Browse > Article
http://dx.doi.org/10.7731/KIFSE.2018.32.2.082

Analysis of the Working Conditions of Screen Fire Shutters in the Goyang Bus Terminal Fire  

Lee, Eui-Pyeong (Dept. of Fire Safety Engineering, Jeonju Univ.)
Publication Information
Fire Science and Engineering / v.32, no.2, 2018 , pp. 82-91 More about this Journal
Abstract
This study analyzed the working conditions and problems of screen fire shutters in the Goyang Bus Terminal fire based on the fire investigation results. At that time, screen fire shutters in the 1st basement, which was under construction, did not work because the power was shut off. Four screen fire shutters in the 1st and 3rd floor did not work despite the power not being shut off. The following problems related to a screen fire shutter were found: shutting off the power to screen fire shutters for the fire compartment on each floor, even when the fire compartments were changed in each area; installing an integral type screen fire shutter without any regulations, installing a two-stage screen fire shutter in a place not related to obstacles during evacuation; stopping the function of the screen fire shutters for a fire compartment on each floor after a combustible sandwich panel was comparted; installing a screen fire shutter over 10 meters in width, in which its performance was not verified; and no safety control standards for reinstalling or maintaining a screen fire shutter.
Keywords
Fire investigation; Fire shutter; Bus terminal fire; Fire case analysis;
Citations & Related Records
연도 인용수 순위
  • Reference
1 E. P. Lee, "Analysis of Lessons of a Goyang Bus Terminal Fire", Proceedings of 2015 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp. 39-40 (2015).
2 E. P. Lee, "Cause Analysis of Fire and Smoke Spread at a Goyang Bus Terminal Fire", Proceedings of 2017 Autumn Annual Conference, Korean Institute of Fire Science & Engineering, pp. 77-78 (2017).
3 E. P. Lee, "Analysis of Occurrence Cause of Many Casualties at a Goyang Bus Terminal Fire", Proceedings of 2017 Autumn Annual Conference, Korean Institute of Fire Science & Engineering, pp. 81-82 (2017).
4 E. P. Lee, "Cause Analysis of Goyang Bus Terminal Fire", Proceedings of 2017 Autumn Annual Conference, Korean Institute of Fire Investigation, p. 258 (2017).
5 E. P. Lee, "Analysis of Structural Problems at a Goyang Bus Terminal Fire", Proceedings of 2017 Autumn Annual Conference, Korean Institute of Fire Science & Engineering, pp. 79-80 (2017).
6 E. P. Lee, "A Study on the Actual Conditions and the Improving Methods of Fire Shutters", Journal of the Architectural Institute Of Korea Planning & Design Vol. 21, No. 10, pp. 247-254 (2005).
7 I. H. Yeo and K. H. In, "The Status and Improving Ways of th Fire Safety Codes for the Fire Shutters and Fire Doors", Proceedings of 2009 Spring Annual Conference, Architectural Institute Of Korea Planning & Design, Vol. 29, No. 1, pp. 567-570 (2009).
8 Y. S. Lee, "Standard and building application", Journal of Korean Institute of Fire Science & Enginnering, Vol. 4, No. 1, pp. 6-12 (2008).
9 J. P. Jeon, B. C. Min, S. M. Jeon and D. H. Lee, "A Study on the Hazard of Radiant Heat of th Fire Shutters in Fire", Proceedings of 2011 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp. 160-164 (2011).
10 W. J. Keum, J. Y. Son, G. Y. Jeon and W. H. Hong, "A Study on Effective Display Method of Single Unit Fireproof Entrance", Proceedings of 2016 Autumn Annual Conference, Korean Institute of Fire Science & Engineering, pp. 15-16 (2016).
11 H. K. Yoon, "A Study on Integral Type Fire Shutter for Securing Evacuation Safety Method", Mater's thetis, Graduate School of Construction industry, Kyonggi University, pp. 32-102 (2015).
12 S. C. Lee, Y. Y. Kim, Y. P. Hong, Y. R. Park and Y. G. Kim, "A Study on Casualty Evacuation Characteristics of Primary School with Single Unit Fireproof Shutter", Proceedings of 2009 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp. 389-395 (2009).
13 Y. S. Hwang, "A study on the flame-retardant screen applied with insulation paint on the silica nano fiber for closer space", Master's thesis, Graduate School of Engineering, Yonsei University (2011).
14 S. S. Lee, S. Y. Kim, Y. P. Hong, Y. R. Bang and Y. G. Kim, "A Study on casualty evacuation characteristics of primary school with single unit fireproof shutter", Proceedings of 2009 Spring Annual Conference, Korean Institute of Fire Science & Engineering, p. 391 (2009).
15 E. P. Lee, "Investigation and Analysis of a Goyang Bus Terminal Fire", Proceedings of 2017 Autumn Annual Conference, Korean Institute of Fire Investigation, pp. 13-42 (2017).
16 E. P. Lee, "Analysis of the Causes of Catastrophic Damage of Goyang Bus Terminal Fire and the Preventive Measures for Similar Catastrophic Fires", Journal of Scientific Criminal Investigation, Vol. 12, No. 1, p. 3 (2018).