• Title/Summary/Keyword: Gas Insulation Switchgear

Search Result 87, Processing Time 0.03 seconds

A Study on Dielectric Strength and Insulation Property of High Voltage Switchgear Applied Dry Air Gas (Dry Air Gas를 적용한 초고압 Switchgear 절연특성연구)

  • Jeong, D.H.;Chung, Y.H.;Seo, K.B.;Kim, T.H.;Kim, J.B.;Lee, H.S.
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.10
    • /
    • pp.1731-1737
    • /
    • 2008
  • This paper present the fundamental insulation characteristics of Dry Air gas and insulation coating in high voltage power apparatus. It is known that the dielectric strength. of Dry Air is approximately one-third that of SF6 gas. we attempt that the insulation coating and dry air gas have replaced the SF6 gas as insulation of the switchgear. We proposed the dry air insulated switchgear(DAIS) for High Voltage apparatus. To acquire technology of insulation characteristic improvement made standards for complex insulation structure and conducted simulations and experiments

Review of Insulation Performance in Synthetic Air and Dry Air for High Voltage Equipment in Distribution Class (배전급 전력설비를 위한 친환경 가스의 절연성능검토)

  • Lim, Dong-Young;Choi, Eun-Hyeok;Choi, Byoung-Ju;Choi, Sang-Tae;Lee, Kwang-Sik;Bae, Sungwoo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.12
    • /
    • pp.33-39
    • /
    • 2015
  • This paper examines the insulation performance of synthetic air and dry air. This examination was conducted based on dielectric strength in uniform and non-uniform field, electric field distribution by interior structure and defects in gas insulation switchgear (GIS) and insulation performance in different temperatures. From this review, it was found that eco-insulation gas required to possess low moisture content for power equipment in the distribution class. The results of this paper are valuable to ensure the insulation design and insulation reliability of GIS using air.

Insulation Characteristics of Dry-air Insulated Switchgear for 72.5 kV Wind Power Generation (72.5 kV 풍력 발전용 Dry-air Switchgear의 절연 특성)

  • Chan-Hee Yang;Jin-Seok Oh;Hee-Tae Park;Young-il Kim
    • Journal of Wind Energy
    • /
    • v.15 no.2
    • /
    • pp.5-9
    • /
    • 2024
  • This paper describes the insulation breakdown characteristics of 72.5 kV dry-air insulated switchgear under development for installation in a wind power generator when a lightning impulse voltage is applied. For this study, the weak point of insulation due to the electric field concentration of the switchgear's internal shape was identified by finite element method (FEM) analysis, and the shape was actually simulated to measure and analyze the polarity of the lightning impulse voltage and the insulation breakdown characteristics according to the gas pressure at dry-air pressures of 0.1 Mpa to 0.45 Mpa. This study derives the maximum electric field with a 50 % discharge probability for each switchgear internal insulation vulnerable point based on the actual test and electrical simulation, which will be useful as reference data for supplementing and changing insulation design in the future.

Surface Flashover Characteristics on Poor Contact in N2/O2 Mixture Gas under Non-Uniform Field (불평등 전계 중 불량 접촉갭에 관한 N2/O2 혼합가스의 연면플래쉬오버특성)

  • Lim, Dong-Young;Choi, Eun-Hyeok;Choi, Sang-Tae;Choi, Byoung-Ju;Lee, Kwang-Sik;Bae, Sungwoo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.8
    • /
    • pp.63-69
    • /
    • 2015
  • This paper presents the surface flashover characteristics to simulate the poor contact between an anode and a solid dielectric in a $N_2/O_2$ mixture gas (8/2) under a non-uniform field. The surface flashover voltage of the $N_2/O_2$ mixture gas revealed the irregular tendency that was not in accordance with the Paschen's law with an increasing gap of the poor contact. In addition, the insulation performance of the $N_2/O_2$ mixture gas at 0.6MPa was comparable to that of $SF_6$ gas of 0.1MPa based on the insulation performance on the poor contact. These results are able to apply the insulation design of eco-friendly gas insulation switchgear considering the internal faults.

A Study on the Manufacture of Gas Insulated Switchgear Spacer Using APG Molding Process (APG 주형방식을 이용한 가스절연개폐기용 절연 스페이서 제작에 관한 연구)

  • Lee, Chanyong;Bae, Jaesung;Cho, Han-Gu;Lee, Sangmook;Lee, Jaehyeong
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.35 no.4
    • /
    • pp.386-391
    • /
    • 2022
  • The gas insulation switchgear, which is a device for protecting a power system, cannot be supported by the insulation gas itself in a charge unit stored in a metal container. Therefore, molding technology is required to manufacture a gas insulation switch spacer. The APG method injection molding simulation was performed by applying the variables obtained through the physical properties of an epoxy composite used for manufacturing an insulating spacer to a moldflow software. After varying the temperature conditions of heater in the simulation, the thermal characteristics and the degree of hardening of the spacer were analyzed, based on which the optimum process conditions are presented.

Breakdown Characteristics of Dry Air under 170[kV] GIB (170[kV] GIB 내에서 건조공기(Dry Air)의 절연파괴 특성)

  • Han, Ki-Son;Yoon, Jin-Yul;Ju, Hyung-Jun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.10
    • /
    • pp.136-142
    • /
    • 2010
  • In this paper, we changed $SF_6$ insulation gases used already in the GIB(Gas Insulated Bus, gas insulated busbar) of switching appliances of power grid 170[kV] GIS(Gas Insulated Switchgear, Gas Insulated Switchgear) with green insulation dry air gases and studied dielectric breakdown voltage characteristics by the AC voltage withstand test. Withstand test AC voltage applied to the standard KEPCO's 170[kV] GIB with dry air insulation and and the equivalent of dry air and $SF_6$ gas were examined. Breakdown voltage of dry air, using an expression of the experiments were calculated and AC Withstand criterion of dry air insulation for the AC voltage test was derived. Using the criterion, dry air gases can be used instead of the $SF_6$ gas was confirmed in the factory acceptance test at 170[kV] GIB.

$SF_6$ Gas Insulation for next Generation GIS

  • Endo, Fumihiro
    • Electrical & Electronic Materials
    • /
    • v.11 no.10
    • /
    • pp.13-18
    • /
    • 1998
  • Many factors influence SF6 insulation and a number of them have been clarified quantitatively. For the next generation of gas-insulated switchgear (GIS), quantitative considerations of these factorsare necessary to enhance reliability and to make GIS more compact. Advanced insulation technology this purpose is described.

  • PDF

30 Magnetic Analysis on Temperature Rise Resulting from Induced Eddy current In Gas Insulated Switchgear (3차원 자계해석을 통한 GIS 모선의 와전류에 의한 온도 상승)

  • Lee, B.W.;Sohn, J.M.;Kang, J.S.;Seo, J.M.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2274-2276
    • /
    • 1999
  • In this work, temperature rise and eddy current distribution on the enclosure and conductor of 3 pole gas insulated switchgear were investigated using analytical and experimental measures. The design of the diameters of the conductors and the enclosures of a meal clad gas insulated switchgear is primarily based on the insulation requirements. It is very difficult problem to predict the temperature rise of enclosed switchgear due to the complexity of the phenomena of heat transfer and existence of eddy current loss. To overcome this situations, we focused on the eddy current distribution on the enclosure of switchgear caused by high current 3 pole conductor as a fundamental basis. The experimental results about temperature distribution of 3 pole gas insulated switchgear were reported and measurements are compared with predictions of three-dimensional thermal model for eddy current analysis. As a result, three dimensional numerical analysis found to be in close relationship with experimental results and thermal model is efficient to predict the abnormal temperature rise in switchgear.

  • PDF

Analysis on the Dielectric Characteristics of Dry Air According to Pressures for Developing an Eco-friendly High Voltage Switchgear (친환경 고압배전반 개발을 위한 dry air의 압력별 절연내력특성 분석에 관한 연구)

  • Nam, Seok-Ho;Kang, Hyoung-Ku
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.8
    • /
    • pp.1560-1565
    • /
    • 2011
  • The environmental pollution caused by green-house gases such as $CO_2$ and $SF_6$ has been becoming the main issue of industrial society. Many developed countries are making efforts to minimize the amount of $CO_2$ emission come from the operation of high voltage electrical apparatuses. As a part of these efforts, 180 countries signed the Kyoto Protocol in 1997 to cut back on their green-house gas emissions. Nowadays, the study on the development of dry air insulated switchgear (DAIS) which is known as an eco-friendly electrical apparatus is in progress. A DAIS is advantageous for minimizing the effect of impurities and enhancing the dielectric characteristics over an air insulated switchgear (AIS) by applying constant pressure to an enclosed cubicle. Therefore, a study on the electrical insulation performance of dry air as a gaseous insulation medium is conducted in this paper to substitute a gas insulated switchgear (GIS) for DAIS. As results, it is verified that the AC dielectric characteristics of dry air are similar to those of air and the lightning impulse dielectric characteristics of dry air are superior to those of air at 1bar pressure condition. However, dry air is of inferior dielectric characteristics to $SF_6$ at 4bar pressure condition. Finally, it is suggested that the internal pressure of DAIS should be over 4bar pressure to develop a high voltage switchgear which has similar electrical performance to a conventional GIS. Also, the empirical formulae on calculating the maximum electric field intensity at sparkover of dry air are deduced by experiments according to pressures. It is expected that these results are helpful to design and develop a high voltage electrical apparatus.

The Analysis of Insulation Properties with Electron Collision Processes on SF6 Mixture Gases (전자충돌과정을 통한 SF6 혼합기체의 절연특성 분석)

  • So, Soon-Youl
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.59 no.2
    • /
    • pp.197-201
    • /
    • 2010
  • $SF_6$ gas would be used in power transformer, GIS (Gas insulated switchgear) and so on because of its electrically superior insulation and chemically stable structure. Recently, the reduction of $SF_6$ is required to avoid global warming and the researches on the dilution of $SF_6$ with other gases have been carried out. $SF_6$ mixture gases with $N_2$ and $C_xF_y$ have drawn attention to the synergy effect. However, in order to understand the mechanism of the synergy effect, it is important to analyze and evaluate properties of mixture gases quantitatively. In this paper, we investigated the mechanism of synergy effect from electron collision processes and electron energy distribution by solving Boltzmann equation with propagator method. Three kinds of gases for dilution of $SF_6$ ($SF_6/N_2$, $SF_6/CF$4 and $SF_6/C_4F_8$) are considered in this simulation. On the properties of $SF_6/N_2$ mixture gas, the variation of reduced electric field was shown highly within 0%~40% mixtures of $SF_6$. And the more low-level electron energy has been distributed, the higher insulation capability has appeared.