• 제목/요약/키워드: Fire Experiment of a Single Area

검색결과 5건 처리시간 0.02초

단일구획실험을 통한 화재안전설계에 관한 기초적 연구 (A Basic Study on the Fire Experiment of a Single Area for Fire Safety Design.)

  • 김동은;윤웅기;서동구;권영진
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2013년도 추계 학술논문 발표대회
    • /
    • pp.110-111
    • /
    • 2013
  • This research studies in the field of domestic fires are an issue in many scientific fire research as a research method to validate the domestic environment and ISO-9705 housing on the basis of experiments in virtual space by making a single fire compartment space for conducting experiments and Appearance of a fire occurring within each flammable Heat Release Rate analysis was carried out mainly. Placed within the space of one flammable HRR calculated as the sum of the number of single-room fire experiments conducted and the results compared with the value in comparing the conduct of fire locations and fire load within the building area of the future, the HRR value represents the change in domestic a consideration of the safety of the building is to propose matters.

  • PDF

단일화재실험을 통한 화재성상예측 및 건축구조물의 화재안전 설계에 관한 연구 (A Study on the Fire Safety Design and Predicting Fire Behavior Using Compartment Fire Test)

  • 윤웅기;서동구;김동은;권영진
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2013년도 춘계 학술논문 발표대회
    • /
    • pp.107-108
    • /
    • 2013
  • In this study, combustibles investigation and fire growth rate experiment were performed for predicting initial fire behavior in buildings. Combustibles investigation was performed for residential buildings, which is most frequently affected by fire in Korea. Spatial characteristics and combustibles properties were separately investigated, and occupied area and layout characteristics of combustibles were identified to produce general layout models. Of the layout models, room was selected for fire test of a single compartment. From this test, fire propagation for each combustible was identified, which was delayed compared to the summed heat release rate of a single combustible.

  • PDF

성능위주설계를 위한 가연물의 열발생률 및 화재성장률 측정 - 판매시설의 플라스틱 화재를 중심으로 - (Measurements of the Heat Release Rate and Fire Growth Rate of Combustibles for the Performance-Based Design - Focusing on the Plastic Fire of Commercial Building)

  • 장효연;남동군
    • 한국화재소방학회논문지
    • /
    • 제32권6호
    • /
    • pp.55-62
    • /
    • 2018
  • 국내 성능위주소방설계(PBD)에 신뢰성이 향상된 예측결과를 기여하고자 판매시설 가연물 중 플라스틱으로만 이루어진 제품을 대상으로 실규모 화재실험이 수행되었다. 이때 판매시설의 경우 다양한 가연성 물질이 진열된 판매대의 간섭 또는 상품 적재 등으로 인한 화재확산의 검토를 위하여 단일 및 다수가연물로 분리되어 실험조건이 선정되었다. 이에 따라 최대 열 발생률에 따른 가연물의 노출 면적 및 중량은 대략 93%와 89%의 매우 선형적인 관계를 확인할 수 있다. 또한 다양한 가연물에 대한 가스농도의 분석 결과 이산화탄소($CO_2$)는 최대 열 발생률에 대하여 선형적인 관계를 나타내는 반면 일산화탄소(CO)는 지수함수의 형태를 나타낸다. 이러한 결과는 판매시설에서 발생되는 플라스틱 화재의 PBD에 신뢰성있는 화원정보로서 적용될 수 있다. 추후 실제 판매시설에서 적용되는 진열대의 면적이 적용된 추가적인 실험을 통하여 판매시설의 플라스틱 화재에 대표되는 화원 정보로서 적용할 수 있을 것이라 기대된다.

실내 가스 폭발시 폭발압력 방출에 관한 연구 (A Study on the Explosion Relief Venting in the Gas Explosion)

  • 오규형
    • 한국안전학회지
    • /
    • 제20권3호
    • /
    • pp.71-77
    • /
    • 2005
  • This study aims to find the safe vent area to prevent a destruction of building by gas explosion in a building. Explosion vessel which used in this experiment is 1/5 scale down model of simple livingroom and its dimension is 100cm in length 60cm in width and 45cm in height. Liquified petroleum gas(LPG) was injected to the vessel to the concentration of 4.5vol%, and injection rate were varied in 1L/min or 4L/min. Gas mixture was ignited by the 10kV electric spark. For analysis the characteristics of vented explosion pressure according to the vent size and vent shape, its size and shape were varied. From the experiment, it was found that explosion pressure in the vented explosion :in affected by the gas injection rate, vent area and vent shape. And the vent area to volume ratio(S/V) to prevent the building destruction by explosion pressure, it is recommended that the design of vent area happened by the explosion should be above 1/500cm in S/V. And if the vent area has complicate structure in same area, vented explosion pressure will be higher than a single vent, and possibility of building destruction will increase. Therefore to effectively vent the explosion pressure for protect a building and residents from the gas explosion hazards, the same vent area should have a singular and constant shape in the cross-sectional area of the vessel.

물과 공기가 공급되는 2유체노즐을 활용한 에탄올 풀화재 소화 실험 (Ethanol Pool Fire Extinguishing Experiment Using Twin-fluid Nozzle Supplied with Water and Air)

  • 정찬석;이치영
    • 한국화재소방학회논문지
    • /
    • 제33권3호
    • /
    • pp.37-43
    • /
    • 2019
  • 본 연구에서는 2유체노즐을 이용하여 에탄올 풀화재(Ethanol pool fire) 소화 실험을 수행하였다. 화원 면적이 5.027 × 10-3 ㎡와 1.131 × 10-2 ㎡(연료팬 직경은 각각 80 mm와 120 mm)를 대상으로 하였고, 화재 소화 실험 시 2유체노즐로의 공급 유량의 경우 물은 156-483 g/min, 공기는 20-70 L/min 조건이었다. 화원 면적이 증가하면 열방출률도 증가하였고, 화원 면적이 5.027 × 10-3 ㎡와 1.131 × 10-2 ㎡일 때의 열방출률은 각각 1.01 kW와 5.51 kW로 측정되었다. 본 실험 영역에서 2가지 화원 면적 조건 모두, 물 공급 유량 조건과는 상관없이 공기 공급 유량이 40 L/min 이상의 조건에서 소화가 가능하였다. 소화 소요 시간 및 물 소모량의 경우 모든 물 공급 유량 조건에서 공기 공급 유량이 증가함에 따라 감소하는 경향이 관찰되었고, 공기 공급 유량이 비교적 많은 영역(예를 들면, 약 50 L/min 이상)에서 소화 소요 시간은 약 23 s, 물 소모량은 약 185 g 이내로 나타났다. 본 연구 결과와 단일유체노즐을 이용한 기존 연구 간 단위 열방출률 당 물 소모량 비교를 통하여, 2유체노즐이 단일유체노즐에 비해 더 적은 물 소모량으로 소화가 가능할 수 있음을 확인하였다.