• 제목/요약/키워드: Fire hose

검색결과 42건 처리시간 0.025초

일반 소방호스와 꼬임방지 소방호스의 꼬임 횟수에 따른 방수시간 분석 (Analysis of Waterproof Time by Number of Twists between Ordinary Fire Hose and Anti-twist Fire Hose)

  • 홍석환;김서영;공하성
    • 대한안전경영과학회지
    • /
    • 제23권4호
    • /
    • pp.55-60
    • /
    • 2021
  • This study is to check waterproof by number of twists of fire hose and measure the first waterproof time to analyze the relationship between twists of fire hose and first waterproof time and waterproof by position of twists so as to suggest the efficient plan to prevent twists of fire hose. Ordinary fire hose did not make waterproof in case that position of twists was near the nozzle with twists 5 times or more, while anti-twist fire hose had no problem for waterproof only with delayed time. Like ordinary fire hose, anti-twist fire hose also showed the tendency to increase the waterproof time in proportion to the number of twists. In case that the position of twists was near waterproof port even with 10 times of twists in anti-twist fire hose, the first waterproof time was increase by 0.63 seconds on average without any problem for waterproof, which was somewhat faster than that in ordinary fire hose. With respect to the position of twists, waterproof of anti-twist fire hose was affected more as the number of twists was increased more near the nozzle rather than near the waterproof port, like ordinary fire hose. In summary, anti-twist fire hose equipped with anti-twist tool at the middle connection port and the nozzle showed a good waterproof performance with delayed waterproof time regardless of number of twists, as a solution for the twist problem of ordinary fire hose.

호스걸이형 소방호스와 호스릴 소방호스의 전개시간 비교 분석 (Comparative Analysis of Preparation Time between Rack-type and Reel-type Fire Hoses)

  • 홍석환;김서영;공하성
    • 대한안전경영과학회지
    • /
    • 제23권4호
    • /
    • pp.49-53
    • /
    • 2021
  • The objective of this study was to understand which type of fire hose should be placed in indoor fireplug box upon analyzing the preparation time between rack-type fire hose and reel-type one. With respect to the type of hose, rack-type stacking method was used and hose preparation time was measured with 5 times of repeat test, separating men and women. Study results reveal that preparation time of reel-type fire hose took longer than that of rack-type one in both men and women. For both rack-type hose and reel-type hose, preparation time by two persons took shorter than that by one man. Also, preparation time by three persons took shorted than that by two women. Preparation time for both rack-type hose and reel-type one by men took shorter than that by women. In summary, it was confirmed that rack-type hose could be prepared within shorter time than reel-type one. Since the size of drum set in the reel-type fire hose is relatively small, it had some difficulty in preparation of fire hose timely.

화재현장에서 사용하는 소방호스의 마찰손실 감소 방안에 관한 연구 (A Study on the Friction Loss Reduction in Fire Hoses Used at a Fire Scene)

  • 민세홍;권용준
    • 한국화재소방학회논문지
    • /
    • 제27권3호
    • /
    • pp.52-59
    • /
    • 2013
  • 본 연구에서는 화재현장에서 사용하는 소방호스에 대하여 사용압력과 방수량 변화에 따른 마찰손실을 실측하였다. 소방호스의 종류, 수량, 사용압력 등 소방호스의 사용 실태를 분석하여 그 결과를 토대로 실측한 결과 화재현장에서 소방공무원이 사용하는 조건에서 소방호스의 마찰손실은 무려 56.8%까지 측정되었다. 옥내 외 소화전설비에서 펌프양정 계산시 사용하는 소방호스의 등가 길이와도 많은 차이가 난다. 관련규정조차 마찰손실에 대한 제한 규정이 없고, 소방호스를 생산하는 업체에서도 마찰손실을 측정한 자료가 없으며, 화재현장에서는 마찰손실을 고려하지 않고 소방호스를 전개함으로써 호스의 사용량이 많아지고 소방펌프차에서 고압으로 방수하게 되는 원인이 되므로 본 연구를 통하여 소방호스 마찰손실에 대한 등가길이 기준을 정립하고 화재현장에서 소방호스의 마찰손실을 고려한 전개 방법을 제안하고자 한다.

옥내소화전 호스 적재 방법이 신속한 화재진압에 미치는영향 (Effect of indoor fire hydrant hose loading method on rapid fire suppression)

  • 전재인
    • 문화기술의 융합
    • /
    • 제8권5호
    • /
    • pp.535-539
    • /
    • 2022
  • 이 연구는 옥내소화전의 효율적 호스 적재 방법에 대하여 분석한 것으로 실험 결과는 다음과 같다. 옥내소화전소방호스 적재 방법과 화재진압의 신속성을 비교하는 실험을 통하여 효과적인 소방호스 적재 방법을 도출하고자 한다. 접이식으로 소방호스를 적재하였을 때 평균 33초가 소요되었고, 한겹말은 소방호스 적재는 평균 69초가 소요되어유의미한 차이를 보였다. 첫째, 접이식 호스 전개 실험에서 실험대상자 A,C,D,E는 34초~37초로 각각 비슷한 수치를 나타냈다. 그 이유는 소방호스를 전개할 때 꼬임현상이 나타나지 않았고, 원활한 호스 전개가 가능하여 나타난 결과로 보인다. 실험대상자 B는 25초로 가장 낮은 전개 시간을 보였는데, 이는 B가 소방호스 전개 경험이 있어서 나타난 결과로 보인다. 둘째, 한겹말은 호스 전개 실험에서 실험대상자 A,B,C,E는 44초~76초로 각각 비슷한 시간대를 나타냈다. 그러나, 실험대상자 D는 110초로 유의하게 높게 나타났다. 그 이유는 소방호스를 전개할 때 호스 꼬임을 방지하기 위한 시도와 긴장을 통한 불안정한 심리상태가 소방호스 전개 시간을 높인 것으로 판단된다.

옥내소화전설비의 소방호스 적재방식에 따른 꼬임횟수 분석 (Analysis of the Number of Kinks with the Fire Hose Staking Method of Indoor Hydrant System)

  • 홍석환;공하성
    • 대한안전경영과학회지
    • /
    • 제23권4호
    • /
    • pp.61-66
    • /
    • 2021
  • In this study, according to the staking method of the fire hose in the indoor hydrant system, the number of kinks when the fire hose is deployed was measured and analyzed to examine how the staking method of the fire hose affects the kink when the hose is deployed. The fire hose staking method was classified into three types: donut-type, accordion-type, and hose hanger-type, and the walking speed and number of kinks were measured by repeating the experiment 5 times for male and female students. The results of the study are as follows. (1) Among the three types of fire hose staking methods, the donut-type staking method had an average of 92 times for male students and 86 times for female students on average. (2) The accordion-type and hose hanger-type staking methods showed similar results with an average of one or two kinks for both male and female students. (3) Regardless of the staking method, it was found that in general, male students with high walking speed had more kinking than female students with slow walking speed.

옥내소화전설비에서 도너츠형 적재방식의 소방호스 전개형태에 따른 방수준비시간 비교 (Comparison of Waterproofing Preparation Time with the Unfolded of Donut-type Staking Method Fire Hose in Indoor Hydrant System)

  • 홍석환;공하성
    • 대한안전경영과학회지
    • /
    • 제23권3호
    • /
    • pp.115-122
    • /
    • 2021
  • In this study, the purpose of this study was to examine the effect of twisting in the preparation of waterproofing in the process of unfolded donut-type staking method fire hoses in indoor hydrant system. The central pull-out method caused more twisting than the rolling method, and there was no significant difference in the number of twists according to the pull-out method in the case of male and female students. It was found that the time it took to untwist and prepare waterproofing was much shorter for male students. The angle valve and hose are connected, and the time to untwist and prepare for waterproofing after withdrawing the fire hose with the hose and nozzle connected was shorter than the unconnected state. In the rolling method, when a hose connected with two 15 m fire hoses was used and the angle valve-hose was connected, but the hose-nozzle was not connected, the least kinking occurred. The time to untwist and prepare for waterproofing was also the shortest. As a result, in the withdrawal method of the donut-type loaded fire hose in the indoor hydrant system, it is a rolling method rather than a central withdrawal method. With the angle valve and hose connected, unfold the fire hose with the hose and nozzle connected, if a large number of people unwind the twisted hose, the time to prepare for waterproofing can be shortened.

Measurement of the Time Taken for Initial Water Discharge According to the Number of Kinks in the Fire Hose of the Indoor Hydrant System

  • Hong, Suk-Hwan;Kong, Ha-Sung
    • International Journal of Advanced Culture Technology
    • /
    • 제9권3호
    • /
    • pp.360-366
    • /
    • 2021
  • In this study, we tried to examine how the kinking of the fire hose affects the time taken for initial water discharge by measuring and analyzing the time taken for initial water discharge with different number of kinks at different locations of the hose. The average time taken for initial water discharge was obtained by measuring the time in the unkinked state of the fire hose. Based on this standard, we conducted the experiment by selecting the kinking locations in the hose near the water outlet and nozzle, and setting the number of kinks to 3, 6, 9, and 12. The results of this study are as follows: First, if the fire hose has 5 kinks or more near the nozzle, no water was released. Second, when comparing the case of no kinks and 4 kinks near the nozzle, there was no significant difference in the time taken for initial water discharge. Third, when the fire hose was kinked 10 times near the outlet, the time required for initial water discharge increased by 1.62 seconds on average compared to the case with no kinking, but there was no problem with water discharge. Lastly, regarding the kinking locations of the fire hose, it was found that the greater the number of kinks near the nozzle than near the outlet, the greater the effect on the discharge. As a result, it is concluded that it would be preferable to install non-kinking devices near the nozzle of the fire hose.

화재진압 시 발생하는 주수 기둥의 저항분석 방법 연구 (A Study on the Method of Resistance Analysis of Water Stream During Fire Supperession)

  • 정병선;김응식;박종열
    • 한국안전학회지
    • /
    • 제33권6호
    • /
    • pp.22-27
    • /
    • 2018
  • Fire fighters are exposed to the risk of many accidents during fire suppression, especially near the high voltage circuit. In order to prevent and analyze the electric shock accidents, measurement of water resistance is crucial. However, this has been one of the overlooked research areas and it has been very difficult to measure the mixed up resistance components separately. In this paper, we measured a total resistance of apparatus and regarded it as a serial resistance of contact resistance and length dependant resistance. Measuring the resistance by varying the length of water stream, the variable resistance and fixed contact resistance appear, which are used to calculate the both components of resistances. In addition, the resistance of fire hose can be calculated from the parallel circuit which is formed by grounding the fire hose with the resistance of water stream. Results show that we can successfully measure the resistance per unit length of water stream and fire hose, thereby proving that this method is a facile way to measure water and fire hose resistance. However, many experiments are still required to obtain the precise contact resistance of ground under various condition and the resistance between the human body and fire hose.

호스릴옥내소화전 호스에 대한 압력손실에 관한 연구 (Study on the Pressure Loss of Hoses in a Fire Hose Reel Hydrant)

  • 황영권;이승철
    • 한국화재소방학회논문지
    • /
    • 제33권2호
    • /
    • pp.63-67
    • /
    • 2019
  • 본 연구에서는 호스릴옥내소화전의 압력손실 실험을 실시한 후 각 요소의 압력 손실에 미치는 영향을 비교 분석하였다. 첫째, 호스릴옥내소화전의 호스릴 길이에 따른 압력손실 실험에서, 호스릴의 길이가 길어짐에 따라 압력 손실이 증가하였으며, 이는 25 m 호스를 기준으로 일반 옥내소화전 호스에 비하여 38.86% 만큼 압력손실이 증가하는 것을 알 수 있었다. 둘째, 단위 길이 당 호스릴의 압력손실은 $.13{\sim}.15kgf/cm^2$으로 측정되었다. 셋째, 유량의 변화에 따른 압력손실 실험에서는 일반 배관 유동에서의 유량-압력손실 관계(${\Delta}P{\sim}Q^2$)와 유사한 결과를 얻을 수 있었다. 이 연구 결과는 호스릴옥내소화전이 사용되는 건축물에 펌프의 양정계산, 호스릴옥내소화전의 성능위주소방설계에 기초자료로 활용될 수 있을 것이다.

소방호스 밀착강도시험방법에 관한 연구 (A Study on Adhesion Test Methods for Fire Hose)

  • 김준배;백창선;김학진
    • 한국화재소방학회논문지
    • /
    • 제15권1호
    • /
    • pp.66-74
    • /
    • 2001
  • 소방호스의 밀착강도 시험방법을 개선하기 위하여 5개국(한국, 미국, 영국, 중국, 일본), 7개의 기술기준(KOFEIS, UL, FM, NFPA, BS, 중국기술기준, JIS, 일본검정기술기준)을 비교 고찰하고, 국내에서 생산되는 소방호스를 무작위로 발췌하여 밀착강도시험을 실시하였다. 밀착강도시험 및 기술기준 비교 고찰을 통하여 밀착강도시험은 소방호스의 호칭별로 시험시료의 크기와 박리시험속도 및 판정기준을 세분화함으로서 소방호스의 밀착강도를 개선시킬 수 있다는 결론을 얻었다.

  • PDF