Browse > Article
http://dx.doi.org/10.12812/ksms.2021.23.4.055

Analysis of Waterproof Time by Number of Twists between Ordinary Fire Hose and Anti-twist Fire Hose  

Hong, Suk-Hwan (Deokwon Technical Team Co., Ltd)
Kim, Seo-Young (Fire and Disaster Prevention, Woosuk University)
Kong, Ha-Sung (Fire and Disaster Prevention, Woosuk University)
Publication Information
Journal of the Korea Safety Management & Science / v.23, no.4, 2021 , pp. 55-60 More about this Journal
Abstract
This study is to check waterproof by number of twists of fire hose and measure the first waterproof time to analyze the relationship between twists of fire hose and first waterproof time and waterproof by position of twists so as to suggest the efficient plan to prevent twists of fire hose. Ordinary fire hose did not make waterproof in case that position of twists was near the nozzle with twists 5 times or more, while anti-twist fire hose had no problem for waterproof only with delayed time. Like ordinary fire hose, anti-twist fire hose also showed the tendency to increase the waterproof time in proportion to the number of twists. In case that the position of twists was near waterproof port even with 10 times of twists in anti-twist fire hose, the first waterproof time was increase by 0.63 seconds on average without any problem for waterproof, which was somewhat faster than that in ordinary fire hose. With respect to the position of twists, waterproof of anti-twist fire hose was affected more as the number of twists was increased more near the nozzle rather than near the waterproof port, like ordinary fire hose. In summary, anti-twist fire hose equipped with anti-twist tool at the middle connection port and the nozzle showed a good waterproof performance with delayed waterproof time regardless of number of twists, as a solution for the twist problem of ordinary fire hose.
Keywords
IOrdinary fire alarm Hose; Anti-twist Fire Hose; Number of Twist; Waterproof Time;
Citations & Related Records
연도 인용수 순위
  • Reference
1 J. S. Nam, S. H. Sakong, C. S. Baek, J. Y. Park, N. H. Cho, K. W. Yun(2002), "A study on the inspection of actual condition and he assessment of performance in fire hose." Fire Science and Engineering, 2002:242-247.
2 Ministry of Government Legislation(2021, April 1), Fire safety standards for indoor hydrant system. Article 7(2), Partial Revision.
3 H. E. Lee(2020), "An experimental study on pressure loss in fire hose under various deployment situations." Fire Safety Research, 1(1):116-118.
4 YookSong, http://www.yooksong.com/kor/product/product07_view02
5 M. E. Benfer, E. Forssell, J. Scheffey(2017), "Determination of fire hose friction loss characteristics." Fire Technology, 53(3):1059-1062.   DOI
6 Korea Ministry of Government Legislation(2019), Technical standard for type approval and product inspection of fire hose Article 2 No.1~No.8. 1. 10. Enforcement.
7 H. S. Kong, J. M. Yun, J. H. Lee, K. C. Kim(2012), "A study on connection of fire hose." Journal of the Korea Safety Management & Science, 2012(11):93-98.
8 S. H. Min, S. H. Jung(2012), "A study on improvement of discharge pressure measurement of indoor fire hydrant system." Fire Science and Engineering, 26(3):67-72.   DOI