• Title/Summary/Keyword: FACTS (Flexible AC Transmission System)

Search Result 90, Processing Time 0.039 seconds

Study of Optimal Location and Compensation Rate of Thyristor-Controlled Series Capacitor Considering Multi-objective Function

  • Shin, Hee-Sang;Cho, Sung-Min;Kim, Jin-Su;Kim, Jae-Chul
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.3
    • /
    • pp.428-435
    • /
    • 2013
  • Flexible AC Transmission System (FACTS) application study on enhancing the flexibility of AC power system has continued to make progress. A thyristor-controlled series capacitor (TCSC) is a useful FACTS device that can control the power flow by adjusting line impedances and minimize the loss of power flow and voltage drop in a transmission system by adjusting line impedances. Reduced power flow loss leads to increased loadability, low system loss, and improved stability of the power system. This study proposes the optimal location and compensation rate method for TCSCs, by considering both the power system loss and voltage drop of transmission systems. The proposed method applies a multi-objective function consisting of a minimizing function for power flow loss and voltage drop. The effectiveness of the proposed method is demonstrated using IEEE 14- and a 30-bus system.

The Enhancement of Power System Security Using flexible AC Transmission Systems (FACTS) (FACTS 기기를 이용한 전력시스템의 안전도 향상)

  • 송성환;임정욱;문승일
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.3
    • /
    • pp.165-172
    • /
    • 2003
  • This paper presents an operation scheme to enhance the power system security by applying FACTS on Power systems. Three main generic types of FACTS devices are suggested an illustrated. Flow congestions over lines have been solved by controlling active power of series-compensated FACTS devices and low voltages at buses have been solved by controlling reactive power of shunt-compensated FACTS devices. Especially, Especially, UPFC has been applied in both line congestion and low voltages. Two kinds of indices which indicate the power system security level related to line flow and bus voltage are utilized in this paper. They have been minimized to enhance the power system security level through the iterative method and the sensitivity vector of security index is derived to determine the direction to minimum. The proposed algorithm has been tested on the IEEE 57-bus system with FACTS devices in a normal condition and a line-faulted contingency.

Analysis of the Distribution STATCOM Operating Results for Improving Distribution System Power Quality (전력품질 향상을 위한 배전용 STATCOM 운전결과 분석)

  • 오관일;전영수;박상태;추진부
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.5 no.4
    • /
    • pp.377-385
    • /
    • 2000
  • This paper presents the test and operation results of the domestic demonstration of the reactive power compensation device called STATCOM (STATic COMpensator). The object of the paper is to describe the reliability of the unit based on the extensive operation databases. The custom power is similar in nature to the concept of FACTS(Flexibel AC Transmission System). By controlling reactive power, the technology offers utilities the opportunity for increased efficiency and their capabilities will permit transmission planners make the best use of their existing transmission resources. STATCOM is a custom power device in a way and can be used in a similar way for the dynamic compensation of power transmission systems, providing reactive power compensation, voltage regulation and mitigation of voltage flicker. It is shown that the STATCOM has clear advantages in areas such as; providing reactive power compensation and improving power factor.

  • PDF

Setting Considerations of Distance Relay for Transmission Line with STATCOM

  • Zhang, Wen-Hao;Lee, Seung-Jae;Choi, Myeon-Song
    • Journal of Electrical Engineering and Technology
    • /
    • v.5 no.4
    • /
    • pp.522-529
    • /
    • 2010
  • Distance relay plays an important role in the protection of transmission lines. The application of flexible AC transmission systems (FACTS) devices, such as the static synchronous compensator (STATCOM), could affect the performance of the distance relay because of compensation effect. This paper analyzes the application of distance relay on the protection of a transmission line containing STATCOM. New setting principles for different protection zones are proposed based on this analysis. A typical 500 kV transmission system employing STATCOM is modeled using Matlab/Simulink. The impact of STATCOM on distance protection scheme is studied for different fault types, fault locations, and system configurations. Based on simulation results, the performance of distance relay is evaluated. The setting principle can be verified for the transmission line with STATCOM.

The Comparision of Four Transmission methods to enhance Transmission Capability (전력수송능력향상을 위한 4가지 송전방식의 비교)

  • Lee, Geun-Joon;Chang, Byung-Hoon;Kim, Yeng-Han;Bak, Yeng-Ki
    • Proceedings of the KIEE Conference
    • /
    • 1996.07b
    • /
    • pp.646-651
    • /
    • 1996
  • This paper presents the study results of four transmission methods to enchance transmission capability. The four transmission methods studied were FACTS, HVDC, High Phase Order and new conductor material method. The study was Performed based on mid and long term KEPCO system in 2000 and 2006 year. Among them FACTS(Flexible AC Transmission System) is an exciting new field which holds great promise for improved utilization of AC transmission systems.

  • PDF

Improvement of Line Protection Methods by Dynamic Analysis on a FACTS-compensated transmission line (FACTS 보상 송전선의 동적 해석을 통한 송전선 보호 방안 개선)

  • Lim Jung-Uk;Runolfsson Thodur
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.54 no.12
    • /
    • pp.573-579
    • /
    • 2005
  • Dynamic analysis of a transmission line which is compensated by a FACTS device such as STATCOM, SSSC and UPFC is carried out in this paper and the impacts on conventional line protection methods such as the DCPM (Differential Current Protection Method) and the DPM (Distance Protection Method) are reviewed. A refined DCRM is proposed to detect faults properly regardless of the FACTS operation. The proposed method is applied to a FACTS-compensated line with a variety of faults and is verified by simulation results. An adaptive DPM on a FACTS-compensated line was proposed previously in the literature. In order to emphasize the necessity of the modified DPM, the conventional DPM is applied to a FACTS-compensated system. Significant factors such as fault types, fault locations, and fault resistances as well as FACTS device types are considered for relaying setting.

Design of Nonlinear FACTS Controller with intelligent Algorithm (FACTS 비선형 지능 제어기 설계)

  • Park, Seong-Wook;Seo, Bo-Hyeok
    • Proceedings of the KIEE Conference
    • /
    • 2000.11a
    • /
    • pp.33-35
    • /
    • 2000
  • We propose a intelligent controller for FACTS(Flexible AC Transmission System) device to stabilize a power system. In order to identify the nonlinear characteristics of the power system and to estimate a control signal, an artificial neural network is utilized. The control signal which is provided for FACTS device installed in the network is produced. The proposed controller is applied to Unified Power Flow Controller(UPFC) to verified the effectiveness of the proposed control system. The results show that the proposed nonlinear FACTS controller is able to enhance the transient stability of three machine nine bus power system.

  • PDF

Available Transfer Capability Enhancement with FACTS Devices in the Deregulated Electricity Market

  • Manikandan, B.V.;Raja, S. Charles;Venkatesh, P.
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.1
    • /
    • pp.14-24
    • /
    • 2011
  • In order to facilitate the electricity market operation and trade in the restructured environment, ample transmission capability should be provided to satisfy the demand of increasing power transactions. The conflict of this requirement and the restrictions on the transmission expansion in the restructured electricity market has motivated the development of methodologies to enhance the available transfer capability (ATC) of existing transmission grids. The insertion of flexible AC transmission System (FACTS) devices in electrical systems seems to be a promising strategy to enhance single area ATC and multi-area ATC. In this paper, the viability and technical merits of boosting single area ATC and multi-area ATC using Thyristor controlled series compensator (TCSC), static VAR compensator (SVC) and unified power flow controller (UPFC) in single device and multi-type three similar and different device combinations are analyzed. Particle swarm optimization (PSO) algorithm is employed to obtain the optimal settings of FACTS devices. The installation cost is also calculated. The study has been carried out on IEEE 30 bus and IEEE 118 bus systems for the selected bilateral, multilateral and area wise transactions.

Fitness Sharing Particle Swarm Optimization Approach to FACTS Installation for Transmission System Loadability Enhancement

  • Chang, Ya-Chin
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.1
    • /
    • pp.31-39
    • /
    • 2013
  • Proper installation of Flexible AC Transmission Systems (FACTS) devices in existing transmission networks can enable power systems to accommodate more power transfer with less network expansion cost. The problem to maximize transmission system loadability by determining optimal locations and settings for installations of two types of FACTS devices, namely static var compensator (SVC) and thyristor controlled series compensator (TCSC), is formulated as a mixed discrete-continuous nonlinear optimization problem (MDCP). For solving the MDCP, in the paper, the proposed method with fitness sharing technique involved in the updating process of the particle swarm optimization (PSO) algorithm, can diversify the particles over the search regions as much as possible, making it possible to achieve the optimal solution with a big probability. The modified IEEE-14 bus network and a practical power system are used to validate the proposed method.

1MVA Distribution-STATCON for Flexible AC Transmission System (FACTS) (유연송전 시스템을 위한 1MVA 배전용 동기 조상기)

  • Moon, Gun-Woo;Yoon, Suk-Ho;Park, Yong-Bae;Yoon, Jong-Soo;Choo, Jin-Boo
    • Proceedings of the KIEE Conference
    • /
    • 1997.07f
    • /
    • pp.1933-1935
    • /
    • 1997
  • The availability of high power IGBT has led to development of controllable reactive power and harmonics compensation source for use in power transmission system. The paper describes the fundmental operating principles and several application examples. The control technique of reactive power and harmonics compensation for Distribution STATCON is presented, and the computer simulation results are shown to show the effectiveness of tile proposed control technique.

  • PDF