• Title/Summary/Keyword: Distribution lines

Search Result 1,027, Processing Time 0.023 seconds

A Study on the Development of Corrosion Detecting System for 22.9 kV Distribution Power Line Insulation Cable (22.9kV 배전선로 절연전선의 부식 검출 시스템 개발에 대한 연구)

  • Kim, Yong-Jun;Oh, Yong-Cheul;Yi, Keon-Young
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.7
    • /
    • pp.1410-1416
    • /
    • 2011
  • A corrosion detecting system for 22.9 kV distribution power line insulation cable, which can travel autonomously along the live line, is proposed. Eddy current test method is employed to detect the corrosion, and the system developed here is capable of detecting internal corrosion of a ACSR-OC. Somewhat details of the electrical and mechanical mechanism of the system and traveling algorithm are introduced. Experimental results applied to the sample cables having artificial corrosion and the operating distribution lines are provided. From the result, we confirmed that the system is useful for detecting internal corrosion of a ACSR, and is expected to be a new non-destructive testing equipment in the area of diagnosis for the distribution power line.

Current Distribution Factor Based Fault Location Algorithms for Double-circuit Transmission Lines (전류분배계수를 사용하는 병행 2회선 송전선로 고장점 표정 알고리즘)

  • Ahn, Yong-Jin;Kang, Sang-Hee;Choi, Myeon-Song;Lee, Seung-Jae
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.50 no.3
    • /
    • pp.146-152
    • /
    • 2001
  • This paper describes an accurate fault location algorithm based on sequence current distribution factors for a double-circuit transmission system. The proposed method uses the voltage and current collected at only the local end of a single-circuit. This method is virtually independent of the fault resistance and the mutual coupling effect caused by the zero-sequence current of the adjacent parallel circuit and insensitive to the variation of source impedance. The fault distance is determined by solving the forth-order KVL(Kirchhoff's Voltage Law) based distance equation. The zero-sequence current of adjacent circuit is estimated by using a zero-sequence current distribution factor and the zero-sequence current of the self-circuit. Thousands of fault simulation by EMTP have proved the accuracy and effectiveness of the proposed algorithm.

  • PDF

Phase Shift Analysis and Phase Identification for Distribution System with 3-Phase Unbalanced Constant Current Loads

  • Byun, Hee-Jung;Shon, Sugoog
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.4
    • /
    • pp.729-736
    • /
    • 2013
  • Power grids are large complicated networks in use around. An absolute phase value for a particular unknown-phase line at a local site should be identified for the operation and management of a 3-phase distribution network. The phase shift for a specific point in the line, as compared with a phase reference point at a substation, must be within a range of ${\pm}60^{\circ}$ for correct identification. However, the phase shift at a particular point can fluctuate depending on the line constants, transformer wiring method, line length, and line amperage, etc. Conducted in this study is a theoretical formulation for the determination of phase at a specific point in the line, Simulink modeling, and analysis for a distribution network. In particular, through evaluating the effects of unbalanced current loads, the limitations of the present phase identification methods are described.

Applied Technology of FRP Single Pole for Power Distribution Line (배전용 지지물의 FRP 적용 기술)

  • 박기호;조한구;한동희
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.07a
    • /
    • pp.79-81
    • /
    • 2000
  • Outdoor insulation of overhead distribution lines with wood, concrete and steel pole has been safety under various environmental conditions including contamination, moisture condensation, rain and lightning overvoltages. In this paper introduce to FRP technology of the power distribution single pole. FRP pole has been used very much as high strength material for insulators because of its high strength and good insulation properties. In addition, FRP pole was made by filament winding method. In a filament winding process, a band of continuous resin-impregnated rovings or monofilaments is wrapped around a rotating mandrel and cured to produce axisymmetric hollow parts.

  • PDF

Frequency Distribution for Soybean Seed Size in $F_{2}\; and\; F_{3}$ Generation ($F_{2}\; and\; F_{3}$ 세대에서 대두 종자크기에 대한 빈도분포)

  • ;James E. Specht
    • Journal of Life Science
    • /
    • v.7 no.4
    • /
    • pp.355-357
    • /
    • 1997
  • Seed size is a important yield components in soybean (Glycine max L.). The seed size frequency distributions in the mating between two G. max parents possessing quite different seed size exhibited a continuous distribution in the F$_{2}$ and F$_{3}$ generations. A progeny seed size equal to that of either parent was not observed in either generation. The population mean seed size in each generation was less than the mid-parent, with the distribution of lines skewed toward the small seeded parent.

  • PDF

Analysis on the Short Circuit Current of a Low Voltage Direct Current(DC) Distribution System using PSCAD/EMTDC (PSCAD/EMTDC를 이용한 저전압 직류 배전 시스템의 단락 고장 전류 분석)

  • Ahn, Jae-Min;Jeon, Jeong-Chay;Lim, Young-Bae;Bae, Seok-Myeong;Byeon, Gil-Sung;Lee, Kyoung-Ho
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.59 no.4
    • /
    • pp.473-476
    • /
    • 2010
  • In this paper, we analyzed the short circuit current of a low voltage direct current distribution system. For the analysis, we performed the modeling of the low voltage direct current distribution system with a 6-pulse three-phase thyristor rectifier using the PSCAD/EMTDC, surveyed impedance of sources, transformers and distribution lines to run a simulation. A result of the simulation is that short circuit currents of the direct current distribution system with the rectifier decreased due to a thyristor-ON-resistance(Ron). But in case of the low thyristor-ON resistance, output fault current of the rectifier increased over three-phase short circuit current of an AC power system without a rectifier by regular ratio of the rectifier. Because the output fault current of the rectifier can increase over interrupting the capacity of circuit breakers, studying short circuit currents of a low voltage direct current distribution system with a rectifier is necessary for introducing the direct current distribution systems.

Bayesian and maximum likelihood estimations from exponentiated log-logistic distribution based on progressive type-II censoring under balanced loss functions

  • Chung, Younshik;Oh, Yeongju
    • Communications for Statistical Applications and Methods
    • /
    • v.28 no.5
    • /
    • pp.425-445
    • /
    • 2021
  • A generalization of the log-logistic (LL) distribution called exponentiated log-logistic (ELL) distribution on lines of exponentiated Weibull distribution is considered. In this paper, based on progressive type-II censored samples, we have derived the maximum likelihood estimators and Bayes estimators for three parameters, the survival function and hazard function of the ELL distribution. Then, under the balanced squared error loss (BSEL) and the balanced linex loss (BLEL) functions, their corresponding Bayes estimators are obtained using Lindley's approximation (see Jung and Chung, 2018; Lindley, 1980), Tierney-Kadane approximation (see Tierney and Kadane, 1986) and Markov Chain Monte Carlo methods (see Hastings, 1970; Gelfand and Smith, 1990). Here, to check the convergence of MCMC chains, the Gelman and Rubin diagnostic (see Gelman and Rubin, 1992; Brooks and Gelman, 1997) was used. On the basis of their risks, the performances of their Bayes estimators are compared with maximum likelihood estimators in the simulation studies. In this paper, research supports the conclusion that ELL distribution is an efficient distribution to modeling data in the analysis of survival data. On top of that, Bayes estimators under various loss functions are useful for many estimation problems.

Development of Parallel Arc Fault Detector Using Ripple Voltage (리플전압을 이용한 병렬아크 사고 감지기 개발)

  • Choi, Jung-Kyu;Kwak, Dong-Kurl
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.21 no.5
    • /
    • pp.453-456
    • /
    • 2016
  • The major causes of electrical fire in low-voltage distribution lines are classified into short-circuit fault, overload fault, electric leakage, and electric contact failure. The special principal factor of the fire is electric arc or spark accompanied with such electric faults. This paper studies the development of an electric fire prevention system with detection and alarm of that in case of parallel arc fault occurrence in low-voltage distribution lines. The proposed system is designed on algorithm sensing the instantaneous voltage drop of line voltage at arc fault occurrence. The proposed detector has characteristics of high-speed operation responsibility and superior system reliability from composition using a large number of semiconductor devices. A new sensing control method that shows the detection of parallel arc fault is sensed to ripple voltage drop through a diode bridge full-wave rectifier at electrical accident occurrence. Some experimental tests of the proposed system also confirm the practicality and validity of the analytical results.

Development of a high Impedance Fault Detection Method in Distribution Lines using Neural network (신경회로망을 이용한 배전선로 고저항 사고 검출 기법의 개발)

  • 황의천;김남호
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.13 no.2
    • /
    • pp.80-87
    • /
    • 1999
  • This paper proposed a high impedance fault detection method using a neural network on distribution lines. The $\upsilon-i$ characteristic curve was obtained by high impedance fault data tested in various soil conditions. High impedance fault was simulated using EMTP. The pattern of High Impedance Fault on high density pebbles was taken as the learning model, and the neural network was evaluated on various soil conditions. The average values after analyzing fault current by FFT of even.odd harmonics and fundamental rms were used for the neural network input. Test results were verified the validity of the proposed method .ethod .

  • PDF

Development of RCD Auxiliary Trip Device by using High Precision Current Sensor (고정밀 전류센서를 이용한 RCD 보조트립 장치 개발)

  • Kwak, Dong-Kurl
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.8
    • /
    • pp.1532-1537
    • /
    • 2009
  • Nowadays the diversity and large-capacity of electric appliances are strong effect on electrical fires augment in an alarming way. But, as the inactive response characteristics of the existing RCD (Residual Current protective Device) used on low voltage power distribution lines, so control of overload and electric short circuit faults, major causes of electrical fires, are not enough. Therefore this paper is confirmed the unreliability of the existing RCD by electrical faults simulation and is proposed a auxiliary trip device of RCD by using a high precision current sensor (namely, reed switch) for the prevention of electrical disasters in low voltage power distribution lines caused by overload or electric short circuit faults. The sensitive reed switch in the proposed ATD (auxiliary trip device) exactly detects the increased magnetic flux with the overload or the short current caused by a number of electrical faults, and then rapidly cuts off the existing RCD. The proposed auxiliary trip device of RCD is confirmed the excellent characteristics in response velocity and accuracy in comparison with the conventional circuit breaker through various operation performance analysis. The proposed ATD can also prevent electrical disaster, like as electrical fires, which resulted from the malfunction and inactive response characteristics of the existing RCD.