물분무노즐의 분사각이 화재실 내부의 온도장에 미치는 영향

Effect of Spray Angle of Water Mist Nozzle on Temperature Field of Compartment Fire

  • 발행 : 2003.06.01

초록

The present study investigates the effect of injection angle of water mist on fire suppression characteristics by numerical simulation. In order to validate the temperature field by numerical simulation, the predicted results are compared with experimental data. It shows that the temperature difference between measurements and predictions are within $10^{\circ}C$. Numerical simulations of fire suppression are performed for 4 different injection angle($60^{\circ}$, $90^{\circ}$, $^120{\circ}$, and $180^{\circ}$). The global mean temperature over the fire compartment decrease with increasing of spray angle. The result shows that the heat transfer between droplets and gas phase are enhanced with the increasing of spray angle. Near the fire source, temperature field by the wide spray angle is slightly higher than that of narrow injection angle because of direct cooling of fire source.

키워드

참고문헌

  1. Herterich O., 1960, Water as an extinguishing agent, Alfred Huthig Pubilishing Company, Heidelberg
  2. Ohkubo H, Nishio S., 1990, Study on accurate prediction of heat transfer characteristics of mist cooling, JSME Int. J. Ser. II, Vol. 33, No.2, pp. 326-332
  3. Kaleta A, 1986, Effect of drop size on extinguishing effectiveness of a water spray, Archivum Combustions, Vol. 6, No.3, pp. 201-212
  4. Hirst R., 1989, Underdown's practical fire precautions, 3rd edn., London, Gower Press
  5. Ranz, W., E., and Marshell, Jr. W.,R., 1952, Evaporating from drops, Part I, Cham. Eng. Prog., Vol. 48, pp. 141-146
  6. Ranz, W., E., and Marshell, Jr. W.,R., 1952, Evaporating from drops, Part II, Cham. Eng. Prog., Vol. 48, pp. 173-180
  7. Fire Dynamics Simulator Technical Reference Guide, 2000, NIST, U.S.A