• Title/Summary/Keyword: Fire Simulation(FDS)

Search Result 200, Processing Time 0.033 seconds

Development of the Program(FDS2EXODUS) for Generating Hazard condition file of Building-EXODUS code based on the FDS Fire-simulation Data (화재모사전용 FDS code의 계산값을 이용하여 피난해석 BuildingEXODUS code의 피난의 환경조건 파일을 생성하는 프로그램(FDS2EXODUS) 개발)

  • Kim, H.B.;Jang, Y.J.;Jung, W.S.;Park, W.H.;Lee, D.H.
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2009.04a
    • /
    • pp.570-575
    • /
    • 2009
  • In this paper shows the development of the Program(FDS2EXODUS) for Generating Hazard condition file of BuildingEXODUS code based on the FDS Fire-simulation Data. The program were applied with numerical method to translate from FDS to BuildingEXODUS. Using both single or multi block meshes of FDS get to be possible. For application of fire effect, the fire data were loaded directly to BuildingEXODUS in the case of FDS code with using this Program(FDS2EXODUS). It was very convenient to input to BuildingEXODUS and could be reduced the procedure of egress simulation from fire disaster.

  • PDF

Simulation of Heat and Smoke Behavior for Wood and Subway Fires by Fire Dynamics Simulator(FDS) (FDS에 의한 목재 및 지하철 화재의 열 및 연기 거동 시뮬레이션)

  • Sonh, Yun-Suk;Dan, Seung-Kyu;Lee, Bong-Woo;Kwon, Seong-Pil;Shin, Dong-Il;Kim, Tae-Ok
    • Journal of the Korean Institute of Gas
    • /
    • v.14 no.6
    • /
    • pp.31-37
    • /
    • 2010
  • In this study, to propose the analysis method of heat and smoke behavior of fire using the CFD-based fire simulator FDS, comparison of the simulation results against the experimental results and the sensitivity of the results to the grid sizes have been investigated. For the wood fire, thermal images captured from the experiments were compared against the FDS simulations, and the maximum temperatures agreed in~4.3 % error, showing the applicability of FDS in the interpretation of the fire phenomena. In the aspect of the sensitivity to the grid size for the subway fire, FDS results of smoke temperature, CO concentration and visibility converged and showed no distinct changes for the grid size < $28(L){\times}28(W){\times}14(H)$, guaranteeing that the FDS fire model set in this research could interpret the fire phenomena successfully.

A Study on the Modeling of Vertical Spread Fire of Exterior Panel by Fire Dynamic Simulation (FDS) (FDS를 이용한 외장재의 수직 확산 화재의 모델링에 관한 연구)

  • Min, Seh-Hong;Yoon, Jung-En
    • Journal of the Korea Safety Management & Science
    • /
    • v.11 no.2
    • /
    • pp.77-85
    • /
    • 2009
  • Considering heat insulation and beautiful sight of construction, making use of exterior panels is increasing. Recently the exterior panels now are weak very much, and so in consequence of the weakness fire spreads rapidly. Compared with internal fire, external vertical fire spread rate goes rapidly and it is extensive in spread range, therefore it is dangerous very much. Accordingly, under present condition of poor standard of exterior panels, it is required to take measure to meet the appropriate situation. In this study, by making use of FDS(Fire Dynamic Simulation) program about external vertical fire of high rise building, fire behavior is searched by computer. It is important that realizing by computer fire modeling about external vertical fire must be included certainly in procedure of fire performance design in the future. In modeling program, FDS version 5 is available, and aluminium composite panel is applied in external panels. In this study, for realizing of actual fire condition, FDS is applied by details of fire scenarios considering influence of wind.

Simulation of Pool Fire with Two Rooms Using FDS Model (화재분석모델을 이용한 이중격실화재 검증분석)

  • Kim, Bong-Hyun;Bae, Yong-Bum;Ryu, Su-Hyun;Lee, Gong-Hee;Kim, Yun-Il;Moon, Chan-Ki;Park, Jong-Seok
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.1332-1337
    • /
    • 2008
  • Fire model shall be verified and validated to reliably predict the consequences of fires within its limitations. This study aims to predict pool fire with two rooms using FDS and to coompare FDS simulation results with PRISME experimental data which can be applicable to the fire of nuclear power plant facility. Four different sizes of grid (0.08m, 0.1m, 0.125m, 0.2m) are used in the simulation and the simulated results of specific quantities such as temperature, chemical composition, heat flux and heat release rate are compared to the experimental data. From this study, the FDS simulation results with the finer grid resolution show better similarity and trend with pool fire experimental data. The sensitivity analysis and the selection of the proper size grid are essential to predict the consequences of pool fire with two rooms reliably.

  • PDF

Comparative Study on The Numerical Simulation for The Back-Layer of The Tunnel Fire-Driven Flow with LES and RANS (터널화재유동의 역기류 해석을 위한 LES 및 RANS 결과의 비교 고찰)

  • Jang, Yong-Jun;Kim, Hag-Beom;Kim, Jin-Ho;Han, Seok-Youn
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.33 no.3
    • /
    • pp.156-163
    • /
    • 2009
  • In this study, comparative analysis on the back-layer phenomena in the tunnel-fire driven flow is performed using numerical simulation with LES and RANS. FDS(Fire Dynamics Simulator) code is employed to calculate the fire-driven turbulent flow for LES and Smartfire code is used for RANS. Hwang and Wargo's data of scaling tunnel fire experiment are employed to compare with the present numerical simulation. The modeled tunnel is 5.4m(L) ${\times}$ 0.4m(W) ${\times}$ 0.3m(H). Heat Release Rate (HRR) of fire is 3.3kW and ventilation-velocity is 0.33m/s in the main stream. The various grid-distributions are systematically tested with FDS code to analyze the effects of grid size. The LES method with FDS provides an improved back-layer flow behavior in comparison with the RANS (${\kappa}-{\epsilon}$) method by Smartfire. The FDS solvers, however, overpredict the velocity in the center region of flow which is caused by the defects in the tunnel-entrance turbulence strength and in the near-wall turbulent flow in FDS code.

Comparison of the Flame Height of Pool Fire according to Combustion Models in the FDS (FDS의 연소모델에 따른 풀화재의 화염높이 비교)

  • Han, Ho-Sik;Hwang, Cheol-Hong;Oh, Chang Bo;Choi, Dongwon;Lee, Sangkyu
    • Fire Science and Engineering
    • /
    • v.32 no.3
    • /
    • pp.42-50
    • /
    • 2018
  • The effect of sub-grid turbulence and combustion models on the mean flame height in a heptane pool fire according to the Fire Dynamics Simulator (FDS) version (5 and 6) based on Large Eddy Simulation (LES) was examined. The heat release rate for the fire simulation was provided through experiments performed under identical conditions and the predictive performance of the mean flame height according to FDS version was evaluated by a comparison with the existing correlation. As a result, the Smagorinsky and Deardorff turbulence models applied to FDS 5 and 6, respectively, had no significant effects on the mean flow field, flame shape and flame height. On the other hand, the difference in pool fire characteristics including the mean flame height was due mainly to the difference in the mixture fraction and Eddy Dissipation Concept (EDC) combustion models applied to FDS 5 and 6, respectively. Finally, compared to FDS 6, FDS 5 provided the predictive result of a significantly longer flame height and more consistent mean flame height than the existing correlation.

Evaluation of the Prediction of B-RISK-FDS-Coupled Simulations for Multi-Combustible Fire Behavior in a Compartment (구획실 내 가연물들의 화재거동에 대한 B-RISK와 FDS 연계 화재 시뮬레이션 예측성능 평가)

  • Baek, Bitna;Oh, Chang Bo
    • Fire Science and Engineering
    • /
    • v.33 no.4
    • /
    • pp.50-58
    • /
    • 2019
  • The prediction performance of B-RISK was evaluated for the fire behaviors of combustibles in a compartment using Fire Dynamics Simulator (FDS). First of all, to predict the heat release rate (HRR) for two combustible sets, the HRR for one combustible set and the design fire curve were used as input values for B-RISK. Comparing results of B-RISK calculations with experimental data for two combustible sets, it was found that B-RISK results predicted insufficiently for fire growth rate of experimental data but there was good agreement for maximum HRR and total HRR with the experimental data. And the B-RISK results were used for input values of FDS to evaluate the fire behaviors of B-RISK results. Comparing results of FDS calculations with experimental data, the simulation results showed that the temperature and concentrations of O2, CO2 in the fire growth phase were different from the experimental data. However, when using the B-RISK result for percentile 70%, the simulation results sufficiently predicted the overall fire behaviors.

A Fire Computer Simulation of Inner Space with Fire Shutters and Refuge Stairs (방화셔터와 피난계단이 존재하는 실내 환경의 화재 컴퓨터 시뮬레이션)

  • Yoo, Doo-Yul;Yang, Jung-Min
    • The Journal of the Korea institute of electronic communication sciences
    • /
    • v.8 no.11
    • /
    • pp.1617-1624
    • /
    • 2013
  • This paper analyzes the relation between fire shutters and fire spread by conducting fire simulation on inner space with fire shutters. Using Fire Dynamics Simulator (FDS), a commercial fire simulation software, the simulation is done on an ideal inner robby, where fire size and the open/close of fire shutters are varied. Our simulation environment can derive significant fire parameters such as temperature variation of fire room walls and entrances of refuge stairs, variation of carbon dioxide, and soot spread. According to the simulation results, temperature and carbon dioxide distribution in refuge stairs have little dependence on vent open or close, but the part close of fire shutters blocks soot inflow to refuge stairs.

Fire Simulations (화재시뮬레이션)

  • Kim Sang-Moon;Yoon Sang-Youl;Kim Kyung-Chun
    • Journal of the Korean Society of Visualization
    • /
    • v.4 no.1
    • /
    • pp.8-13
    • /
    • 2006
  • Fire simulation has been developed for decades to analyze fire cases and provide a tool to study fundamental fire dynamics and combustion. There are three way of fire simulation which are a full scale simulation, an experimental simulation and a computational simulation. In case of a full scale simulation, because a higher cost, a higher risk, more efforts are needed, a demand for it has been decreased. But recently a demand for an experimental simulation and a computational simulation has been increased. A computational simulation has several advantages; lower cost, short period, many case studies, more visual results, a quantitative result and etc. FDS(Fire Dynamics Simulator) which has been developed in BFRL(Building and Fire Research Laboratory), NIST(National Institute of Standards and Technology) is a popular world wide code for fire simulation. Lack of accurate predictions by the model could lead to erroneous conclusions with regard to fire safety. All results should be evaluated by the informed judgment of the qualified user.

  • PDF

Fire Simulation by Pyrolysis Method of FDS for the Small Cone Calorimeter (ISO 5660) (FDS 열분해 모델을 이용한 콘칼로리미터(ISO 5660) 화재 시뮬레이션)

  • Yang, Sung-Jin;Jang, Jung-Hun;Kang, Chan-Yong
    • Proceedings of the KSR Conference
    • /
    • 2009.05a
    • /
    • pp.206-212
    • /
    • 2009
  • Chemical behaviors of each surface material for interior facilities affect to fire initiation and growth in general fire situation. These chemical behaviors were characterized by thermal properties (Heat release rate, Pyrolysis rate, specific heat, etc) which could be derived from experimental test. Especially, Heat release rate which indicates aspect of fire size is one of the most important property to asses fire hazard and protection needs. The cone calorimeter test (ISO 5660) has recently assumed to a dominant role in bench scale fire testing to obtain the Heat release rate of materials. This value could be calculated by the 'Oxygen Consumption Method' under various producing irradiances to each surface of materials. In this study, Process of the cone calorimeter test was simulated by Pyrolysis model of FDS (Fire Dynamics Simulator by NIST) base on the ISO 5660 international standard. Then, we could estimate the simulation method of FDS in case of single materials through the comparative study with test results.

  • PDF