Abstract
This study investigated the evacuation characteristics of student of elementary school with single unit fireproof shutter. In particular, we gathered the data about fireproof shutter and checked the data. And we made comparison and did an analysis of the evacuation characteristics of elementary school student according to working of single unit fireproof shutter for fires. As a result, it took the last occupant 130 seconds to escape from the school with no fire shutter case. But it took time 190 seconds to escape when the single unit fireproof shutter worked. Some of elementary school students could not open the door installed on the shutter when the single unit fireproof shutter worked. Considering this circumstance, it can be led to time delays of escaping when the single unit fireproof shutter work. And many students can be exposed to the fire hazards. Therefore, the study on the power to open the door installed on the shutter must be done in the future.
Keywords
Evacuation characteristics; Single unit fireproof shutter; Simulated fire evacuation training;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Notice of MOCT, No. 2005-232, "Standards of Automatic Fire Shutters and Fire Doors" (2005).
2 Enforcement Ordinance of NEMA, No. 24304 "Article 17, Exception of Standards for Application Fire Protection Systems at the Extension of Specified Fire Protection Object or Change of Use" (2013).
3 Notice of MLTM, No. 2010-528, "Article 5, Standards of Automatic Fire Shutters and Fire Doors" (2010).
4 Korea Consumer Agency, "Investigation of the Actual Condition in a Public Bathing Facility" (2006).
5 Enforcement Ordinance of MOLIT, No. 24568, "Article 46, The Installation of Fire Protection Areas" (2013).
6 Enforcement Regulations of MOLIT, "Article 14, The Structure of the Building Fire and Evacuation" (2013).
7 E. P. Lee, "A Study on the Actual Conditions and the Improving Methods of Fire Shutters", Journal of the Architectural Institute of Korea, Vol. 21, No. 10, pp. 247- 254 (2005).   과학기술학회마을
8 S. C. Lee, S. Y. Kim, Y. P. Hong, Y. R. Park and Y. G. Kim, "A Study on Casualty Evacuation Characteristics of Primary School with Single Unit Fireproof Shutter", Proceedings of 2009 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp. 389-395 (2009).
9 Law of MOLIT, No. 9437, "Article 49, Evacuation of the Building and Restrictions" (2009).
10 Notice of MOCT, No. 1981-327, "Standards of Automatic Fire Shutters" (1981).