Prediction of the Fire Behavior According to the Fire Load in an Underground Life Space (화재하중에 따른 지하생활공간의 화재성상 예측)

  • Chae, Han-Sik;Suk, Chang-Mok;Kim, Ie-Sung;Lee, Ji-Hee;Kim, Wha-Jung
    • Fire Science and Engineering
    • /
    • v.21 no.1 s.65
    • /
    • pp.51-59
    • /
    • 2007
  • The purpose of this study is analyzing the fire behavior according to the fire load for G underground shopping mall located in Daegu city. when predict fire behavior, fire load and ventilation coefficient are important factor who dominate fire temperature or fire continuance time. Therefore, size of unit room, opening size and inflammable investigated on the field. Fire load calculated using unit calorific value by each material of inflammable that investigate. And reduction model experimented fire load about 6 models with variable. Fire behavior analyzed by heat flows of inside space that temperature rise and temperature change by time of fire source.

A Review on Fire Safety Engineering: Key Issues for High-Rise Buildings

  • Li, Guo-Qiang;Zhang, Chao;Jiang, Jian
    • International Journal of High-Rise Buildings
    • /
    • v.7 no.4
    • /
    • pp.265-285
    • /
    • 2018
  • This paper presents a state-of-the-art review on the design, research and education aspects of fire safety engineering (FSE) with a particular concern on high-rise buildings. FSE finds its root after Great Fire of Rome in 64 AD, followed by Great London Fire in 1666. The development of modern FSE is continuously driven by industry revolution, insurance community and government regulations. Now FSE has become a unique engineering discipline and is moving towards performance-based design since 1990s. The performance-based fire safety design (PBFSD) involves identification of fire safety goals, design objectives, establishment of performance criteria, and selection of proper solutions for fire safety. The determination of fire scenarios and design fires have now become major contents for PBFSD. To experience a rapid and positive evolution in design and research consistent with other engineering disciplines, it is important for fire safety engineering as a profession to set up a special educational system to deliver the next-generation fire safety engineers. High-rise buildings have their unique fire safety issues such as rapid fire and smoke spread, extended evacuation time, longer fire duration, mixed occupancies, etc., bringing more difficulties in ensuring life safety and protection of property and environment. A list of recommendations is proposed to improve the fire safety of high-rise buildings. In addition, some source information for specific knowledge and information on FSE is provided in Appendix.

The Analysis of the Carbonization Properties between RCD Source Terminals Deteriorated by Tracking (누전차단기 외함 전원측 단자사이의 트래킹에 의한 탄화특성 분석)

  • 최충석;송길목;김동우
    • Fire Science and Engineering
    • /
    • v.17 no.4
    • /
    • pp.13-19
    • /
    • 2003
  • In this paper, we studied on the characteristics of RCD(Residual Current Device) case deteriorated by tracking, and compared the tracked samples between in the site of fire($S_1$) and in the reappearance experiment($E_1$). This experiment is applied to IEC Publ. 112 method. Electrical fire by tracking occurred after scintillation and dry-band generated. The insulation resistance between source terminals of RCD case was about 25.7Ω in $E_1$ and the resistance was about 58.6Ω in $S_1$.The exothermic peaks of $E_1$ appeared at $491.0^{\circ}C$ and $603.2^{\circ}C$. The exothermic peak at $603.2^{\circ}C$ was shown by tracking. And the exothermic peak of $S_1$ appeared at $593.1^{\circ}C$. In spectrum of $S_1$ and $E_1$, absorption peak didn't appear at near 1590 cm$^{-1}$ .

Performance Analysis and Improvement of National Fire Safety Code elements of Sprinkler System (스프링클러설비의 화재안전기준 요소의 성능분석 및 개선방안)

  • Oh, Taekhum;Lee, Jungil
    • Journal of the Society of Disaster Information
    • /
    • v.9 no.4
    • /
    • pp.413-422
    • /
    • 2013
  • This study evaluated the fire safety code elements through analyze the loss of life when the fire occurred in the facility sprinklers installed evaluated. And through comparison with national fire safety code elements and standards of NFPA 13 in the United States, Was looking for ways to improve for Life and property damage. In the United States, in some cases, if you do not install the sprinkler are installed as per the fire death rate compared to 83 % lower. By contrast, If the domestic rate of 280 % fatalities were 3.37 times than the United States. This lack of fire performance were analyzed uniform occupancy classification, the amount of source of water supply, live not consider the density according to the standard number and the horizontal distance that causes the installation of sprinkler facilities were analyzed.

Possibility of Are Tracking at the Circuit Breaker After Starting Fire (화재발생 이후 분전반 차단기에서의 트래킹현상 진행 가능성)

  • Park, Y.G.;Oh, D.H.;Lee, S.H.;Park, J.T.;Kim, J.P.
    • Journal of Korean Institute of Fire Investigation
    • /
    • v.10 no.1
    • /
    • pp.37-45
    • /
    • 2007
  • In this paper, the possibility of arc tracking, caused by combustion at the circuit breaker, was discussed. The arc tracking, occurred at the source terminals of all the circuit breakers, when we burned electric leakage circuit breakers with 220V applied. We had a same results of the experiment to simulate fire scene, in the circumstance of fire, all of the circuit breakers had arc tracking caused by combustion. Therefore we confirmed that the arc tracking at the source terminal of circuit breaker could be occurred by just combustion in the fire scene, and it was impossible to decide the cause of fire for reason of discriminating arc tracking at the terminals of circuit breaker.

  • PDF

Ventilation Effects on Smoke Behavior in Rescue Station for Tunnel Fires (철도터널 화재시 구난역 내의 연기거동에 미치는 배연효과에 관한 수치연구)

  • Jang, Won-Cheol;Kim, Dong-Woon;Ryou, Hong-Sun;Lee, Seong-Hyuk
    • Proceedings of the KSR Conference
    • /
    • 2008.06a
    • /
    • pp.2130-2138
    • /
    • 2008
  • The present study investigates the ventilation effects on smoke spreading characteristics in railway tunnels with the rescue stations. Experiments were carried out for n-heptane pool fires with a square length 4 cm at different fire locations, and the heat release rates (HRR) were obtained by the measurement of burning rates. In addition, using the commercial code (FLUENT), the present article presents numerical results for smoke behavior in railway tunnels with rescue station, and it uses the MVHS (Modified Volumetric Heat Source) model for estimation of combustion products resulting from the fire source determined from the HRR measurement. As a result, it is found that smoke propagation is prevented successfully by the fire doors located inside the cross-passages and especially, the smoke behavior in the accident tunnel can be controlled through the ventilation system because of substantial change in smoke flow direction in the cross-passages.

  • PDF

A Study on the Short-Circuit Characteristics of Vinyl Cords Damaged by External Flame (외부화염에 의해 소손된 비닐 코드의 단락 특성에 관한 연구)

  • Choi Chung-Seog;Kim Hyang-Kon;Shong Kil-Mok
    • Fire Science and Engineering
    • /
    • v.18 no.4
    • /
    • pp.72-77
    • /
    • 2004
  • In this paper, we studied on the short-circuit process, surface structure, and component variation of vinyl cords. In the results of high speed imaging system (HSIS) analysis, as soon as wire covering was damaged by heat, the conductor of wire came in contact with the other conduct of wire, and the short-circuit occurred. Stereomicroscope and SEM analysis indicated that the source part of wire showed V-type form. The molten beads of load part were bigger than those of source part. In the results of EDX analysis, Cu and O were detected in the source part, whereas covering material (Cl, Ca), Cu and O were detected in the load part. The results will help us to find out the cause of electrical fire.

A Numerical Study of Smoke Movement by Fire In Atrium Space (화재 발생시 연기 거동에 대한 수치해석적 연구 - 아트리움 공간을 중심으로 -)

  • 노재성;유홍선;정연태
    • Journal of the Korean Society of Safety
    • /
    • v.13 no.1
    • /
    • pp.70-76
    • /
    • 1998
  • The smoke filling process for the atrium space containing a fire source is simulated using two types of deterministic fire models : Zone model and Field model. The zone model used is the CFAST(version 1.6) model developed at the Building and Fire Research Laboratories, NIST in the USA. The field model is a self-developed fire field model based on Computational Fluid Dynamics(CFD) theories. This article is focused on finding out the smoke movement and temperature distribution in atrium space which is cubic in shape. A computational procedure for predicting velocity and temperature distribution in fire-induced flow is based on the solution, in finite volume method and non-staggered grid system, of 3-dimensional equations for the conservation of mass, momentum, energy, species and so forth. The fire model i. e. Zone model and Field model predicted similar results for the clear height and the smoke layer temperature.

  • PDF

Fire test for interior material satisfied with the guide for the safety of rail vehicle (철도차량 안전기준을 만족하는 철도차량 내장재의 화재성능 시험)

  • Park, Won-Hee;Lee, Duck-Hee;Jung, Woo-Sung
    • Proceedings of the KSME Conference
    • /
    • 2008.11b
    • /
    • pp.2149-2153
    • /
    • 2008
  • A large-scale fire test was done for interior materials from a vehicle installed within a fire test room. The interior materials are satisfied with the Korean guide for the safety of rail vehicle. The guide has taken effect since December 2004 in Korea. Ignition source (gas burner) was increased in several controlled steps. The objectives of this test are to assess the fire performance in terms of ignition and flame spread on interior lining materials and to provide data on an enclosure fires involving train interior materials that grow to flashover. This data will be used to develop and calibrate an Fire Dynamics Simulator (FDS) model for fire growth on the interior vehicle.

  • PDF

Performance Based Design of Passive Fire Protection Using Consequence Analysis (사고 영향 분석을 이용한 성능위주의 내화설계)

  • Han, Dong-Hoon;Lee, Jong-Ho
    • Journal of the Korean Society of Safety
    • /
    • v.19 no.1
    • /
    • pp.102-107
    • /
    • 2004
  • Performance based design is a recent evolutionary step in the process of designing fire protection systems. In essence, it is a logical design process resulting in a solution that achieves a specified performance. Sometimes the prescriptive solutions presented in various codes and standards are too expensive or inflexible. Often the solutions do not and enables optimization of a solution for cost and function. In this study, performance based design was carried out to determine the extent of passive fire protection for oil terminal facilities. The results of performance based design were compared with those of prescriptive code based design. Performance based design is not always more economic than prescriptive code based design but provides more reliable and effective design that is fit for the purpose.