• 제목/요약/키워드: Fire-effect Simulation

검색결과 155건 처리시간 0.027초

화재 성장 모델이 객차내 화재 특성에 미치는 영향에 관한 수치해석적 연구 (A Numerical Study of the Effect off Fire Growth Model on Fire Characteristics in a Carriage)

  • 김성찬;유홍선;최영기;김동현
    • 한국철도학회논문집
    • /
    • 제7권3호
    • /
    • pp.180-185
    • /
    • 2004
  • The present study investigates the effect of fire growth model on fire development characteristics in a carriage. The parallel processing version of FDS code is used to simulate the fire driven flow in a carriage and two types of fire growth model which are flame spread model and t$^2$ model are examined for the same geometrical condition. The heat release rates(HRR) of both model are similar each other until 30 s after ignition, but the flame spread model predicts 5 times higher than those of the t$^2$ fire model during the quasi-steady fire period. Maximum heat release rate in the case of flame spread model reaches about to 12 MW at 100 s after fire ignition. Also, various database of fire properties for combustible materials and more elaborate combustion model considering the flame spreading phenomena are required for better predictions of fire development characteristics using numerical simulation.

시뮬레이션을 이용한 화재 시 고층건축물의 압력분포 특성에 관한 연구 (A Sutdy on the Pressure Distribution Characteristic of High-rise Buildings in Fire Using Computer Simulation)

  • 김혜원;이병흔;진승현;권영진
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2019년도 춘계 학술논문 발표대회
    • /
    • pp.49-50
    • /
    • 2019
  • In the case of High-rise buildings, it has a problem by stack effect that rise of vertical height. Especially in case of fire, it need to the consideration of stack effect that it has bigger than general. Therefore in this study, we used to the Contamw and FDS simulation for analysis of stack effect and pressure distribution characteristic in fire. As a result the Contamw simulation shows the pressure distribution by stack effect in general high-rise buildings. However, in case of fire, the height of the neutral plane is lowered and stack effect is larger. Therefore, it is necessary to multiply analyze the temperature distribution and the stack effect in fire.

  • PDF

산불 전파의 수치 시뮬레이션 (Numerical Simulation of a Forest Fire Spread)

  • 이명성;원찬식;허남건
    • 설비공학논문집
    • /
    • 제20권2호
    • /
    • pp.137-143
    • /
    • 2008
  • In the present study, a forest fire spread was simulated with a three-dimensional, fully-transient, physics-based, computer simulation program. Physics-based fire simulation is based on the governing equations of fluid dynamics, combustion and heat transfer. The focus of the present study is to perform parametric study to simulate fire spread through flat and inclined wildland with vegetative fuels like trees or grass. The fire simulation was performed in the range of the wind speeds and degrees of inclination. From the results, the effect of the various parameters of the forest fire on the fire spread behavior was analyzed for the future use of the simulation in the prediction of fire behavior in the complex terrain.

스프링클러 분무 해석에 영향을 미치는 통계적액적군집의 영향 (Effect of the Statistical Droplet Parcel on Numerical Simulation of Sprinkler Spray)

  • 김성찬;이상우;박원주
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 추계학술논문발표회 논문집
    • /
    • pp.363-370
    • /
    • 2008
  • The present study has been performed to investigate the effect of statistical number of droplets on the simulation of the sprinkler spray using fire field model. In order to simulate the sprinkler spray characteristics, the present study uses NIST Fire Dynamics Simulator version 5.2. A group of Lagrangian particle with similar droplet characteristics, such as diameter, velocity, temperature and so on, is represented by parcel concept to decrease the total number of droplets tracked in the simulation. The present study introduces a new parameter to represent the ratio between real number of droplets and computational parcels. The dependency of the number of parcels on the fire suppression characteristics and spray patterns is quantitatively examined for different ratio between the real number of droplets and computational parcels.

  • PDF

대심도 역사의 화재위치에 따른 연기확산 영향 분석 (Analysis of Smoke Spread Effect Due to The Fire Location in Underground Subway-Station)

  • 장용준;구인혁;김진호;남성원
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2011년도 정기총회 및 추계학술대회 논문집
    • /
    • pp.2885-2890
    • /
    • 2011
  • 본 연구에서는 최근 증가하고 있는 대심도역사의 화재위치에 따른 연기확산영향에 대하여 분석하였다. 시뮬레이션모델은 신금호 역사(5호선, 깊이 46m)를 대상으로 하였으며, 화재위치에 따른 연기확산 영향을 분석 하였다. 현장조사 및 실측을 통하여 계측된 실제 역사의 제연팬에 관한 데이터를 화재시뮬레이션 조건으로 적용하였다. 역사전체를 해석 대상으로 하여 총 400만개의 격자를 사용하였으며, 화재위치에 따른 연기확산 영향 비교를 위하여 화재 시나리오를 작성하여 Case별로 화재해석을 수행하였다. 계산 효율을 높이기 위하여 MPI병렬처리기법을 사용하였으며 해석코드는 LES(large eddy simulation) 기법을 주로 사용하는 FDS5 code를 사용하였다.

  • PDF

물분무노즐의 분사각이 화재실 내부의 온도장에 미치는 영향 (Effect of Spray Angle of Water Mist Nozzle on Temperature Field of Compartment Fire)

  • 김성찬;유홍선;박현태;방기영
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2003년도 춘계학술대회
    • /
    • pp.1703-1708
    • /
    • 2003
  • The present study investigates the effect of injection angle of water mist on fire suppression characteristics by numerical simulation. In order to validate the temperature field by numerical simulation, the predicted results are compared with experimental data. It shows that the temperature difference between measurements and predictions are within $10^{\circ}C$ Numerical simulations of fire suppression are performed for 4 different injection angle($60^{\circ}$, $90^{\circ}$, $120^{\circ}$, and $180^{\circ}$). The grobal mean temperature over the fire compartment decrease with increasing of spray angle. The result shows that the heat transfer between droplets and gas phase are enhaced with the increasing of spray angle. Near the fire source, temperature field by the wide spray angle is slightly higher than that of narrow injection angle because of direct cooling of fire source.

  • PDF

물분무노즐의 분사각이 화재실 내부의 온도장에 미치는 영향 (Effect of Spray Angle of Water Mist Nozzle on Temperature Field of Compartment Fire)

  • 김성찬;유홍선;박현태;방기영
    • 한국안전학회지
    • /
    • 제18권2호
    • /
    • pp.28-33
    • /
    • 2003
  • The present study investigates the effect of injection angle of water mist on fire suppression characteristics by numerical simulation. In order to validate the temperature field by numerical simulation, the predicted results are compared with experimental data. It shows that the temperature difference between measurements and predictions are within $10^{\circ}C$. Numerical simulations of fire suppression are performed for 4 different injection angle($60^{\circ}$, $90^{\circ}$, $^120{\circ}$, and $180^{\circ}$). The global mean temperature over the fire compartment decrease with increasing of spray angle. The result shows that the heat transfer between droplets and gas phase are enhanced with the increasing of spray angle. Near the fire source, temperature field by the wide spray angle is slightly higher than that of narrow injection angle because of direct cooling of fire source.

대심도 역사의 화재강도에 따른 연기확산 영향 분석 (ANALYSIS OF SMOKE SPREAD EFFECT DUE TO THE FIRE STRENGTH IN UNDERGROUND SUBWAY-STATION)

  • 장용준;구인혁;김학범;김진호
    • 한국전산유체공학회:학술대회논문집
    • /
    • 한국전산유체공학회 2011년 춘계학술대회논문집
    • /
    • pp.373-378
    • /
    • 2011
  • As the number of deeply-underground subway station(DUSS) increases, the safety measures for DUSS have been requested. In this research, Shingumho station (The line # 5, Depth: 46m) has been selected as case-study for the analysis of smoke-spread speed with the different fire strength. Field test data measured for actual fan in DUSS was applied as a condition of a simulation. The whole station was covered in this analysis and total of 4 million grids were generated for this simulation. The fire driven flow was analyzed case by case to compare the smoke-spread effect according to the fire strength. in order to enhance the efficiency of calculation, parallel processing by MPI was employed and large eddy simulation method in FDS code was adopted.

  • PDF

FOFIS: 산불 정보 시스템 (FOFIS : Forest Fire Information Systems)

  • 지승도
    • 한국시뮬레이션학회논문지
    • /
    • 제8권2호
    • /
    • pp.13-28
    • /
    • 1999
  • The main purpose of this paper is to design and implement forest fire information system (FOFIS) for effective prevention of forest fire using GIS, database, 3-D graphics, and simulation techniques. In contrast to conventional fire information systems that are mostly based on the 2-D graphics and analytic modeling approaches, we have proposed the cell-based modeling approaches, i.e., spatial, data, and simulation modeling approaches. The cell-based spatial modeling is proposed by eliminating the cliff effect of the typical elevation model so that it can provide realistic 3-D graphics of the forest fire. The cell-based data modeling of geography, meteorology, and forestry information is also proposed. The cell-based dynamic modeling for forecasting of the fire diffusion is developed using the variable structure modeling techniques. Several simulation tests of FOFIS performed on a sample forest area of Chungdo, Kyungsangbukdo will demonstrate our approaches.

  • PDF