• 제목/요약/키워드: EMTP MODELS

검색결과 65건 처리시간 0.025초

전압의 주파수 편의를 이용한 동기탈조 검출 알고리즘에 관한 연구 (A Study on the Out-of-Step Detection Algorithm using Frequency Deviation of the Voltage)

  • 소광훈;허정용;김철환
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제53권3호
    • /
    • pp.175-181
    • /
    • 2004
  • The protection against transient instability and consequent out-of-step condition is a major concern for the utility industry. Unstable system may cause serious damage to system elements such as generators and transmission lines. Therefore, out-of-step detection is essential to operate a system safely. The detection of out-of-step is generally based upon the rate of movement of the apparent impedance. However such relay monitors only the apparent impedance which may not be sufficient to correctly detect all forms of out-of-step and cannot cope with out-of-step for a more complex type of instability such as very fast power swing. This paper presents the out-of-step detection algorithm using voltage frequency deviation. The digital filters based on discrete Fourier transforms (DFT) to calculate the frequency of a sinusoid voltage are used, and the generator angle is estimated using the deviation of the calculated frequency component of the voltage. The proposed out-of-step algorithm is based on the assessment of a transient stability using equal area criterion. The proposed out-of-step algorithm is verified and tested by using EMTP MODELS.

혼합배전계통 선로구성요소 변화를 고려한 선로 서지해석 (Surge Analysis Considering Variation of Line Configuration Factor in Combined Distribution Systems with Power Cables)

  • 김병숙;이장근;한병성;이종범
    • 전기학회논문지
    • /
    • 제56권3호
    • /
    • pp.472-480
    • /
    • 2007
  • This paper analyzes overvoltage on testing line for various parameter effect examination. Model systems consist of overhead line and underground cable. The model considered actual characteristic data of distribution lines. and will be constructed at testing yard. The simulations were performed under various line configuration such as cable kinds, cable length, lightning wave, lightning wave time, transformer and branch circuits. The simulation models are established by EMTP/ATPDraw and Line Constants are calculated by ATP_LCC. When lightning surge strikes on conductor of overhead line, EMTP/ATPDraw calculates overvoltage in many cases. Simulation results will be compared with real testing results at testing yard. The compared results will be used to establish protection methods in actual underground distribution systems.

거리 계전기의 EMTP 모델링에 관한 연구 (A Study on Distance Relay Modeling Using EMTP)

  • 심재철;유창완;강유원;임화영
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 D
    • /
    • pp.997-999
    • /
    • 1997
  • This Paper presents a relay modeling technique to deal with the relay transient characteristics. Existing relay models are based on steady-state concepts. The ninth-order state space mathematical model of the Mho distance relay has been constructed. Computer modeling of a typical distance relay is done within the Transient Analysis of Control System(TACS) subsection of the ElectroMagnetic Transient Program(EMTP).

  • PDF

EMTP를 이용한 전자식 CT, PT의 시뮬레이션 특성 분석 (The Analysis for the Simulational Characteristics of the Electronic CT & PT using EMTP)

  • 신중은;김재철;송승엽;권영목;김언석;추동욱
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.310-312
    • /
    • 2004
  • Generally, instrument transformer of the core type have been used for measuring current. Because instrument transformer has defects, electronic instrument was appeasred. This paper is introduced a basic concept and thoery of electronic instrument and described the the simulation of core type CT and no saturation CT. The evaluation of CT models implemented using EMTP(Electro Magnetic Transients Program) was carried out. The result of comparison both core type CT and no saturation CT are presented.

  • PDF

분산전원을 고려한 적응적 재폐로 기법 (An Adaptive Reclosing Technique Considering the Distributed Generation)

  • 서훈철;김철환;여상민
    • 전기학회논문지
    • /
    • 제56권2호
    • /
    • pp.227-232
    • /
    • 2007
  • The autoreclosing is applied to power system for maintaining system stability and continuity of supply. Developments on distributed generation(DG) grows significantly by environmental issues and economical issues. If the DG is connected to distribution system, the DG influences the technical aspects such as power quality, protection and stability. It causes the challenges to protection, especially to reclosing. In order to achieve reliability and safety of the distribution system, the rules and guidelines suggest that the DG units should be rapidly disconnected from the network before the reclosing. If the DG is disconnected whenever the fault occurs, it cannot be utilized effectively. This paper presents the adaptive reclosing algorithm considering the DG. The algorithm consists of angle oscillation's judgment, EEEAC(Emergency Expanded Equal-Area Criterion), calculation of optimal reclosing time and re-connection algorithm. The simulation is implemented for the DG technology by using EMTP MODELS. The simulation results show that the transient stability is maintained and the DG is protected against disturbance.

시변 저항을 이용한 배전 계통의 고저항 사고 모델링 (Modeling of a High Impedance Fault in a Distribution System Using Time-Varying Resistance)

  • 남순열;강용철;박종근
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 추계학술대회 논문집 학회본부 A
    • /
    • pp.113-115
    • /
    • 1999
  • A more reliable relaying algorithm for detecting a high impedance fault (HIF) requires fault currents at the relaying point containing information of various HIF characteristics as well as load conditions. As HIF characteristics, there are buildup, shoulder, nonlinearity and asymmetry. This paper presents a modeling method of a HIF in a distribution system using EMTP. In order to represent HIF characteristics, the proposed method uses two time-varying resistances. The first TVR models nonlinearity and asymmetry using voltage as the input. The second TVR models buildup and shoulder using time information as the input. The proposed method is implemented in EMTP.

  • PDF

Development of Fault Detector for Series Arc Fault in Low Voltage DC Distribution System using Wavelet Singular Value Decomposition and State Diagram

  • Oh, Yun-Sik;Han, Joon;Gwon, Gi-Hyeon;Kim, Doo-Ung;Kim, Chul-Hwan
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권3호
    • /
    • pp.766-776
    • /
    • 2015
  • It is well known that series arc faults in Low Voltage DC (LVDC) distribution system occur at unintended points of discontinuity within an electrical circuit. These faults can make circuit breakers not respond timely due to low fault current. It, therefore, is needed to detect the series fault for protecting circuits from electrical fires. This paper proposes a novel scheme to detect the series arc fault using Wavelet Singular Value Decomposition (WSVD) and state diagram. In this paper, the fault detector developed is designed by using three criterion factors based on the RMS value of Singular value of Approximation (SA), Sum of the absolute value of Detail (SD), and state diagram. LVDC distribution system including AC/DC and DC/DC converter is modeled to verify the proposed scheme using ElectroMagnetic Transient Program (EMTP) software. EMTP/MODELS is also utilized to implement the series arc model and WSVD. Simulation results according to various conditions clearly show the effectiveness of the proposed scheme.

비대칭 고장전류에 따른 초전도 한류기 동작 분석 (An Analysis of Superconducting Fault Current Limiter Operation According to Asymmetry Fault Current)

  • 이상봉;김철환;김규호;김재철;현옥배
    • 전기학회논문지
    • /
    • 제58권3호
    • /
    • pp.450-454
    • /
    • 2009
  • This paper analyzes a asymmetry current with SFCL (Superconducting Fault Current Limiter) operation during transient period, when a fault occurs in power systems. The principle of asymmetry current nature is reviewed and asymmetry components reduction with SFCL operation is explained. To verify the performance of SFCL, a EMTP/ATPDraw model of SFCLs using MODELS language developed and simulated. Throughout the simulation, results presents the main factors for reducing the asymmetry component of fault current are not a quenching time, but a limiting resistance of SFCL and fault initiated angle.

GPS를 이용한 동기페이저측정장치의 EMTP모델 구현 (Implementation of Synchronized Phasor Measurement Unit Using GPS)

  • 조기선;허문준;채명석;신중린
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 C
    • /
    • pp.1262-1266
    • /
    • 1999
  • More precise operation and control is required to ensure the stability and security of modern large power systems that is a complicated and widely dispersed structure. To ensure the precise operation and control of modern power system, most of all, precise monitoring and measurement of the various state values of power system is required. This paper discusses phasor measurement unit using synchronization signals from the GPS satellite system- Synchronized Phasor Measurement Unit. Considering the power system operation state, the transmitting data format over modems is defined. To provide all available information, PMU process the measurements to generate three phase symmetrical component. This paper proposes the transmitted data format and implements the PMU model using EMTP/Models. The validity of proposed model is confirmed through several contingency on the simple power system.

  • PDF

An Adaptive Autoreclosure Scheme with Reference to Transient Stability for Transmission Lines

  • Heo, Jeong-Yong;Oh, Yun-Sik;Seo, Hun-Chul;Kim, Chul-Hwan
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권3호
    • /
    • pp.795-803
    • /
    • 2015
  • Autoreclosure provides a means of improving power transmitting ability and system stability. Conventional reclosure adopts the fixed dead time interval strategy, where the reclosure is activated after a time delay to restore the system to normal as quickly as possible without regard to the system conditions. However, these simple techniques cannot provide optimal operating performance. This paper presents an adaptive autoreclosure algorithm including variable dead time, optimal reclosure, phase-by-phase reclosure and emergency extended equal-area criterion (EEEAC) algorithm in order to improve system stability. The reclosure algorithm performs the operations that are attuned to the power system conditions. The proposed adaptive reclosure algorithm is verified and tested using ATP/EMTP MODELS, and the simulation results show that the system oscillations are reduced and the transient stability is enhanced by employing the proposed adaptive reclosure algorithm.