• Title/Summary/Keyword: Deteriorated wire

Search Result 34, Processing Time 0.027 seconds

The Properties Analysis of 600V Grade Polyvinyl Chloride Insulated Wire with Variation of Thermal Stress (열적 스트레스 변화에 따른 600V 비닐절연전선의 특성 분석)

  • 최충석
    • Fire Science and Engineering
    • /
    • v.15 no.1
    • /
    • pp.108-115
    • /
    • 2001
  • In this paper, we analyzed the properties change of electric wire when the thermal stress was applied to 600V grade polyvinyl chloride insulated wire (IV). In the structure analysis, normal wire has the properties of direction on the surface, but in case of deteriorated wire at above $400^{\circ}c$, it formed the carbide, the crack and the crystal. The surface composition rate of normal wire was Cu : 100%, but the section composition of the deteriorated wire at $800^{\circ}c$ showed Cu : 78.89%, O : 21.11%. In result of analyzing the differential scanning calory of copper wire, the new reaction peak was observed on the deteriorated wire at above $700^{\circ}c$. In case of the deteriorated wire as $150^{\circ}c$ at the differential thermal analysis, an endothermic reaction appeared at $264^{\circ}c$ lower than the reactive point of normal wire. The occupation rate of oxygen according to the deterioration of copper wire is about 20% at $500^{\circ}c$.

  • PDF

Analysis of Properties Variation of Thermal Deteriorated 600V Grade Hest-Resistant Polyvinyl Chloride Insulated Wires (열열화된 600V 2종 비닐절연전선의 특성변화 분석)

  • Choe, Chung-Seok;Lee, Gyeong-Seop;Lee, Deok-Chul
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.49 no.1
    • /
    • pp.8-12
    • /
    • 2000
  • The properties variation by deterioration of the 600V grade heat-resistant polyvinyl chloride insulated wire(HIV) was analyzed. The weight variation of the thermal deteriorated HIV was about 42% at 80$0^{\circ}C$ and over. From the analysis result of the metallurgical microscope photographs it shows that the sorface of normal wire showed the elongated structures. However the elongated structures did not appear at $900^{\circ} and over and we could observe that particles were grown. The grown oxidized substances in the thermally deteriorated electric wire were observed by SEM. The CuL, CuK, $CuK_b$, OK and CIK spectra of the thermally deteriorated HIV at $300^{\circ}C$ were uniform regardless of the scanning length, but the spectra of CIK could not found at above $700^{\circ}. At the DTA analysis, the endothermic reactions were occurred around $3006{\circ}C\; and\; 400^{\circ}C$ and the exothermic reactions were occurred around $470^{\circ}, respectively.

  • PDF

A Study on the Growing Characteristics of Dendrite Structure of Melted Wire Deteriorated by Over Current (과전류 열화에 의해 용단된 전선의 수지상 조직 성장특성에 관한 연구)

  • Shong, Kil-Mok;Choi, Chung-Seog;Kim, Dong-Woo;Kwak, Hee-Ro
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1463-1465
    • /
    • 2003
  • In this paper, we studied on the growing characteristics of dendrite structure of melted wire deteriorated by over current. Electric wire was melted by Jolue's heat. By using HSIS(High Speed Imaging System), we found out a lot of melted parts of wire were dispersed and radiated. Electric wire had narrow melted areas in case of short fusing time. A lot of very small dots generated around the grain of copper cross-section and they were changed into dendrite structure. Dendrite structure appeared at the values lower than 2.5[A/sec]. In case of very short fusing time, fusing current was calculated by empirical formula. The Preece equation was not enough to analyze a variety of characteristics of melted wire because it did not consider melting time, atmosphere, etc.

  • PDF

A Study on the Electrical-Fire Analysis and Firing Characteristics of Power Cord by Thermal Stress (열적 피로에 의한 전원코드의 발화 특성과 전기화재 분석에 관한 연구)

  • 최충석;송길목;김향곤;김동욱;김동우
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2003.04a
    • /
    • pp.164-170
    • /
    • 2003
  • In this paper, we studied on the firing characteristics and electrical fire analysis of power cord deteriorated by thermal stress. The cross section of PVC insulating cord deteriorated by indirect flame decreased through heat convection. PVC insulating cord deteriorated by direct flame was bumpy shape. The exothermic peak of normal cord was shown at ($526.7^{\circ}C$), but the peaks or on(heat treatment temperature) ($150^{\circ}C$) cord was shown at ($299.6^{\circ}C$) and [$502.2^{\circ}C$]. The exothermic peaks according to high temperature were similar to those of amorphous carbon. In the FT-IR analysis, the absorption peak of normal cord indicated double bond of oxygen and carbon in benzene ring at 1720.0$cm^{1}$. As the HTT was high, the height of characteristic peak decreased and the peak of carbonyl group was shown at about 1625.7$cm^{-1}$. The characteristic peak of single bond(O-H) was shown at about 3479.2$cm^{-1}$. In case of the internal part of wire covering deteriorated by over current, the characteristic peak were shown at about 3417.3$cm^{-1}$ and 1600.2$cm^{-1}$. The above results show that we can distinguish the differences according to the fire pattern through the internalㆍexternal analysis of wire covering deteriorated by heat.

  • PDF

Mechanical characteristic of ACSR Transmission lines by forest fires (산불에 열화된 ACSR 전선의 기계적 특성 검토)

  • Kang, J.W.;Jang, T.I.;Hong, D.S.;Park, C.G.;Bang, H.K.;Kim, Y.D.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.506-508
    • /
    • 2003
  • In the case of a fire in the mountains, steel wires coated with zinc and aluminum wires of those power cables exposed to the fire or near around will be deteriorated by the blaze and the high temperature. This paper shows the experimental results that apply to a new wire by an artificial flame-maker and results including the intensity of extension and wrench for a conductor. In addition, there's been an experiment and analysis about the mechanical characteristics of the wire of ACSR $480mm^2$ which was removed from A T/L by a forest fire. Then, the database will be made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.

  • PDF

The characteristics analyses of deteriorated PVC insulated flexible cords by over-current (과전류에 의해 열화된 비닐코드의 특성 분석)

  • Kim, Hyang-Kon;Choi, Chung-Seog;Kim, Dong-Ook;Chung, Hun-Sang
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07a
    • /
    • pp.489-492
    • /
    • 2003
  • In this paper, we experimented on the deterioration process of power supply cords and analyzed the heating temperature of each part of those cords. We also analyzed the surface states, metallurgical structures surface structures and compositions of the wire melted by over-current. In the results of the analyses, the covering began to be deteriorated from the inside. The heating temperature of extension cord was higher than that of plug body. The dendrite structures appeared at the melted wire. By the SEM and EDS analyses, the dendrite structure showed the growth of copper oxide. We found out the characteristics of PVC insulated flexible cords by over-current from the above experiments and analyses. These results may be useful data in the analyses of deterioration causes of power supply cords.

  • PDF

The surface profile of Wire-cut EDMed Surface by Lapping Process (래핑가공에 의한 와이어 방전가공면의 표면형상)

  • 이재명;김원일;왕덕현;이윤경
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 2001.04a
    • /
    • pp.956-959
    • /
    • 2001
  • In die and mould industry, major material such as cemented carbide is broadly used for increasing the life time and decreasing the cost. It is also required the development for the skills of wire-cut electrical discharge machining(WEDM), but the WEDMed surface was found to be worst due to the attached components of wire. Precision machining method like lapping is necessary for obtaining high quality surface. The lapping compound such as Al2O3 and SiC and cast iron lap can be used for lapping process. The components of Cu and Zn were found WEDMed surface of the specimen. As the result, the low quality of precision was obtained and the heat damage layer of the specimen was occurred. The value of surface hardness was deteriorated, and therefore finish process was required.

  • PDF

The analysis of the dynamic response between the pantograph and overhead wire (고속열차 주행을 위한 판토그래프와 가선시스템과의 동적응답 해석)

  • Shin Seung-Kwon;Song Yong-Soo;Mun Hyung-Scok;Eum Ki-Young;Kim Jae-Mun
    • Proceedings of the KSR Conference
    • /
    • 2004.10a
    • /
    • pp.1366-1371
    • /
    • 2004
  • The development of the European railway high speed network brings new problems related to the interoperability across the railways of different countries. The pantograph and the overhead wire form a dynamic coupled system and they affect each other through the contact force. Unfortunately, as the operational speed of a train increases, the vibration of the pantograph and the overhead wire also increases. This may lead to a zero contact force between the pantograph head and the overhead wire, which can results in the loss of contact, arching and abrasion. If the arching and spark happen between the pantograph and the overhead catenary system, the EMI(electro magnetic interface) and noises may occur. After an, the quality of current collection is deteriorated. This paper describes the dynamic response between the pantograph and catenary system by the numerical simulations and predicts the possibility of operating the high speed train in the conventional lines.

  • PDF

The SAG Behavior of Overhead Conductor due to Forest Fire (산불에 의해 가열된 가공송전선의 이도거동)

  • Kim, Byung-Geol;Kim, Shang-Shu;Jun, Wan-Gi;Han, Se-Won;Kim, Jin-Han
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.11a
    • /
    • pp.516-517
    • /
    • 2007
  • Because forest fire can give a serious damage to overhead conductors, the thorough understanding about sag behavior of burned conductor is very important in maintaining the transmission line safely. Therefore, a systematic investigation was carried out by heating method. As the heating temperature increases, drastic change of tensile strength of Al wire due to the softening of Al wire occurred. When Al wire is exposed to the flame(about $800^{\circ}C$) during only 13 seconds, the remained tensile strength of Al wire showed under 90%. and then sag of overhead conductor become deteriorated. The detailed results will be given in the text.

  • PDF

Reliance analysis for Mechanical characteristics of ACSR Transmission Line due to a Flame (화염에 의한 ACSR 송전선의 기계적 특성에 관한 신뢰성 분석)

  • Kim, Young-Dal;Shim, Jae-Myung;Kim, Jong-Suk
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.71-76
    • /
    • 2004
  • This paper deals with the experimental results that apply to a new wire by an artificial flame-maker because it's difficult to directly analyze the characteristic of deterioration by a forest fire. Those results include tension load, extension rate and torsion number for a conductor. In addition, there's been an experiment and analysis about the mechanical characteristics of the wire of ACSR $48mm^2$ which was removed from Pohang area by a forest fire. Then, the database will be made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.

  • PDF