Experimental study for the pressure drop of R-22 and R-4O7C during the condensation in the micro-fin tubes  

Roh, Geon-Sang (동명대학교 환경설비공학과)
Abstract
Experiments were conducted for the investigation of pressure drop inside horizontal micro-fin tubes during the condensation of R-22 and ternary refrigerant. R-407C(HFC-32/125/134a 23/25/62 wt%) as a substitute of R-22. The condenser is a double-tube and counterflow type heat exchanger which is consisted with micro-fin tubes having 60 fins with a length of 4000mm, outer diameter of 9.53mm and fin height of 0.2mm. The mass velocity varied from 102.1 to $301.0kg/(m^2{\cdot}s)$ and inlet quality was fixed as 1.0. From the experimental results. the pressure drop for R-407C was considerably higher than that for R-22. The value of PF(penalty factor) for both of refrigerants was not bigger than the ratio of micro-fin tube area to smooth tube area. Based on the experimental data. correlation was Proposed for the prediction of frictional pressure drop during the condensation of R-22 and R-407C inside horizontal micro-fin tubes.
Keywords
Pressure drop; R-407C; Micro-fin tube; Penalty Factor; Condensation;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Sami, S. M., Schnotale, J. and Smale, J. G., 1992, 'Prediction of the Heat Transfer Characteristics of R-22/ R-152a/R-114 and R-22/R-152a/R-124', ASHRAE Trans., Vol. 98, Part. 2, p. 51-58
2 虫至子穀, 戶田一美, 奧山和之, 鳥越邦和, 1995, 非共沸混合冷媒HFC-32/125/134a の傳熱促 進に關する硏究', 第29回 空氣調和.冷凍聯合 講演會講演論文集, pp. 69 - 72
3 McLinden, M. O., Klein, S. A., Lemmon, E. W., Peskin, A. P., 1998, NIST Thermodynamic Properties and Refrigerant Mixtures Database (REFPROP), Version 6.01, National Institute of Standards and Technology, Gaithersburg, MD, U.S.A
4 Kaushik, N., and Azer, N. Z., 1990, 'A General Pressure Drop Correlation for Condensation inside Internally Finned Tubes', ASHRAE Trans., Vol. 96, Part. 2, pp. 242 - 248
5 Sur, B., and Azer, N. Z., 1991, 'An Analytical Pressure Drop Prediction Model for Condensation inside Longitudinally Finned Tubes', ASHRAE Trans., Vol. 97, Part. 2, pp. 54-61
6 Fauske, H. K., 1961, 'Critical Two-Phase Steam Water Flows', Proc. Heat Transfer & Fluid Mech
7 Zivi, S. M., 1964, 'Estimation of Steady-State Steam Void Fraction by Means of the Principles of Minimum Entropy Production', J. of Heat Transfer, Vol. 86, pp. 247-252   DOI
8 藤井哲, 本田博司, 長田孝志, 藤井不夫, 野律 滋, 1976, '冷媒R-11の水平管內凝縮 (第1報, 流動樣式ぉよひ壓力降下)', 日本機械學會論文集(B編), 第 42 卷, 第 363 號, pp. 3541-3548
9 本田博司, 野律滋, 松岡洋一, 靑山享, 中田春 男, 1988, '傳熱促進管を內管とする水平二重 管環狀部たぉげる冷媒R-11とR-113の凝縮た 關する硏究', 日本冷凍協會論文集, 第 5 卷, 第 2 號, pp. 113-123
10 Koyama, S., Miyara, A., Takamatsu, H. and Fujii, T., 1990, 'Condensation Heat Transfer of Binary Refrigerant Mixtures of R22 and R114 inside a Horizontal Tube with Internal Sprial Grooves', Intl. J. Ref., Vol. 13, No. 7, pp. 256-263   DOI   ScienceOn
11 Geon-Sang, Roh, Chang-Hyo, Son, Hoo-Kyu, Oh, 2007, 'Evaporation Heat Transfer Characteristics of Hydrocarbon Refrigerants R-290 and R-600a in the Horizontal Tubes', The Korea Society of Marine Engineering, Vol. 31, No. 1, pp. 74-83   과학기술학회마을   DOI   ScienceOn
12 Schlager, L. M., Pate, M. B. and Bergles, A. E., 1988, 'Evaporation and Condensation of Refrigerant-Oil Mixtures in a Smooth Tube and a Micro-fin Tube', ASHRAE Trans., Vol. 94, Part. 1, pp. 149-166
13 노건상, 오후규, 권옥배, 1996, '냉매 R-22, R-407c의 수평평활관내 압력강하에 관한 연구', 한국박용기관학회지, Vol. 20, No. 4, pp. 392-402
14 Turner, J. M., and Wallis, G. B., 1965, 'The Separate-Cylinders Model of Two-Phase Flow', Report No. NYO-3114-6, Thayer's School of Engineering
15 Kaushik, N., and Azer, N. Z., 1990, 'A General Pressure Drop Correlation for Condensation inside Internally Finned Tubes', ASHRAE Trans., Vol. 96, Part. 2, pp. 242-248
16 Soliman, M., Schuster, J. R., and Berenson, P. J., 1968, 'A General Heat Transfer Correlation for Annular Flow Condensation', J. Heat Transfer, Vol. 90, pp. 267-276   DOI
17 Sami, S. M. and Schnotale, J., 1991, 'Forced Convection Condensation of Nonazeotropic Refrigerant Mixtures inside Enhanced Surface Tubing', Applied Scientific Research
18 Blaise, J. C., Dutto, T., and Ambrosino, J. L., 1989, 'First Industrial Application of Non-Azeotropic Mixture', Intl. J. Ref., Vol. 12, No. 9, pp. 255-258   DOI   ScienceOn