• Title/Summary/Keyword: Fin-and-tube condenser

Search Result 56, Processing Time 0.02 seconds

Determination of Heat-Transfer Coefficients and Pressure tosses and their Correlation for Design of a Air-Cooled Condenser (공랭식 복수기 설계를 위한 열 전달계수 및 압력손실 측정과 상관 식 결정)

  • 김성원;권세준;이지은;이상호;이정훈;이재두
    • Proceedings of the KAIS Fall Conference
    • /
    • 2003.06a
    • /
    • pp.75-78
    • /
    • 2003
  • These experiments is to determine design equations for heat transfer and for pressure drop in a new designed heat exchanger with the waved circular fin tube bundles under various experimental conditions. The results with waved circular fin tube bundles are compared with those with the flat circular fin tube bundles. Heat transfer coefficients in the waved circular fin tubes were enhanced to about 50% in comparison with those in the flat circular fin tubes, This is expected to reduce the capacity of a heat exchanger up to 30%.

  • PDF

Condensation heat transfer characteristics of R-22 and R-407C in micro-fin tubes (마이크로핀관에서의 냉매 R-22, R-407C의 응축전열특성에 관한 연구)

  • Roh, Geon-Sang
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.32 no.1
    • /
    • pp.50-56
    • /
    • 2008
  • Experimental results for forced convection condensation of Refrigerant-22 and ternary Refrigerant-407C(HFC-32/125/134a 23/25/52 wt%) which is being considered as a substitute R-22 inside a horizontal micro-fin tube are presented. The test section was horizontal double-tube counterflow condenser with a length 4,000 mm micro-fin tube, having 8.53 mm ID, 0.2 mm fin height and 60 fins. The range of parameters of mass velocity were varied from 102.1 to 301.0 kg/(m2.s) and inlet quality 1.0. At the given experimental conditions. the average heat transfer coefficients for R-407C were lower than that for R-22 at a micro-fin tube. Over the mass velocity range tested. the PF(penalty factor) for R-22, R-407C were lower than the increasing ratio of heat transfer area by fins, and the EF(enhancement factor) for R-22, R-407C were higher than the increasing ratio of heat transfer area by fins.

Experimental study for the pressure drop of R-22 and R-4O7C during the condensation in the micro-fin tubes (마이크로핀관내에서 R-22와 R-4O7C의 응축압력강하 특성에 관한 실험적 연구)

  • Roh, Geon-Sang
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.31 no.6
    • /
    • pp.715-722
    • /
    • 2007
  • Experiments were conducted for the investigation of pressure drop inside horizontal micro-fin tubes during the condensation of R-22 and ternary refrigerant. R-407C(HFC-32/125/134a 23/25/62 wt%) as a substitute of R-22. The condenser is a double-tube and counterflow type heat exchanger which is consisted with micro-fin tubes having 60 fins with a length of 4000mm, outer diameter of 9.53mm and fin height of 0.2mm. The mass velocity varied from 102.1 to $301.0kg/(m^2{\cdot}s)$ and inlet quality was fixed as 1.0. From the experimental results. the pressure drop for R-407C was considerably higher than that for R-22. The value of PF(penalty factor) for both of refrigerants was not bigger than the ratio of micro-fin tube area to smooth tube area. Based on the experimental data. correlation was Proposed for the prediction of frictional pressure drop during the condensation of R-22 and R-407C inside horizontal micro-fin tubes.

Performance Analysis of Integral Receiver/Dryer Condenser for Automobile (자동차용 리시버/건조기 일체형 응축기의 성능해석)

  • Won, Sung-Pil
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.3
    • /
    • pp.245-252
    • /
    • 2007
  • The important problems from the point of view of preventing global warming are to save the power consumption of automotive air-conditioning systems and reduce the refrigerant amount filled. To achieve such requirements, integral receiver/dryer (R/D) condensers were developed recently. Typical integral R/D condensers have extra headers that play the role of R/D. Except an extra header and somewhat complex tube array resulting from the extra header, the most integral R/D condensers have almost the same specification that tube has multi channels, fin has louvers, flow in tube is parallel, etc. When integral condensers are applied, it is known that the refrigerating effect increases, resulting from the increase of subcooling degree in condenser, and the refrigerant amount used saves. In spite of several merits, integral condensers have not been applied a lot. That is why there is an uncertainty in performance, using integral condensers. The objective of this study is to theoretically optimize the tube array in an integral R/D condenser that is really being applied to some vehicles. The tube array has a great effect on the performance of the integral condenser as well as common ones. Through computer simulation, we could see that the tube array, 14-6-3-5-3-4, in the same condenser was the best, comparing heat release rate, pressure drop, etc. to the real array, 17-5-3-3-2-5. It should be noted that the optimization is based on the condenser performance only.

Advances In Air-Cooled Heat Exchanger Technology for Residential Air-Conditioning

  • Webb Ralph L.;Kim Nae-Hyun
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.13 no.4
    • /
    • pp.184-195
    • /
    • 2005
  • This paper describes the recent work on advanced technology concepts applied to air cooled heat exchangers for residential air-conditioning. The concepts include vortex generators for the air-side, micro-fin or flat tubes for the refrigerant-side. Advances in understanding of heat transfer mechanisms, predictive models are discussed.

Heat Transfer Characteristics of Cost Effective Plate Fin-tube Condenser for Household Refrigerator (가정용 냉장고의 응축기 비용저감을 위한 판형 핀-관 열교환기의 열전달 특성)

  • Son, Young-Woo;Lee, Jang-Ho
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.323-327
    • /
    • 2008
  • 본 연구는 판형 핀-관 열교환기의 열전달 특성을 상용 CFD 코드인 SC/Tetra를 사용하여 해석한 내용에 관한 것이다. 해석조건은 입구속도 0.63 m/s, 튜브온도 $44.5^{\circ}C$이다. 해석 열교환기는 총6가지로 검토하였으며 각각의 온도분포와 유동패턴을 해석하고 판형 핀-관 열교환기의 열전달 특성을 비교 검토하였다.

  • PDF

Study on the pressure drop of ternary refrigerant R-407c during condensation inside horizontal micro-fin tubes (3성분 혼합냉매 R-407c의 수평 마이크로핀관내 응축압력강하에 관한 연구)

  • 정재천
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.22 no.2
    • /
    • pp.210-218
    • /
    • 1998
  • Experimental results for forced convection condensationof Refrigerant-22 and ternary Refrigerant-407c(HFC-32/125/134a 23/25/52 wt%) considered as a substitute R-22 inside horizontal micor-fin tubes are presented. The test section was horizontal double-tubed counterflow condenser with a length 4000 mm micro-fin tube having 9.53 mm OD., 0.2 mm fin height and 60 fins. The refrigerants R-22 and R-407c were cooled by a coolant circulated in a surrounding annulus. The range of parameters of mass velocity was varied from 102.1 to 301.0kg/($\textrm{m}^{2}.s$) with inlet quality 1.0. Both refrigerant R-22 and its alternative refrigerant R-407c were tested within the same range of parameters. At the given experimental conditions for R-22 and R-407c the pressure drops for R-407c were considerably higher than those for R-22 at micro-fin tubes. Over the mass velocity range tested the PF(penalty factor)was lower than the increasing ratio of heat transfer area by fins. Based on the data correlation was proposed for predicting the frictional pressure drops for R-22 and R-407c for a duration of condensation inside a horizontal micro-fin tube.

  • PDF

A Study on Finned Tube Used in Turbo Refrigerator( I ) -for Condensation Hear Transfer- (터보 냉동기용 핀튜브에 관한 연구 ( I ) - 응축 열전달에 관하여 -)

  • Cho, Dong-Hyun;Han, Kyu-Il;Kim, Si-Young
    • Journal of Fisheries and Marine Sciences Education
    • /
    • v.5 no.1
    • /
    • pp.31-44
    • /
    • 1993
  • Through the early 1900's, the evolution of the surface condenser was closely tied to the development of steam engine and the turbine. As the chemical and petroleum industries evolved in the 1900's, the use of surface condensers in many different processes. Today, industry uses condensers in many shapes and sizes. The actual condensation process occurs on the outside surface of tubes. The nature of this surface geometry affects the condenser's heat transfer performance. The first condensers were built with plain tubes. As tube manufacturing techniques advanced, manufacturers started making tubes with integral fins. In the 1940's, fin densities were limited to about 600 to 700 fins per meter(fpm) because of manufacturing procedure. Today new manufacturing techniques allow production of tubes with fin densities ranging from 750 to 1600 fpm. The integral-fin tubes investigated in this paper are nominally 19 mm diameter. Eight tubes have been used with trapezodially shaped integral-fins having fin density from 748 to 1654 fpm and 10, 30 grooves. For comparison, tests are made using a plain tube having the same inside diameter and an outside diameter equal to that at the root of the fins for the finned tubes. Betty and Katz's theoretical modelis is used to predict the R-11 condensation coefficient on horizontal integral-fin tubes having 748, 1024 and 1299 fpm. Experiments are carried out using R-11 as working fluid. The refrigerant condensates at a saturation state of $30^{\circ}C$ on the outside tube surface cooled by coolant. The amount of noncondensable gases present in the test loop is reduced to a negligible value by repeated purging. For a given heat input to the boiler and given cooling water flow rate, all test data are taken at steady state. The observed heat transfer enhancement for the finned and grooved tubes significantly exceeded that to be expected on grounds of increased area. For the eight fin tubes and one plain tube tested, the best performance has been obtained with a tube having a fin density of 1299 fpm, and a fin bight of 1.2mm and 30 grooves.

  • PDF

Prediction and Experiment of Pressure Drop of R22, R407C and R410A on Design Conditions of Condenser (응축기의 설계조건에서 R22, R407C, R410A의 압력강하 예측 및 실험)

  • 김창덕;박일환;이진호
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.1
    • /
    • pp.42-53
    • /
    • 2004
  • An experimental study on the refrigerant-side pressure drop of slit fin-tube heat exchanger has been carried out. A comparison was made between the predictions of previously proposed empirical correlations and experimental data for the pressure drop on design conditions of condenser in micro-fin tube for R22 and its alternatives, R407C (R32/125/134a, 23/25/52 wt.%) and R410A (R32/125, 50/50 wt.%). Experiments were carried out under the conditions of inlet refrigerant temperature of 6$0^{\circ}C$ and mass fluxes varying from 150 to 250 kg/$m^2$s for R22, R407C and R410A. The inlet air conditions are dry bulb temperature of 35$^{\circ}C$, relative humidity of 40% and air velocity varying from 0.68 to 1.43 m/s. Experiments show that pressure drop for R410A and R407C were 17.8∼20.2% and 5∼6.8% lower than those of R22 respectively for the degree of subcooling of 5$^{\circ}C$. For the mass fluxes of 200∼250 kg/$m^2$s, the deviation between the experimental and predicted values for the pressure drop was less than $\pm$20% for R22, R407C and R410A.

Modeling of Fin-Tube Heat Exchanger (핀-관 열교환기의 모델링)

  • 박희용;이관수;박동규
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.13 no.5
    • /
    • pp.952-961
    • /
    • 1989
  • The purpose of this study is to investigate the behavior of operational and design factors on the performance characteristics of a horizontal fin-tube heat exchanger under phase change conditions for refrigerant. The flow and heat transfer in the heat exchanger are simulated numerically taking into account the variations of heat transfer coefficients, thermodynamic and flow properties of refrigerant, and the axial heat conduction in the tube wall. As the results of this study, it was found that the annular flow model was more reasonable physically than the homogeneous one for the two phase flow of refrigerant and axial heat conduction of tube wall did not have a great influence on the analysis. The effects of refrigerant pressure, mass flow rate of air, diameter of tube and the number of fins per unit length of tube were also discussed.