• 제목/요약/키워드: Difficult ground

검색결과 785건 처리시간 0.026초

전류 및 전위 보조전극을 수직으로 배치하는 전위강하법을 이용한 접지저항의 측정 (Measurement of the Ground Resistance using the Fall-of-Potential Method with the Vertically-placed Current and Potential Auxiliary Electrodes)

  • 이복희;김기복;김유하
    • 조명전기설비학회논문지
    • /
    • 제26권3호
    • /
    • pp.53-60
    • /
    • 2012
  • The fall-of-potential method is commonly used in measuring the ground resistance of large-scaled grounding system and the current and potential auxiliary electrodes are horizontally arranged. Because the distances between the ground grid to be tested and auxiliary electrodes are limited in downtown areas, it is very difficult to measure accurately the ground resistance of large-scaled grounding system. In this paper, the fall-of-potential method of measuring the ground resistance with the vertically-placed current and potential auxiliary electrodes was examined and discussed. The validity and good accuracy of the proposed method of measuring the ground resistance were confirmed through various simulations and actual tests carried out in uniform and two-layer soil structures.

대지파라미터에 따른 접지저항의 변동 특성에 관한 연구 (A Study on the Variation Characteristics of Ground Resistance According to Ground Parameters)

  • 한기붕;정세중;이대종;이상익
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 A
    • /
    • pp.434-436
    • /
    • 2000
  • It is difficult to accurately measure the ground resistance because it varies widely not only with the type of soil but also with the ground parameters; the moisture, the temperature the buried depth of electrodes, and the ground augmentation material and so on. Therefore, in this paper we analyzed the relation between the parameters and the resistance of ground in order to obtain a method of maintaining ground resistance stable. In experiments, the variation coefficients of ground resistance were calculated by the monthly measured data. The ground resistance decreases as the length of the ground rod increases. The variation between the ground resistance and the moisture rate of soil was low in case of using the ground augmentation material. Without the ground augmentation material, the ground resistance decreases as the moisture rate of soil increases. The ground resistance becomes small when the earth temperature becomes low.

  • PDF

다층토 지반에서 매입말뚝(SIP)의 신뢰성 연구 (The Reliability of SIP Pile in Layered Ground)

  • 이민선;황의석;이봉열;김학문
    • 한국지반공학회:학술대회논문집
    • /
    • 한국지반공학회 2002년도 봄 학술발표회 논문집
    • /
    • pp.567-574
    • /
    • 2002
  • Rapid urbanization of many cities require large scale constructions such as high rise buildings in difficult ground conditions. SIP(Soil-cement Injected Precast pile) type piles are tile most popular choice of foundation method in soft ground as well as layered ground in many cities in Korea since SIP offer negligible amount of noise and vibration. But SIP method of construction provide wide range of pile capacity depending on the construction method, equipment, ground conditions and quality control method etc. Therefore this paper intend to investigate the reliability of SIP pile in layered ground through a comparison of existing design formulars and SIP pile load test.

  • PDF

난삭재의 고능률 연삭을 위한 연삭숫돌의 개발에 관한 연구 (A Study on the Development of High Performance Grinding Wheel for the Difficult-to-Grind Materials)

  • 조기수;이종한;손기락
    • 한국정밀공학회:학술대회논문집
    • /
    • 한국정밀공학회 1995년도 춘계학술대회 논문집
    • /
    • pp.118-123
    • /
    • 1995
  • A new grindignwheel was developed for the high performance gfinding of difficult-to-grind materials. Te grinding performance (such as grinding forces, grinding ratio, and surface roughness of ground surface) of the newly developed wheel was evaluated through experiments. Experimental results show that the performance of the newly developed wheel is superior to conventional alumina wheel and comparable to the S-G wheel.

  • PDF

Umbrella Arch 공법에 의한 터널 천단부 보강시 주변 지반의 거동에 관한 연구 (A Study on the Ground Movement around Tunnel Reinforced by Umbralla Arch Method)

  • 배규진;김창용;문홍득;훙성완
    • 터널과지하공간
    • /
    • 제7권4호
    • /
    • pp.299-309
    • /
    • 1997
  • Soil and rock improvement and reinforcement techniques are applied to achieve safe tunnel excavation in difficult geological conditions. The Umbrella Arch Method(UAM), one of the auxiliary techniques, is used to reduce ground permeability and improve stabtility of the tunnel by inserting a series of steel pipes into ground around the crown inclined to the longitudinal axis of the tunnel. Additionally, multi-step grouting is added through the steel pipes. UAM combines the advantages of a modern forepoling system with the grouting injection method. This technique has been applied in subway, road and utility tunneling sites for the last few years in Korea. This paper presents the results of analysis of the case studies on ground movements associated with UAM used in the Seoul Subway line 5 constructon site. Improvement of tunnel stability and decrease of ground settlement expected with pipe insertion are also discussed. Finally, the method to minimize ground settlements caused by NATM tunnelling are suggested.

  • PDF

Trend of global land cover mapping and global land cover ground truth database

  • Tateishi, Ryutaro;Sato, Hiroshi P.;Lin, Zhu
    • 대한원격탐사학회:학술대회논문집
    • /
    • 대한원격탐사학회 2002년도 Proceedings of International Symposium on Remote Sensing
    • /
    • pp.715-720
    • /
    • 2002
  • There are many global/continental or large area land cover mapping projects because land cover is one of key parameters in environmental studies. Though ground truth collection is a important and difficult task in land cover mapping, it is usually performed independently in each project without any cooperation between them. This is the background of the development of Global Land Cover Ground Truth (GLCGT) database by the cooperation of many projects and researchers. The developed GLCGT database will be used freely by any researcher. This cooperative and common development of GLCGT database will realize reliable and continuously improved land cover ground truth data. It also eliminates duplicated efforts of ground truth collection among projects.

  • PDF

비접지 LVDC 배전망의 지락고장 검출을 위한 분석 (Analysis for Pole to Ground Fault Detection in Ungrounded LVDC Distribution Network)

  • 박철원
    • 전기학회논문지P
    • /
    • 제67권3호
    • /
    • pp.119-124
    • /
    • 2018
  • Recently, LVDC distribution network and DC microgrid with many advantages are being built. However, this LVDC distribution is an IT grounded or ungrounded system, and it is difficult to detect a ground fault because the fault current is small. In this paper, we propose a signal injection method for unipolar LVDC distribution network to detect ground fault in ungrounded LVDC distribution, and various analyzes were performed for ground fault detection.

운전중인 전력설비의 접지저항 측정방법 (A measuring Method of Ground Resistance for Energized Power Systems)

  • 이복희;김성원;엄주홍;이승칠
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2000년도 학술대회논문집
    • /
    • pp.77-81
    • /
    • 2000
  • The purpose of this paper is to describe a new measuring method of ground resistance for the grounding system in energized power equipment and substations. It is very difficult to measure the accurate ground resistance in energized power equipment and substations because of the noise conducted from all external connections to the grounding system and harmonics components caused by unbalanced loads and overloads. The ground resistance that is measured with existing methods includes not only the effect of desired signals but also noise components for the measurement period in grounding system. The measured value of ground resistance can entirely be different from actual value. In this paper, to eliminate 60[Hz] power system interference and harmonic components the low-pass filter method was used in the measurement of ground resistance.

  • PDF

지표면전위 해석에 의한 접지저항 측정기법에 관한 연구 (A Study on the Measurement of Grounding Resistance based on the Earth Surface Potential Analysis)

  • 윤장완;안용호;정길조;한병성
    • 조명전기설비학회논문지
    • /
    • 제16권4호
    • /
    • pp.117-123
    • /
    • 2002
  • 접지저항의 측정은 접지계통의 접지성능이 적정한가를 평가하기 위한 가장 기본적이고 중요한 작업이라고 할 수 있다. 그러나 실제 현장에서, 특히 접지극의 크기가 큰 경우일수록 접지저항을 정확히 측정하기란 쉽지 않은데, 이는 정확한 접지전위 측정을 위한 기준전위 점을 찾기가 힘들기 때문이다. 본 논문에서는 접지극 주변에서 측정한 지표면전위를 분석하여 기준전위 점의 위치를 정확히 식별하는 방법과 그 정당성을 제시하였다.

임펄스 전류에 대한 대규모 접지시스템의 정상상태 및 과도상태의 접지임피던스 특성 (Charicteristics of Stationary and Transient Ground Impedance of Large-Scale Grounding Piles)

  • 이복희;이승칠;박종순
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2296-2298
    • /
    • 1999
  • The stationary ground resistance and the transient ground impedance of grounding system are very important parameters in the field of lightning and surge protection. But, it is very difficult to obtain correct values of them in large-scale grounding system. In this paper, the stationary and transient ground impedances of a large-scale grounding system have been measured and analyzed under impulse currents. In order to obtain correct values of them, we have described Z-v(impedance vs ground potential rise) distributions and Z-t waveforms. The transient ground impedance of 36 [m] long three-parallel grounding piles have showed the inductive aspects and the hysterisis region under impulse currents.

  • PDF