• Title/Summary/Keyword: Double Peak Current Limiting

Search Result 5, Processing Time 0.009 seconds

Double Peak Current Limiting Properties of Series Connection-Type SFCL with Two Magnetic Paths (두 개의 자속경로를 갖는 직렬연결형 초전도한류기의 이중 피크전류제한 특성)

  • Ko, Seok-Cheol;Han, Tae-Hee;Lim, Sung-Hun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.7
    • /
    • pp.62-68
    • /
    • 2014
  • We proposed a series connection-type superconducting fault current limiter(SFCL) using E-I core that can prevent the internal magnetic flux generation of cores during normal operation, and prevent the saturation of cores due to a sudden magnetic flux generation at the initial stage of fault occurrence while limiting the peak current. Through a short-circuit simulation experiment, we analyzed the operating status of the two superconducting elements and limiting characteristics according to the size of the fault current peak before and after the failure. Further, the double peak current limiting characteristics according to the winding directions as well as the current and the voltage of each coil were compared and analyzed.

Analysis on Current Limiting Characteristics of Transformer Type SFCL with Additionally Coupled Circuit

  • Lim, Seung-Taek;Ko, Seok-Cheol;Lim, Sung-Hun
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.2
    • /
    • pp.533-539
    • /
    • 2018
  • In this paper, the transformer type superconducting fault current limiter (SFCL) with additionally coupled circuit was suggested and its peak fault current limiting characteristics due to the fault condition to affect the fault current were analyzed through the fault current limiting tests. The suggested transformer type SFCL is basically identical to the previous transformer type SFCL except for the additional coupled circuit. The additional coupled circuit, which consists of the magnetically coupled winding to the primary and the secondary windings together with another superconducting element and is connected in parallel with the secondary winding of the transformer type SFCL, is contributed to the peak fault current limiting operation for the larger transient fault current directly after the fault occurrence. To confirm the fault current limiting operation of the suggested SFCL, the fault current limiting tests of the suggested SFCL were performed and its effective peak fault current limiting characteristics were analyzed through the analysis on the electrical equivalent circuit.

Arc Extinguishing of a Vacuum Interrupter for an HTS First Peak Current Limiter (반주기내 한류성능을 위한 진공차단기의 아크소호)

  • Kim, W.S.;Park, C.R.;Hyun, O.B.;Kim, H.R.;Yim, S.W.;Yu, S.D.;Yang, S.E.
    • Progress in Superconductivity
    • /
    • v.12 no.1
    • /
    • pp.23-26
    • /
    • 2010
  • A double line commutation (DLC) type SFCL with first peak limiting function has been proposed for ideal fault current limiting operation. Very fast switching (commutation) without any arc or high voltage problems for any kind of switching device is needed for the first peak current limiting. We've tried to find suitable conditions for a successful switching of a Vacuum Interrupter (VI) with HTS elements as a Peak Current limiting Resistance (PCR).

Analysis on Current Limiting Characteristics of Double Quench Flux-Lock Type SFCL Using Its Third Winding (삼차권선을 이용한 이중퀜치 자속구속형 초전도한류기의 전류제한 특성 분석)

  • Han, Tae-Hee;Lim, Sung-Hun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.29 no.5
    • /
    • pp.289-293
    • /
    • 2016
  • The flux-lock type superconducting fault current limiter (SFCL) connects the two parallel windings in parallel with a ferromagnetic core. We suggest that the double quench flux-lock type SFCL should add a third winding. We analyzed characteristics of the fault current and the peak current using the quench of the high-Tc superconducting element. The proposed SFCL's inductances of a primary winding and the third winding were fixed and the amplitude of inductance of the secondary winding was changed. We found that the fault current can be more effectively controlled through the analysis of the equivalent circuit and the short-circuit tests.

Analysis Operating Characteristics of Matrix-Type Superconducting Fault Current Limiter in Ground Faults of Power Grid (전력계통의 지락사고에 대한 매트릭스형 초전도 한류기의 동작특성)

  • Oh, Kum-Gon;Cho, Yong-Sun;Choi, Hyo-Sang;Oh, Seong-Bo;Kim, Deog-Goo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.10
    • /
    • pp.14-20
    • /
    • 2009
  • It is very important for power stability to suppress the excessive fault current happened frequently in the real power grid The superconducting fault current limiter (SFCL) is one of the most effective ways to reduce the fault current among the facilities developed so far. In this paper, we have investigated the operating characteristics of the power grid with the SFCL according to three types such as the single, double and triple line-to-ground faults. In addition, we analyzed the consumption power of the superconducting units based on the working data of the SFCL. We confirmed that the fault current could be limited lower than its peak value to 85 percentage in initial fault condition and to 85 percentage after one cycle in the matrix-type SFCL. The consumption powers of the superconducting units were almost equal by reduction of the difference of the critical current between superconducting units element.