In this paper, we analyzed the short circuit current of a low voltage direct current distribution system. For the analysis, we performed the modeling of the low voltage direct current distribution system with a 6-pulse three-phase thyristor rectifier using the PSCAD/EMTDC, surveyed impedance of sources, transformers and distribution lines to run a simulation. A result of the simulation is that short circuit currents of the direct current distribution system with the rectifier decreased due to a thyristor-ON-resistance(Ron). But in case of the low thyristor-ON resistance, output fault current of the rectifier increased over three-phase short circuit current of an AC power system without a rectifier by regular ratio of the rectifier. Because the output fault current of the rectifier can increase over interrupting the capacity of circuit breakers, studying short circuit currents of a low voltage direct current distribution system with a rectifier is necessary for introducing the direct current distribution systems.

Keywords

References

  1. D Nilsson, A Sannino, "Efficiency analysis of lowand medium-voltage DC distribution system", IEEE PES., 2004
  2. D Nilsson, "DC Distribution Systems", Division of Electric Power Engineering Department of Energy and Environment CHALMERS UNIVERSITY OF TECHNOLOGY, Sweden, 2005
  3. 이경호, 구경완, "구내 직류배전기술과 그린홈 구현사례", 대한전기학회, 전기의세계, vol.59, No.7, July, 2010.
  4. 송길영, "송배전공학", 동일출판사, 2006
  5. ANSI/IEEE C37. 010-1979
  6. 대한전기학회, "배전시스템공학", 대한전기학회, 2006