• Title/Summary/Keyword: GIS Busbar

Search Result 12, Processing Time 0.021 seconds

Coupling of Flux2D and Analytic Method for Temperature Rise Prediction of Busbar Part of EHV GIS (GIS 모선의 온도상승 예측을 위한 해석적 방법과 Flux2D의 결합)

  • Kim, H.H.;Kim, J.C.;Hahn, S.C.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07a
    • /
    • pp.376-378
    • /
    • 1999
  • In order to design the current carrying conductor for GIS, it is important to predict temperature-rise when rated current flows. This paper deals with the coupling of Flux2D and analytic method to calculate the heat transfer coefficient. Heat transfer by conduction and convection is considered between the current carrying conductor and $SF_6$ gas. The result shows reasonable temperature distribution.

  • PDF

Breakdown Characteristics of Dry Air under 170[kV] GIB (170[kV] GIB 내에서 건조공기(Dry Air)의 절연파괴 특성)

  • Han, Ki-Son;Yoon, Jin-Yul;Ju, Hyung-Jun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.10
    • /
    • pp.136-142
    • /
    • 2010
  • In this paper, we changed $SF_6$ insulation gases used already in the GIB(Gas Insulated Bus, gas insulated busbar) of switching appliances of power grid 170[kV] GIS(Gas Insulated Switchgear, Gas Insulated Switchgear) with green insulation dry air gases and studied dielectric breakdown voltage characteristics by the AC voltage withstand test. Withstand test AC voltage applied to the standard KEPCO's 170[kV] GIB with dry air insulation and and the equivalent of dry air and $SF_6$ gas were examined. Breakdown voltage of dry air, using an expression of the experiments were calculated and AC Withstand criterion of dry air insulation for the AC voltage test was derived. Using the criterion, dry air gases can be used instead of the $SF_6$ gas was confirmed in the factory acceptance test at 170[kV] GIB.