• Title/Summary/Keyword: Fire shutter

Search Result 16, Processing Time 0.029 seconds

The Evacuation Characteristics of Elementary School Student According to Working of Single Unit Fireproof Shutter for Fires (화재 시 일체형 방화셔터 작동유무에 따른 초등학생의 피난특성)

  • Lee, Seung-Chul;Hong, Yi-Pgo;Kim, Sang-Il
    • Fire Science and Engineering
    • /
    • v.27 no.4
    • /
    • pp.35-40
    • /
    • 2013
  • This study investigated the evacuation characteristics of student of elementary school with single unit fireproof shutter. In particular, we gathered the data about fireproof shutter and checked the data. And we made comparison and did an analysis of the evacuation characteristics of elementary school student according to working of single unit fireproof shutter for fires. As a result, it took the last occupant 130 seconds to escape from the school with no fire shutter case. But it took time 190 seconds to escape when the single unit fireproof shutter worked. Some of elementary school students could not open the door installed on the shutter when the single unit fireproof shutter worked. Considering this circumstance, it can be led to time delays of escaping when the single unit fireproof shutter work. And many students can be exposed to the fire hazards. Therefore, the study on the power to open the door installed on the shutter must be done in the future.

Methods of Ensuring Safety for Integrated Fire Protection Shutters at Elementary and Middle Schools (초등학교 및 중학교의 일체형 셔터 안전성 확보 방안)

  • Youn, Hae-Kwon
    • Fire Science and Engineering
    • /
    • v.30 no.5
    • /
    • pp.36-45
    • /
    • 2016
  • Integral fire shutters are installed indiscriminately, regardless of evacuation. There is always the risk of an accident because integral shutters are applied mainly to corridors, passages, and stairs of schools This study evaluated the problem of integral shutter's entrance, evacuation, construction management, and maintenance control through a fire shutter accident case, including present condition of fire shutter installed at school of Okgil, Bucheon and Dongtan, Hwaseong. The results suggest that emergency lighting or signs for passage be set up to check location of entrance easily and install obstruction sensors at fire shutter to reduce life damage. In addition, the number of efficiency tests of fire shutters should be increased by running a trial test monthly or weekly to maintain the performance of fire shutter. Schools need to install a fire shutter- applied sprinkler at the entire floor.

Analysis of the Working Conditions of Screen Fire Shutters in the Goyang Bus Terminal Fire (고양종합터미널화재 시 스크린방화셔터의 작동실태 분석)

  • Lee, Eui-Pyeong
    • Fire Science and Engineering
    • /
    • v.32 no.2
    • /
    • pp.82-91
    • /
    • 2018
  • This study analyzed the working conditions and problems of screen fire shutters in the Goyang Bus Terminal fire based on the fire investigation results. At that time, screen fire shutters in the 1st basement, which was under construction, did not work because the power was shut off. Four screen fire shutters in the 1st and 3rd floor did not work despite the power not being shut off. The following problems related to a screen fire shutter were found: shutting off the power to screen fire shutters for the fire compartment on each floor, even when the fire compartments were changed in each area; installing an integral type screen fire shutter without any regulations, installing a two-stage screen fire shutter in a place not related to obstacles during evacuation; stopping the function of the screen fire shutters for a fire compartment on each floor after a combustible sandwich panel was comparted; installing a screen fire shutter over 10 meters in width, in which its performance was not verified; and no safety control standards for reinstalling or maintaining a screen fire shutter.

A Study on the Effects of All-in-one Automatic Fire Shutters Installed in High School on Evacuation Time

  • Lee, Soon Beom;Kong, Ha Sung;Lee, Jai Young
    • International Journal of Internet, Broadcasting and Communication
    • /
    • v.14 no.3
    • /
    • pp.182-192
    • /
    • 2022
  • This study analyzed the effects of the all-in-one automatic fire shutter (hereinafter referred to as "all-in-one shutter") installed along the fire compartment in a five-story high school building on the evacuation time by using the Pathfinder simulation program. When the all-in-one shutter was added as a new variable, the evacuation time was delayed, indicating insufficient evacuation safety. The evacuation time exceeded the appropriate standard when the evacuation exit was designated to the students in the present state of being placed on the 2nd, 3rd, and 4th floors and the all-in-one shutter was activated. When students were placed on the 1st, 2nd and 3rd floors under the same conditions, the evacuation time was also greatly exceeded. However, when the width of the entrance was set to 130cm, the evacuation time was almost the same as when the all-in-one shutter was not installed. In high-rise school buildings, the bottleneck caused by all-in-one shutters is becoming a major factor in evacuation barriers. To ensure the evacuation safety of school buildings, it has been judged that evacuation education and training to predict the evacuation time required through the all-in-one shutter entrance and induce an evacuation procedure suitable for the standard evacuation time should be carried out in parallel. The implications of this study and suggestions for effective fire compartments and follow-up studies were discussed.

Optimal Display Method Considering the Display Element and Color of Fire Shutter Door (방화셔터 출입구의 표시 요소 및 색상을 고려한 최적 표시방법)

  • Son, Jong-Yeong;Hong, Won-Hwa;Bae, Young-Hoon
    • Fire Science and Engineering
    • /
    • v.32 no.2
    • /
    • pp.67-72
    • /
    • 2018
  • A fire shutter is installed to prevent the movement of fire or smoke when a fire occurs inside a building. Fire shutters have access doors for passengers. On the other hand, the present fire shutter door display regulation is only required to be displayed in a different color from the surroundings. Hence, the risk of people not being able to recognize the door of the fire shutter is quite high, and the danger increases further in a smoke situation. Therefore, this study attempted to find a way to mark a fire shutter door that can be recognized even when smoke is spreading. First, a preliminary questionnaire was used to draw three factors to mark the fire shutter door (sign, door background, and edge). The experiment type was set by combining 5 colors for the three derived factors. The experiment was conducted on a total of 122 male and female participants. The results showed that a yellow background, red sign, and red edge have the highest awareness in a normal visual field without smoke. This was also the same in the field of view in the case of a fire with smoke, but the red background, yellow sign, and yellow edge were most noticeable in the case of dark smoke.

A Numerical Study for the Atrium Smoke Control by Fire Shutter and Evacuation (방화셔터를 이용한 아트리움 제연과 피난안전에 관한 수치해석 연구)

  • Jeon, Heung-Kyun;Choi, Young-Sang;Choo, Hong-Lok
    • Fire Science and Engineering
    • /
    • v.24 no.5
    • /
    • pp.50-59
    • /
    • 2010
  • Four fire scenarios, as the cases of fire sizes of 2 MW and 5 MW, and no installation and activation of atrium fire shutter for dormitory building of Daegu 'D college', were developed and fire simulations were run using FDS (ver. 5.5.0) and Pathfinder 2009 programs. By assessing fire and evacuation, the effects of atrium fire shutter and vents on the smoke control of atrium were evaluated and this study also analyzed fire hazard and egress safety for occupants in the dormitory. Fire shutter's preventing smoke transport around atrium was much effective, but smoke layer descended down the design limit of smoke height and kept about 2 m height from the atrium floor in all cases because flow rate through vents was not enough. For the case of 5 MW fire and no fire shutter, fire hazard was higher due to visibility than temperature and allowable egress time to stairwell was short less than 5 seconds for the occupants on the floors of 4F to 7F. For total occupants, egress time out of main doorway was calculated about 136 seconds. It is sure that additional systems improving the performance of smoke control need to be installed for more safe evacuation.

Analysis on the Falling Risk of Building Electric Shutter and Reduction Measures (건축물 전동셔터 추락 리스크 분석 및 저감 방안)

  • Jung, Young-Min;Bang, Hong-Soon;Kim, Ok-Kyue
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2021.05a
    • /
    • pp.295-296
    • /
    • 2021
  • With the recent diversification and complication of buildings, the functions of building are also developing. As much as the development of buildings, the machine or equipment used for them is also developing. Thus, all sorts of domestic/foreign industrial facilities and fire stations in the whole nation are using the electric shutter that could meet the insulation just like the exterior wall of general buildings, for bringing-in/storage and crime prevention/fire prevention. Currently, various types of electric shutters are used. Such wrong operation and poor management are causing many panel-falling accidents. This study researched the reduction of electric shutter panel-falling risk by reviewing the domestic/foreign laws and standards, and researching the new safety equipment. First, the causes for falling and accident types were drawn by analyzing the cases of electric shutter accidents. After that, a checklist as the measures for reducing the falling of electric shutter in building was suggested by analyzing the items for the inspection of electric shutter.

  • PDF

A Study on Fire Spread between Office Room and Atrium in the Atrium Building

  • Lee, Su-Kyung;Kim, Jong-Hoon;Ko, Han-Mog
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1997.11a
    • /
    • pp.345-352
    • /
    • 1997
  • We could analyse the fire behavior using the developed software for fire safety assessment in a large space such as atrium. But Korean building law hasn't admitted the result of fire risk assessment in atrium. In the legislation fire resistant wall or shutter must be required between atrium and office rooms, That has obstructed development of building design and fire protection technique in Korea. From this point of view, we made scenarios of fire spread between atrium and office rooms, and then computed fire spread and fire phenomena using FASTLite and Breakl. In this study, we can decide that fire compartmentalization between atrium and office rooms doesn't require in Atrium building if the material and fire protection system were reliable. Consequently, Korean Fire Protection Regulations have to consider in direction of increasing freedom of building.

  • PDF

A Numerical Study on the Smoke Control in Center-Platform Type Subway Station Fires (섬식 지하철역사내 화재시 연기제어에 관한 수치해석적 연구)

  • Lee, Sung-Ryong;Ryou, Hong-Sun
    • Journal of the Korean Society for Railway
    • /
    • v.10 no.3 s.40
    • /
    • pp.313-318
    • /
    • 2007
  • In this study, numerical simulations were carried out to analyze the effect of the smoke extraction system and fire shutters in subway station fires using FDS 4.0. Subway station used in the experiment was 145 m long. Simulation results are validated by comparing with experimental results. Simulation results showed good agreement with experimental results within $10^{\circ}C$. 10 MW polystyrene was used as a fuel in the numerical prediction. Numerical predictions were performed in the center-platform type subway station in case of a kiosk fire. Temperature and CO concentration were lowered by the operation of smoke extraction system. But, the operation of fire shutters had little effect on temperature and CO concentration in the platform level.

A Real Situation Experimental Study on The Thermal Protection Performance of Firefighter Clothes and Gloves (소방방화복 및 소방장갑의 열 보호 성능에 대한 실제 화재 실험 연구)

  • Lee, Won Jae;Kang, Gu Hyun;Jang, Yong Soo;Kim, Wonhee;Choi, Hyun Young;Kim, Jae Guk;Kim, MinJi;Seo, Kyo;kim, Do hee;Lee, Joo-young;Choi, Jung Yoon
    • Journal of the Korean Burn Society
    • /
    • v.21 no.1
    • /
    • pp.17-21
    • /
    • 2018
  • Purpose: This study aimed to evaluate the thermal protective function of firefighter clothes and gloves through real scale fire simulations. Methods: Firstly, the fire simulation by real scale flame was performed for firefighter clothes. A manikin equipped with firefighter clothes was directly exposed to flames which energy average is 84 Kw/m2. for 22 seconds. Heat flux gauges attached on the body measured surface temperature elevation. Secondly, we also performed the other fire simulation by hot plate exposure to firefighter gloves. Firefighter gloves with heat flux gauges exposed hot plate which temperature is 300℃ in both dry and moist conditions. Primary outcome was surface temperature change of manikin body (first simulation) and hand (second simulation) over times. Results: In the first flame simulation, the surface temperature of face and shoulders elevated more rapidly comparing with the other body surface area when initial period of flame shutter open. After 18sec of shutter open, the surface temperature of upper trunk elevated rapildy. After shutter closure, high surface temperature kept continuously on right side of face and left shoulder. In the second hot plate simulation, fingers and palms showed higher surface temperature than the other areas of hands in the both dry and wet conditions. Conclusion: This study suggests that the real scale flame enables firefighter clothes to lose their heat protective function suddenly after 18 seconds. Additionally, the protective function of firefighter gloves were relatively weaker in the palmar side of fingers than the other parts of hand. There should be additional study for evaluate thermal protection performance of firefighter clothes. And, further effort for reinforce palmar side of fingers of firefighter gloves should be done.