Development of Remote Supervision System for Guam Lamps by Way of Leakage Current(Igr) Detection Method (보안등 전거설비의 Igr 누설전류 검출 및 원격감시장치 개발)

  • Choi, Myeong-Il;Kim, Young-Seok;Kim, Chong-Min;Bang, Sun-Bae
    • Journal of the Korean Society of Safety
    • /
    • v.25 no.6
    • /
    • pp.75-80
    • /
    • 2010
  • The present study presented the implementation of a remote control/supervision system for guard lamps used in public illumination with little endeavor by far for safe management, which makes possible to supervise the state and to control the functions remotely including electric safety elements. Especially, the developed system adopts the measurement algorithm for detecting resistive leakage current(Igr) flowing based on the phase difference checkable for sensing at a monitor, being allowable for monitoring at MMI and transmitter for data transmittance. To verify reliability about the algorithm to accurately detect Igr leakage current, the laboratory-based functional test was performed.

Practical Applications of Multi-Agent Transformer Condition Monitoring (다수 변압기의 온라인 모니터링을 위한 실제 적용)

  • Yun, Ju-Ho;Choi, Yong-Sung;Hwang, Jong-Sun;Lee, Kyung-Sup
    • Proceedings of the KIEE Conference
    • /
    • 2008.04b
    • /
    • pp.96-99
    • /
    • 2008
  • On-line condition monitoring is a useful tool for maintaining and extending the longevity of power transformers. An intelligent diagnostic system is desirable for operational safety and reliability. Bringing these concepts together results in a powerful support tool for engineers, reducing the volume of data to deal with, and making the data more meaningful. This paper describes how a multi-agent system for diagnosing the cause of transformer partial discharge activity was coupled with a method of UHF partial discharge monitoring, creating an on-line condition monitoring system. The challenges presented by the on-site environment are discussed, along with the implications for the complete system.

  • PDF

Trends in standardization of IoT based electrical safety technology (사물인터넷 기반 전기안전 기술 및 표준화 동향)

  • An, Y.Y.;Kim, S.H.;Jeong, S.J.;Kang, H.J.
    • Electronics and Telecommunications Trends
    • /
    • v.35 no.1
    • /
    • pp.49-59
    • /
    • 2020
  • This paper describes an IoT-based electrical safety management system for managing the electrical power distribution systems in factories or buildings and for managing private electrical devices in apartment complex. The IoT-based electrical safety management system collects IoT data from the electrical facilities or devices to provide various electrical safety services. In some cases, it uses an IoT adaptor to collect data from legacy facilities. By monitoring and analyzing the IoT data, it is possible to provide protection from and prevent electrical hazards. In addition, an IoT-based electrical safety management system can benefit from using the IoT identification system and standardized data model of the electrical facilities and devices. An IoT identification system is used to increase manageability of large-scale electrical facilities which consists of numerous IoT devices. A standardized data model is used to support interoperability. This paper also explores some international and Korean standards related to IoT-based electrical safety management.

Web-based Real Time Failure Diagnosis System Development for Induction Motor Bearing (유도전동기 베어링의 원거리 실시간 결함진단시스템 개발)

  • Kwon, Oh-Heon;Lee, Seung-Hyun
    • Journal of the Korean Society of Safety
    • /
    • v.20 no.3 s.71
    • /
    • pp.1-8
    • /
    • 2005
  • The industrial induction motor is widely used in the rotating electrical machine for the transmission of power. It is very reliable equipment, but it could lead to the loss of production and lift when failure occurs. Therefore, the failure data is acquired and analyzed by attaching an exclusive instrument to existing induction motor. However, these instruments could lead to side effects, increasing the production costs, because they are very expensive. The purpose of this study is the development of an induction motor bearing failure diagnosis system constructed using LabVIEW which can be supplied the kernelled function, process monitoring and current signature analysis. In addition, the availability and reasonability of the constructed system was examined for an induction motor with failure defects in outer raceway and ball bearing. From the results, it shows that failure diagnosis system constructed is useful for real-time monitoring with detection of bearing defects over the web.

On-Line Monitoring of Power Apparatus with Infrared Thermography (적외선 열화상을 이용한 수전설비 온라인 감시)

  • Lim, Young-Bae;Jeong, Seung-Cheon
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07a
    • /
    • pp.441-444
    • /
    • 2004
  • Each electrical apparatus radiates various infrared as the condition of surface and load current. Because heat distribution of the apparatus changes as the condition, it is able to analyze the condition of the apparatus by using the distribution. However, methods having been used to measure the heat distribution cannot compare normal condition with abnormal, and the apparatus has diagnosed by intuition. This paper deal with a program that is able to analyze changed temperature distribution. The program is to analyze temperatures on pixels in selected region of interest or position and is able momently and logically to analyze condition of the apparatus. The results are able to apply to a on-line monitoring system.

  • PDF

Development of High Reliability Monitoring and Control System for Platform Screen Door (승강장 스크린 도어(PSD)에 대한 고 신뢰성의 감시 및 제어 시스템 개발)

  • Kim, Jin-Sik;Shon, Jin-Geun
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.59 no.2
    • /
    • pp.158-162
    • /
    • 2010
  • PSD is automatically opened and closed when subway train arrive on the station. This system was designed to control electric automatic system. These doors will provide passenger safety, energy saving and a good environment in subway. The monitoring and control systems of PSD are configured so that they can be operated in automatic mode in connection with ATO through the composite control panel in the station control room. The objective of this paper is to obtain high reliability that is essential for monitoring and control systems of PSD. The power supply is based on protection circuit using DC power bridge from two UPS. Also, stable communication system consists of CAN communication line redundancy and RF cross protection algorithm. Monitoring state display results show the validity of the proposed high reliability monitoring and control systems of PSD.

A study on An Application for Ensuring Safety of Computer Based Automatic Train Control System (컴퓨터기반 자동열차제어장치의 안전성 확보에 관한 연구)

  • Lee jongwoo;SHIN jongwoo
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.54 no.6
    • /
    • pp.261-268
    • /
    • 2005
  • This paper propose the safety design of automatic train control system which is used for controlling and monitoring train speed not to excess a permitted speed. Safety activities are shown for the computerized system to achieve a required safety requirement. The safety activities are composed of system dynamic modelling to identify potential hazards contained in the target system, to analyze sub system faults to provoke the hazards. Risks analysis are carried out to estimate losses caused from the hazards to allocate safety requirement. We Proposed design solutions for sub system to meet safety requirement.

A Study on the Development of Value-Added Service Based on Remote Electrical Safety Inspection of Electrical Facilities for Private User (일반용 전기설비의 원격 전기안전점검 모델을 활용한 전기안전 부가서비스 제공 방안에 관한 연구)

  • Choi, Myeong-Il;Yoo, Jae-Geun;Jeon, Jeong-Chay;Jung, Yong-Uk
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.365-368
    • /
    • 2008
  • This paper introduce the model of remote monitoring system that combine information technology in electrical safety checks that has been done by professional staff. And for general use, electrical safety Value-Added Service using remote check data were presented. In the near future, If demand and interests of Value-Added Service will be increased, this will be a electrical safety Value-Added Service as an important role in the blind spot of country electricity disaster.

  • PDF

A Plan for Construction of the National Electrical Safety Grid to Prevent the Fires Caused by Electrical Faults (전기화재 예방을 위한 국가전기안전망 구축 방안)

  • Bae, Seok-Myeong;Jeon, Jeong-Chay;Park, Chan-Eom;Bae, Seok-Myeong;Ko, Won-Sig
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.10 no.9
    • /
    • pp.2267-2273
    • /
    • 2009
  • In this paper, in order to monitor and manage an electrical risk factor like as leakage current, load current, and arc-fault, a real time monitoring and management system being operated in the ubiquitous environment was developed, and a plan of construction of an electrical safety grid using the system was proposed. For confirmation of usefulness and reliability of the proposed safety system and grid, the developed intelligent panels were applied to 28 Korean traditional houses in Jeonjoo city, and the grid including the panels was operated. If the proposed National Electrical Safety Grid is completely constructed in the houses of general electrical users, the Grid will have an effect on that a main manager on electrical safety transfers from management system by general people to real-time management system by expert. As a result, the electrical fires caused by an over-load, an arc-fault, and an earth-fault will be prevented.

Development of Measurement System for Harmonic Analysis of Electric Equipment (전기설비의 고조파 분석을 위한 측정 시스템의 개발)

  • Yoo, Jae-Geun;Lee, Sang-Ik;Jeon, Jeong-Chay
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.259-261
    • /
    • 2002
  • Recently, according to the spread of semiconductor applied technology like motor speed control contrivance, power conversion installation and so on, harmonic ingredients occurred in switching operation flow into a distribution system and increase voltage distortion of distribution system and bring on obstacles like damage, lowering of capability, false operation and so on of various electrical installation. So, in order to consider a countermeasure to limit occurrence quantity of harmonic source, harmonic interception and others, precision measurement and analysis on voltage, current, power, power factor, the each ingredient of harmonic order, the percentage of total harmonic distortion and so forth are needed. In this paper monitoring system to measure and analyze power quality connected with power harmonics was developed and it's performance is verified by measuring and analyzing three-phase voltage and current of R, S, T in the three-phase and four-wire system using the developed measurement system.

  • PDF