Abstract
In this paper, we studied on the characteristics of RCD(Residual Current Device) case deteriorated by tracking, and compared the tracked samples between in the site of fire($S_1$) and in the reappearance experiment($E_1$). This experiment is applied to IEC Publ. 112 method. Electrical fire by tracking occurred after scintillation and dry-band generated. The insulation resistance between source terminals of RCD case was about 25.7Ω in $E_1$ and the resistance was about 58.6Ω in $S_1$.The exothermic peaks of $E_1$ appeared at $491.0^{\circ}C$ and $603.2^{\circ}C$. The exothermic peak at $603.2^{\circ}C$ was shown by tracking. And the exothermic peak of $S_1$ appeared at $593.1^{\circ}C$. In spectrum of $S_1$ and $E_1$, absorption peak didn't appear at near 1590 cm$^{-1}$ .
본 논문은 누전차단기 외함 전원측 단자사이에서 발생하는 전기화재 원인에 대한 분석을 연구하였다. 누전차단기는 보호범위의 전기시설물에서 누전 또는 과부하에 의한 차단을 목적으로 한다 누전차단기의 전원측 단자는 트래킹에 의해 화재로 쉽게 이어질 수 있다. 따라서, 누전차단기의 재현실험을 통해 트래킹시료($E_1$)와 화재현장에서 트래킹된 것($S_1$)을 비교분석하여 전기화재의 원인을 밝히는데 중요한 자료가 되도록 하였다. 실험은 IEC Publ. 112법을 응용하여 실시하였고 누전차단기에서 미소방전과 건조대가 발생한 후 소손되는 것을 확인하였다. $_1$에서 전원측 단자간의 절연저항은 약 25.7Ω이고 $S_1$의 절연저항은 약 58.6Ω이었다. $E_1$의 발열피크는 $491.0^{\circ}C$와 $603.2^{\circ}C$였다. $603.2^{\circ}C$에서의 발열피크는 트래킹에 의한 것이다. $S_1$의 발열피크는 $593.1^{\circ}C$에서 나타났다. 트래킹에 의해 변화된 시료는 IR 흡수스펙트럼에서 $1590 cm^{-1}$ 에서 흡광피크가 나타나지 않았다.