의 특성 해석

  • Published : 1998.09.01

Abstract

This paper describes the study of developing air-cooled absorption system which uses a new working solution instead of LiBr solution to improve the performance of system. The absorption chiller-heater considered was an air-cooled, double-effect, $H_2O/LiBr+HO(CH_2)_3$ system of parallel flow type. In this study, we found out the characteristic of new working solution through the cycle simulation and compared the result that of LiBr solution to evaluate. The new working fluid has a wider working range with $8\%$ higher crystallization limit at the saturated refrigerant pressure of 0.8kPa. The optimum designs and operating conditions of air-cooled absorption system were suggested based on this cycle simulation analysis. It was demonstrated that new working fluid substantially improves the performance of the absorption refrigeration machine and is expected to increase the COP by as much as $5\%$.

Keywords