고체 절연체 내부 공극 또는 금속 이물질 존재시의 GIS 내부의 전계 해석 (Analysis of Electric Fields Inside GIS with a Small Void in Spacer or with a Metal Impurity)

  • 민석원;김용준;김응식
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제49권6호
    • /
    • pp.346-353
    • /
    • 2000
  • In this paper, we developed 3 dimensional Surface Charge Method which could calculate electric fields inside GIS with a small void in solid insulator or with a metal impurity. We find a metal impurity makes much more non-uniform electric field distribution inside GIS than a small void. We also find electric field is much more increased when a metal impurity is close to solid insulator surface at high voltage conductor.

  • PDF

GIS 모의결합의 부분방전원 분류 (PD Source Classification of Model Specimens for GIS)

  • 박성희;임기조;강성화;이창준;이희철
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 춘계학술대회 논문집 방전 플라즈마 유기절연재료 초전도 자성체연구회
    • /
    • pp.100-103
    • /
    • 2004
  • In this paper, BP learning algorithm is studied to apply as a PD source classification in GIS specimens. For occurred partial discharge, three defected models are made; floating particle, surface discharge of spacer, needle to plane. And PD data for discrimination were acquired from PD detector. And these data making use of a computer-aided discharge analyser, statistical and other discharge parameters is calculated to discrimination between different models of discharge sources. And also these parameter is applied to classify PD sources by neural networks. Neural Networks has good recognition rate for three PD sources.

  • PDF

모의 GIS 결함에 따른 UHF 신호의 스펙트럼 분석 (Spectrum analysis of UHF Signals Generated by Defects in a Simulated GIS)

  • 전재근;곽희로;노영수;김두석;김경화
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 C
    • /
    • pp.1797-1799
    • /
    • 2003
  • In this paper, we measured partial discharge inception voltage(PDIV) and frequency spectra of UHF signal under following three cases, (1) a corona discharge due to a non uniform electric field for needle-plate electrode (2) a surface discharge caused by particles attached to a spacer in GIS, (3) free movements of particle in GIS. As a result of the experiment, it was revealed that the PDIV of Case (3) is higher than PDIVs of Case (1) and Case (2). It was also seem that UHF signal frequency spectra of one case are different from those of the other cases.

  • PDF

GIS 스페이서에 파티클 부착시 연면방전과 전계해석 (Numerical Analysis of Surface Discharge due to Particles Attached to the GIS spacer)

  • 장덕근;이재화;곽희로;박하용;김영찬
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 C
    • /
    • pp.1788-1790
    • /
    • 2003
  • GIS is a typical power equipment with higher reliability. It is compact and safe because all the energized parts are enclosed by a sealed cylindrical tank which is filled with $SF_6$. Generally gas insulated power equipments like GIS are designed to have sufficient electrical strength to prevent partial discharges under normal operating condition. Despite of the careful processes in manufacturing, transporting and assembling, voids or particles can be created, resulting in partial discharges at electrically weak points. The key factors causing partial discharges in GIS are; particles, voids in solid insulation, protrusions, poor contact of metal components, etc. The particle can be attached on; spacers, electrodes, internal wall of the GIS tank. It also moves in GIS freely. Most of partial discharges are likely to occur when particles are attached to spacers. In this paper, the electrical characteristics of a surface discharge were investigated under various conditions by using simulation program of FEMLAB.

  • PDF

GIS내 파티클의 상태에 따른 부분방전 신호의 분석 (The analysis of partial discharge signals according to particle states in GIS)

  • 김경화;이동준;곽희로
    • 조명전기설비학회논문지
    • /
    • 제14권1호
    • /
    • pp.67-74
    • /
    • 2000
  • 본 논문에서는 GIS내 파티클에 의해 발생할 수 있는 절연사고를 미연에 방지하고 또한 파티클의 상태를 파 악하기 위하여 GIS 41 파티클 상태에 따른 부분방전 신호를 측정하고 분석하였다. 본 논문에서는 GIS내 파티콜 의 상태를 4가지(전극부착시, 외함부착시, 스페이서 부착시, 자유운동시)로 모의하였으며, 이때 발생하는 부분방전 신호의 $\Phi$-Q-N 분포를 형태적으로 분석하였다 또한, $\Phi$-Q 분포에 대하여 통계적 연산자를 도입하여 파티 클 상태에 따른 부분방전 신호를 정량적으로 분석하였다. 그 결과 파티클 상태에 따른 $\Phi$-Q-N 분포의 형태적인 분석과 $\Phi$-Q 분포의 정량적인 분석으로 파티콜의 상태 구별이 가능하였다.

  • PDF

800kV급 GIS의 모델차단부용 스페이서의 형상설계 (Shape Design of A Spacer for 800kV GIS Interrupter)

  • 신영준;장기찬;박경엽;정진교;송원표;강종호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1994년도 하계학술대회 논문집 C
    • /
    • pp.1639-1642
    • /
    • 1994
  • The severe conditions such as rated voltage of 800kV, gas pressure of $5kg/cm^2$ and rated lighting impulse withstand voltage of 2400kV were adopted for the design of spacers in the 800kV GIS to give a sufficient design margin. The design criteria on the maximum electric field strength of the center conductor and the insulator surface were established by considering the insulator surface characteristics, electrode area and surface effects in the unequal electric field strength of the given gap. The design parameters such as inter/outer envelope degree, thickness, inter/outer inserts, triple junction gap were determined by calculating the electric field using FLUX-2D program package and by referring to the published papers. The mechanical stress analysis was conducted on the feasible model spacers that showed good electric field distributions to confirm the sufficient mechanical design margin. The 800kV spacer designed as described above is now in the process of manufacturing.

  • PDF

$SF_6$GIS용 스페이서 표면 파티클에 의한 절연파괴 특성 (The Particle-Initiated Breakdown Characteristics on the Spacer Surface for $SF_6$GIS)

  • 김정달;이세훈
    • 조명전기설비학회논문지
    • /
    • 제12권1호
    • /
    • pp.3-11
    • /
    • 1998
  • 스페이서 표면 파티클에 의한 오염의 영향은 SF6GIS의 절연내력을 현저히 감소시킨다. 이와 관련해서 우리는 평행평판전극 구성으로 SF6가스중에서 금속 및 비금속 파티클의 위치 및 형태를 변화시키면서 교류전압에서 섬락전압 특성과 파괴 기구에 대해서 연구했다. 주된 결과는 $\circled1$파티클 위치에 대한 섬락전압 감소의 영향은 갭중간에서 가장 적고 전극에서 미소간극 분리된 경우의 영향이 가장 커다. $\circled2$ 섬락전압 감소가 크게 되는 금속 파티클 일수록 FOV 포화 현상은 낮은 압력 영역으로 이동된다. $\circled3$0.6[mm]이하의 비금속 파타클은 섬락전압에 그의 영향을 미치지 않는다.

  • PDF

초고압 절연 스페이서의 자동가압 겔화 성형 공정을 위한 경화 보압의 최적화 (Optimization of Curing Pressure for Automatic Pressure Gelation Molding Process of Ultra High Voltage Insulating Spacers )

  • 이찬용;조한구;이재형
    • 한국전기전자재료학회논문지
    • /
    • 제37권1호
    • /
    • pp.56-62
    • /
    • 2024
  • By introducing curing kinetics and chemo-rheology for the epoxy resin formulation for ultra-high voltage gas insulated switchgear (GIS) Insulating Spacers, a study was conducted to simulate the curing behavior, flow and warpage analysis for optimization of the molding process in automatic pressure gelation. The curing rate equation and chemo-rheology equation were set as fixed values for various factors and other physical property values, and the APG molding process conditions were entered into the Moldflow software to perform optimization numerical simulations of the three-phase insulating spacer. Changes in curing shrinkage according to pack pressure were observed under the optimized process conditions. As a result, it was confirmed that the residence time in the solid state was shortened due to the lowest curing reaction when the curing holding pressure was 3 bar, and the occurrence of deformation due to internal residual stress was minimized.

GIS 내부의 도체이물질에 의한 불평등 전계 해석 (Analysis of unequal electric field by metal particle in GiS)

  • 박경수;김진;이희복;고영호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 추계학술대회 논문집 학회본부 C
    • /
    • pp.531-533
    • /
    • 2000
  • In compared with air insulated switchgear, GIS has a high efficiency and confidence So the transformer substation can be reduced the size to 1/10. Insulation method using $SF_6$ gas has a very excellent insulation characteristics for high pressure equipment but has a characteristics that insulation heredity is changed for internal unequal electric field. So analysis of electromagnetic field in GIS is very important basic data for structure design and trouble diagnosis process. In compared with established method, SNM in this paper observes variation of the electromagnetic field with real time and get result very similar to measurement. In order to know the variation of electromagnetic field distribution for transient response for time and position, variations are observed when the spacer is bonded and metal particles are moving fast.

  • PDF

초고압 전력기기 진단을 위한 UHF PD 센서 및 패턴분석 기술에 관한 연구 (A Study on the UHF PD Sensor and Novel Pattern Analysis Technology for Diagnosis of the High Power Apparatus)

  • 강원종;이창준;강윤식;이희철;박종화
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제53권2호
    • /
    • pp.83-90
    • /
    • 2004
  • This paper describes investigations of the UHF(Ultra High Frequency) PD(Partial Discharge) measuring technology designed for monitoring of PD in high power apparatus. Based on the spiral antenna theory, the hole type sensor for GIS with metal flange spacer and injection type sensor for oil filled transformer are developed. The experimental results show measurement characteristics of the PD sensor for several artificial defects in gas-insulated system(GIS) and oil transformer. Moreover, we proposed the new $\phi$-f-q method for the purpose of condition assessment of high power apparatus.