• 제목/요약/키워드: Dynamic voltage stability

검색결과 169건 처리시간 0.026초

Seamless Mode Transfer of Utility Interactive Inverters Based on Indirect Current Control

  • Lim, Kyungbae;Song, Injong;Choi, Jaeho;Yoo, Hyeong-Jun;Kim, Hak-Man
    • Journal of Power Electronics
    • /
    • 제19권1호
    • /
    • pp.254-264
    • /
    • 2019
  • This paper proposes an indirect current control technique based on a proportional resonant (PR) approach for the seamless mode transfer of utility interactive inverters. Direct-current and voltage hybrid control methods have been used for inverter control under grid-connected and islanded modes. A large bandwidth can be selected due to the structure of single-loop control. However, this results in poor dynamic transients due to sudden changes of the controller during mode changes. Therefore, inverter control based on indirect current is proposed to improve the dynamic transients by consistently controlling the output voltage under all of the operation modes. A PR-based indirect current control topology is used in this study to maintain the load voltage quality under all of the modes. The design processes of the PR-based triple loop are analyzed in detail while considering the system stability and dynamic transients. The mode transfer techniques are described in detail for both sudden unintentional islanding and islanded mode voltage quality improvements. In addition, they are described using the proposed indirect control structure. The proposed method is verified by the PSiM simulations and laboratory-scale VDER-HILS experiments.

무효전력 보상여유를 고려한 SVC와 ULTC의 협조제어 (Coordinated Control of SVC and ULTC Considering Reactive Power Compensation Margin)

  • 문경섭;손광명;이태기;이송근;박종근
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제48권4호
    • /
    • pp.351-357
    • /
    • 1999
  • This paper proposes the coordinated control of SVC and UTLC at the distribution substation to get larger operating margin of SVC for the voltage stability control by reactive power compensation. In the conventional method, ULTC doesn't respond to the variation of source voltage, so SVC has the entire responsibility for it. It could cause the lack of operating margin of SVC in some condition. It, however, is important to secure an operating margin for the dynamic stability control in emergancy. This paper proposes the coordinated control method that SVC controls the supply voltage and ULTC respond to the SVC compensation valve based on the relation between SVC compensation and ULTC tap position. The numerical simulation verifies that the proposed system could increase the operating margin of SVC compared with the conventional system.

  • PDF

345[kV] 전력용 변압기 %임피던스 변화에 따른 계통영향 분석 (A Study on the Impact of the Impedance Change of 345[kV] Power Transformers on Overall System Performance)

  • 신정훈;남수철;이재걸;백승묵;송지영;김태균
    • 조명전기설비학회논문지
    • /
    • 제25권8호
    • /
    • pp.140-149
    • /
    • 2011
  • This paper deals with the impact analysis of the impedance change of 345/154[kV] power transformers on the KEPCO system's overall performance. Through the steady-state and dynamic analysis of power system, the maximum available impedance of power transformers were determined. Checking violation of short-circuit current ratings and transformer overload, parallel operation of power transformers, calculation of voltage variation ratio according to the impedance changes of power transformers are included in the steady-state analysis. In addition, transient and voltage stability analysis are also performed in the study. Available magnitudes to be able to change the impedance of the transformers in KEPCO system are finally determined in the paper.

Transient stability improvement using quasi-multi pulse BTB-STATCOM

  • Vural, Ahmel M.;Bayindi, Kamil C.
    • Advances in Energy Research
    • /
    • 제2권1호
    • /
    • pp.47-59
    • /
    • 2014
  • Back-to-back STATCOM configuration is an extension of STATCOM in which the reactive power at two-sides and the real power flow through the DC link can be controlled concurrently and independently. This flexible operation brings many advantages to the micro-grids, distributed generation based systems, and deregulated power systems. In this paper, the dynamic control characteristics of the back-to-back STATCOM is investigated by simulating the detailed converter-level model of the converters in PSCAD. Various case studies in a single-machine test system are studied to present that the real power control feature of the BtB-STATCOM, even with a simple controller design, can enhance the transient stability of the machine under different fault scenarios.

전력계통의 FACTS적용을 위한 직병렬 보상방안 연구 (The Study of Compensation Strategy for FACTS Application in Power System)

  • 이근준;장병훈;김영한
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 추계학술대회 논문집 학회본부
    • /
    • pp.112-116
    • /
    • 1996
  • This paper presents the study results of FACTS application plan for transmission capability Enhancement. Power transfer across the KEPCO system resulting from a concentration of load in the Kyung-In area are subject to thermal, voltage and stability constrains. In the analysis study of the KEPCO system in 2000 and 2006 year. voltage stability analysis. modal analysis and dynamic stability were simulated by the power system analysis tools(VSTAB, PSS/E).

  • PDF

과도 안정도를 고려한 정지형 여자기의 새로운 설계기술 (New Technology of Static Excitation System Considering Dynamic Stability)

  • 류홍우;김찬기
    • 전력전자학회논문지
    • /
    • 제1권1호
    • /
    • pp.47-55
    • /
    • 1996
  • A new generator excitation system using a boost-buck chopper as a kind of static exciters is proposed to overcome the lack of field forcing capability of the bus fed exciter under the input line fault condition. It increases or maintains the generator field current by boosting the field voltage in the case of the input AC line voltage drop during and immediately after a fault. The validity of the proposed excitation system is verified with the computer simulation. The generator stability according to the each difference exciter is tested using a commercial software package-CYME. The simulation results of the stability analysis on the generator with the proposed exciter is better than that of the bus fed exciter. This boost-buck chopper exciter can be simply implemented and controlled by the modern power electronics technology.

  • PDF

Pulse-width Adjustment Strategy for Improving the Dynamic Inductor Current Response Performance of a Novel Bidirectional DC-DC Boost Converter

  • Li, Mingyue;Yan, Peimin
    • Journal of Power Electronics
    • /
    • 제18권1호
    • /
    • pp.34-44
    • /
    • 2018
  • This paper presents a pulse-width adjustment (PWA) strategy for a novel bidirectional DC-DC boost converter to improve the performance of the dynamic inductor current response. This novel converter consists of three main components: a full-bridge converter (FBC), a high-frequency isolated transformer with large leakage inductance, and a three-level voltage-doubler rectifier (VDR). A number of scholars have analyzed the principles, such as the soft-switching performance and high-efficiency characteristic, of this converter based on pulse-width modulation plus phase-shift (PPS) control. It turns out that this converter is suitable for energy storage applications and exhibits good performance. However, the dynamic inductor current response processes of control variable adjustment is not analyzed in this converter. In fact, dc component may occur in the inductor current during its dynamic response process, which can influence the stability and reliability of the converter system. The dynamic responses under different operating modes of a conventional feedforward control are discussed in this paper. And a PWA strategy is proposed to enhance the dynamic inductor current response performance of the converter. This paper gives a detailed design and implementation of the PWA strategy. The proposed strategy is verified through a series of simulation and experimental results.

Investigation and Simulation Study on the Cascading Trip-off Fault of a Large Number of Wind Turbines in China on May 14, 2012

  • Qiao, Ying;Lu, Zong-Xiang;Lu, Ji;Ruan, Jia-Yang;Wu, Lin-lin
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권6호
    • /
    • pp.2240-2248
    • /
    • 2015
  • The integration of the large-scale wind power brings great challenge to the stability of the power grid. This paper investigates and studies the fault on May 14, 2012 of the large-scale cascading trip-off of wind turbines in North China. According to the characteristics of the voltage variation, the fault process is divided into three stages: the pre-event stage, the critical stage before cascading, and the cascading stage. The scenes in the fault are reproduced, using the full-size actual power system model. Simulation models of double-fed induction generators (DFIGs) and SVCs including protection settings and controller strategies are carefully chosen to find out the reason of voltage instability in each stage. Some voltage dynamic that have never been observed before in the faults of the same kind are analyzed in detail, and an equivalent voltage sensitive dynamic model of DFIG is proposed for the fast computation. The conclusions about the voltage dynamics are validated by the actual PMU observation evidence.

Advanced Small-Signal Model of Multi-Terminal Modular Multilevel Converters for Power Systems Based on Dynamic Phasors

  • Hu, Pan;Chen, Hongkun;Chen, Lei;Zhu, Xiaohang;Wang, Xuechun
    • Journal of Power Electronics
    • /
    • 제18권2호
    • /
    • pp.467-481
    • /
    • 2018
  • Modular multilevel converter (MMC)-based high-voltage direct current (HVDC) presents attractive technical advantages and contributes to enhanced system operation and reduced oscillation damping in dynamic MMC-HVDC systems. We propose an advanced small-signal multi-terminal MMC-HVDC based on dynamic phasors and state space for power system stability analysis to enhance computational accuracy and reduce simulation time. In accordance with active and passive network control strategies for multi-terminal MMC-HVDC, the matchable small-signal stability models containing high harmonics and dynamics of internal variables are conducted, and a related theoretical derivation is carried out. The proposed advanced small-signal model is then compared with electromagnetic-transient and traditional small-signal state-space models by adopting a typical multi-terminal MMC-HVDC network with offshore wind generation. Simulation indicates that the advanced small-signal model can successfully follow the electromechanical transient response with small errors and can predict the damped oscillations. The validity and applicability of the proposed model are effectively confirmed.

에너지함수법을 이용한 가용송전용량(ATC) 계산에 관한 연구 (A study on the ATC(Available Transfer Capabilily) calculation using an Energy Function Method)

  • 김재현;정성원;김양일
    • 조명전기설비학회논문지
    • /
    • 제22권2호
    • /
    • pp.94-100
    • /
    • 2008
  • 가용송전용량(ATC)은 계통내의 한 지역에서 다른 지역까지 실제 전력을 증가시키는 것이다. 지금까지 ATC 계산은 대부분 정상상태에서 실행가능성을 주로 고려하여 계산되어 왔다. 하지만 ATC 평가시 과도안정도로 제약된 ATC 계산은 매우 중요한 부분이다. ATC 평가시에는 제약조건으로 열적용량, 전압 및 과도안정도로 제약된 상정사고(n-1)시 안전도 평가가 요구된다. 본 논문은 자코비안 행렬의 고유치를 이용하여 상정사고 우선순위를 선정하였고, 에너지 함수법을 이용하여 선로의 열적용량, 전압안정도 및 과도안정도를 고려한 ATC를 계산하였다.