• 제목/요약/키워드: EMTDC model

검색결과 235건 처리시간 0.024초

수력 발전기 제어시스템의 계자상실 모델링과 시뮬레이션 (Modeling and Simulation of Loss of Excitation of Hydro Generator Control System)

  • 박철원
    • 전기학회논문지P
    • /
    • 제63권2호
    • /
    • pp.74-80
    • /
    • 2014
  • Generator protection device has to detects an internal fault conditions in generator and abnormal operating conditions must be due to the hazards. Loss of excitation may cause generator itself failure as well as serious operating problem in power system, and then requires an appropriate response of generator protection device. Details modeling of generator control system and analysis of transient states in generator are important for optimal operation in power plants. In addition, the fault simulation data are also used for testing the characteristics of IED. In this paper, the hydro generator control system using PSCAD/EMTDC, visual simulation for power systems, was modeled. The generator control system which is composed of generator, turbine, exciter, governor was implemented. The parameters of generator control system model were obtained from field power plant. Loss of excitation simulations were performed while varying the fixed load. Several signals analysis were also performed so as to analyze transients phenomena.

발전기 계자보호를 위한 계자상실 알고리즘에 관한 연구 (A Study on Loss of Excitation Algorithm for Generator Field Protection)

  • 박유영;박철원
    • 전기학회논문지P
    • /
    • 제63권4호
    • /
    • pp.368-372
    • /
    • 2014
  • The most widely used scheme for detecting loss of excitation on generator is used to sense apparent impedance from generator terminals. This paper presents loss of excitation algorithm using DFT filter based negative offset mho elements for generator field protection. It's algorithm includes two negative mho characteristics looking in the generator. The generator control system was modeled by PSCAD/EMTDC software, and then the proposed algorithm was tested by the collecting relaying signals from selected the generator model. From simulation results, the loss of excitation algorithm can be used to field protection for generator.

여자시스템의 파라미터가 터빈-발전기의 비틀림 스트레스에 미치는 영향 분석 (A Study on Effect of Exciter Parameters for the Torsional Stress of Turbine-Generator)

  • 김찬기
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제52권8호
    • /
    • pp.420-426
    • /
    • 2003
  • This paper deals with the effect of exciter parameters on the torsional stress of turbine-generator. The excitation system effects on the AC network stability and the turbine-generator stress. However. it, until now, have not reported that any parameter among exciter parameters is related to the stability and the stress. In order to verify those CIGRE HVDC model was used. Since the AC network with HVDC has the voltage stability problem due to big capacitor, the worst condition to analyze the stress can considered. The EMTDC program is used for the simulation studies.

다중브리지로 구성된 UPQC(Unified Power Quality Conditioner)의 동적 성능분석 (Dynamic Performance Analysis of Unified Power Quality Conditioner with Cascaded H-Bridges)

  • 한병문;소용철;김현우
    • 전기학회논문지P
    • /
    • 제55권2호
    • /
    • pp.94-102
    • /
    • 2006
  • This paper describes experimental analysis of UPQC, which is composed of cascaded H-bridges and single-phase multi-winding transformers. The operational characteristic was analyzed through experimental works with a scaled model, and simulations with PSCAD/EMTDC. The UPQC proposed in this paper can be directly connected to the distribution line without series injection transformers. It has flexibility to expand the operation voltage by increasing the number of H-bridge modules. The analysis results can be utilized to design the actual UPQC system applicable for the actual distribution system.

고속전철 차량에서 발생한 고조파 파급영향과 그 대책에 관한 연구 (A study on propagation effect and countermeasure of the harmonics generated in high speed traction)

  • 박수만;김재철;강창원
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.59-61
    • /
    • 2003
  • This paper demonstrates an analysis of harmonics at the high speed railway substation and proved on this countermeasure using the PSCAD/EMTDC simulation tool. First, high speed railway feeding system is composed using PSCAD/EMTDC electrical railway feeding system model in advance. Second, This paper applications line capacitance values as feeder-trolley, trolley-rail and feeder-rail to analysis harmonics more accuracy in advance did not application. This capacitance values calculate using the EMTP(Electro Magnetic Transient Program). Third, the tractions are arranged in the section that substation supplies power, and this paper take the simulation each case(fractions composition amount) to see harmonic propagation from traction to substation. As a result, generated harmonics at traction can confirmed that harmonics did not reduce at utility source. This harmonics have an influence on bulk power system. Finally, this paper introduces the methods of harmonics effect minimum. This paper proved harmonics reduce effect through the passive filters application.

  • PDF

단상재폐로 송전선로에 대한 2차 아크 모델링 (Secondary Arc Modeling for Single-Pole Switching on Transmission Lines)

  • 박병철;이욱화;신중린
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 추계학술대회 논문집 학회본부
    • /
    • pp.157-159
    • /
    • 1996
  • The secondary arcing phenomenon can be hardly modeled for computer simulation due to its particularly nonlinear characteristics. This paper describes a new computer modeling technique for the secondary arc which can be implemented with the EMTDC. The computer model proposed is based on realistic are conduction behaviors through both FIT and variable resistor modules which is supported in the EMTDC. Simulation results using the proposed technique are compared with some previous studies.

  • PDF

축약모델을 이용한 HVDC시스템의 안정도 평가 (A Stability Estimation Method of HVDC System Using Reduced Model)

  • 김찬기;임성주;추진부
    • 전력전자학회논문지
    • /
    • 제10권1호
    • /
    • pp.1-12
    • /
    • 2005
  • 본 논문은 HVDC 시스템의 제어기나 제어형태에 따른 HVDC시스템의 안정도를 다루고 있다. HVDC시스템은 제어기 관점에서 PI 또는 PD 그리고 PID 제어기를 가지고 있으며, 각각의 경우는 시스템의 응답이나 안정도를 고려하여 설계되고 있다. 그리고 HVDC시스템은 다른 시스템과 다르게 전압제어기, 전류 제어기 그리고 Alpha 제어기와 같은 다-제어모드로 구성되어 있기 때문에 각각의 경우에 따른 안정도를 구해야한다. HVDC시스템의 안정도를 고려한 제어 게인 튜닝은 HVDC시스템의 제어기를 축약하여 AC계통을 고려한 형태로 구해야하며, PSS/E급에서 해석될 수 있게 하였다. 또한 본 논문에서 구한 제어 게인은 3상 순시해석이 가능한 PSCAD/EMTDC급에서도 안정도를 확인하였다.

계통 연계형 태양광 발전 시스템의 실계통 적용을 위한 시뮬레이션 모델에 관한 연구 (A Study on the Simulation Model of PV Generation System for its Application to Real Power System)

  • 이계병;손광명;전인수
    • 조명전기설비학회논문지
    • /
    • 제22권6호
    • /
    • pp.70-78
    • /
    • 2008
  • 본 논문에서는 태양광 발전시스템을 전력회사의 실배전 계통에 적용하기 위한 시뮬레이션 모델링을 제시한다. 태양광 발전시스템이 실배전 계통에 미치는 영향을 해석하기 위하여, 태양광 발전시스템과 이를 실배전 계통에 적용한 시뮬레이션 모델을 PSCAD/EMTDC를 이용하여 모델링하였다. 태양광 발전 시스템의 적용 후 변전소로부터의 전력공급을 감소시킴으로써 부하 말단전압이 개선됨을 보였다. 또한 부하모선의 전압을 보상함으로써 부하 측의 전력품질이 개선됨을 보였다.

선형 보간법을 이용한 CDC4모델의 파라미터 산정 (Parameter Estimation of CDC4 Model Using Linear Interpolation)

  • 최장흠
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.386-387
    • /
    • 2011
  • HVDC 프로젝트마다 제어기가 달라지게 된다. 따라서 HVDC 설비를 위한 전용의 해석 모델이 존재하지 않는다. 설비의 동특성을 모의하기 위해 모델 라이브러리가 없는 상황이 도래하면, 범용 모델에 적합하도록 데이터를 수정하는 방법과 UDM(User Define Model)을 개발하는 방법이 있다. UDM을 개발하는 것이 바람직하지만, 개발기간이 길고 UDM에 대한 검증의 필요성 때문에 범용 모델에 맞도록 데이터를 수정해야 할 필요가 있다. 이에 본 논문에 PSS/E 결과 데이터 또는 EMTDC 결과 데이터를 이용하여 CDC4 모델의 파라미터를 산정하는 방안을 제시하였다.

  • PDF

다중펄스 컨버터와 PWM 컨버터로 구성된 Back-to-Back 컨버터의 계통연계 성능 분석 (Performance Analysis of Grid Connected Back-to-Back Converter Composed of Multi-pulse Converter and PWM Converter)

  • 정종규;심명보;이혜연;한병문;한영성;정정주;장병훈
    • 전력전자학회논문지
    • /
    • 제15권6호
    • /
    • pp.451-459
    • /
    • 2010
  • 본 논문은 대규모 풍력단지를 교류 전력망에 연계하기 위한 3-레벨 PWM 컨버터와 3-레벨 24-펄스 컨버터로 구성된 하이브리드 Back-to-Back 컨버터의 성능을 비교한 결과에 대해 기술하고 있다. 또한 3-레벨 24-펄스 컨버터를 점호각만 제어하는 경우와 영 전압제어를 같이 수행하는 경우 각각이 제어와 고조파레벨에 미치는 영향을 비교 분석하였다. 구체적인 성능비교를 위해 먼저 PSCAD/EMTDC 소프트웨어를 사용하여 시뮬레이션을 실시하고 이를 바탕으로 2 kVA 용량의 하드웨어 축소모형을 제작하고 실험을 실시하였다. 시뮬레이션과 실험을 통해 영전압과 점호각을 동시에 조절하는 방식과 점호각만 제어하는 방식의 성능비교분석을 하였다.