• 제목/요약/키워드: DC-Surge

검색결과 76건 처리시간 0.066초

Electrical Behaviors of ZnO Elements under Combined Direct and Alternating Voltages

  • Yang, Soon-Man;Lee, Bok-Hee;Paek, Seung-Kwon
    • Journal of Electrical Engineering and Technology
    • /
    • 제4권1호
    • /
    • pp.111-117
    • /
    • 2009
  • This paper presents the characteristics of leakage currents flowing through zinc oxide (ZnO) surge arrester elements under the combined direct-current (DC) and 60 Hz alternating-current (AC) voltages. The current-voltage characteristic curves (I-V curves) of the commercial ZnO surge arrester elements were obtained as a function of the voltage ratio a. At constant peak value of the combined DC and AC voltage, the resistive leakage current of the ZnO blocks was significantly increased as the voltage ratio $\alpha$ increased. The I-V curves under the combined DC and AC voltages were placed between the pure DC and AC characteristics, and the cross-over phenomenon in both the I-V curves and R-V curves was observed at the low current region. The ZnO power dissipation for DC voltages was less than that for AC voltage in the pre-breakdown region and reversed at higher voltages.

AC/DC 병가선로의 개폐서지 과전압 해석 (Analysis of Switching Surge Over-voltage in AC/DC Hybrid Transmission Lines)

  • 유성수;신구용;문채주
    • 한국전자통신학회논문지
    • /
    • 제17권3호
    • /
    • pp.459-466
    • /
    • 2022
  • 개폐서지는 전력시스템에서 발생하는 과전압 현상 중의 하나이며 변전소의 차단기 등 개폐장치의 동작이나 송전선로의 고장으로 인해 발생한다. 특히 송전선로의 절연설계를 위하여 개폐서지의 피크를 산정하는 것은 매우 중요하고 AC/DC 병가선로의 안정적인 운영을 위한 절연협조의 기본적인 검토항목이다. 본 논문에서는 새로운 AC/DC 병가구조의 전력시스템에 대한 상정해석을 위하여 AC 765kV와 DC ±500kV Bi-Pole 시스템이 조합된 송전선로를 대상으로 하였다. 일반적으로 교류 송전시스템의 절연설계를 위한 비정상적인 과전압은 외부과전압으로 낙뢰에 의한 과전압과 내부과전압으로 개폐에 의한 과전압을 고려한다. 직류 송전시스템의 경우에는 개폐에 의한 과전압 보다 송전선로의 중간에서 지락고장이 발생하면 인접한 정상선로에 유기되는 내부과전압을 개폐서지라하며 직류송전선로에 유기되는 가장 큰 일시적인 과전압을 의미한다. 본 논문의 연구목적으로 구성된 선로에 대하여 EMTDC 소프트웨어를 사용하여 모의하였으며, 다양한 AC/DC 혼합 형태에 대한 개폐과전압의 영향을 검토하였다.

중첩전압(직류+교류 60Hz)에서 산화아연 피뢰기 소자의 누설전류 특성 (The characteristic of leakage current in ZnO surge arrestor elements with mixed direct and 60Hz voltage)

  • 이복희;박건영;강성만;최휘성;오성균
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.186-188
    • /
    • 2003
  • The ZnO surge arrester is the protective device for limiting surge voltages on equipment by diverting surge current and returning the device to its original status. The occurrence of overvoltage appears in any phase to AC power supply system and it appears in mixing AC and impulse voltages, moreover because HVDC power supply system uses converter in semiconductor, it makes mixed DC and high harmonics voltages. In this study, the various mixed AC and DC voltages was made for investigating the degradation effect of ZnO arrester according to mixed voltage. As a result, the increase of DC component to mixed voltages causes the increase of resistive component of total leakage current to ZnO block. In changing V-I curve for mixed voltages, the cross-over point acts a factor as making the proper capacitor size of an equivalent circuit for ZnO block.

  • PDF

뇌임펄스전류에 의한 ZnO 피뢰기의 열화특성 (Degradation Properties of ZnO Surge Arresters Due to Lightning Impulse Currents)

  • 이수봉;이복희
    • 조명전기설비학회논문지
    • /
    • 제23권4호
    • /
    • pp.79-85
    • /
    • 2009
  • 이 논문은 피임펄스전류의 입사에 따른 ZnO 피뢰기의 열화 특성에 대하여 기술하였다. 뇌서지에 의한 ZnO 피뢰기의 열화특성을 분석하기 위해 시료 ZnO 피뢰기에 8/20[${\mu}s$], 2.5[kA]의 표준뇌임펄스전류를 인가하였다. 뇌임펄스전류를 인가한 것과 인가하지 않은 ZnO 피뢰기에 흐르는 상용주파수 AC 및 DC 누설전류를 측정하였다. 그 결과 임펄스전류의 인가횟수가 증가함에 따라 누설전류는 증가하였고 AC전압에서 누설전류의 비 대칭성은 뚜렷하게 나타났다. 뇌임펄스전류를 인가하지 않은 ZnO 피뢰기의 ZnO 입자는 균일한데 반해 뇌임펄스전류를 인가한 ZnO 피뢰기의 ZnO 입자는 불균일하게 변형되었다. 또한 뇌임펄스전류 인가에 따른 $Bi_2O_3$의 감소가 입계층의 결핍을 발생시키며 입계층의 결핍에 의한 전류의 집중이 ZnO 피뢰기 소자의 비선형 특성의 열화에 대한 중요한 요인으로 작용한 것으로 밝혀졌다.

직류 전차 탑재형 피뢰기의 하우징 설계 및 성능평가 (Performance Evaluation and Housing Design for Direct Current Surge Arrester in Railway Rolling Stock)

  • 조한구;김석수;한세원;이운용
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 하계학술대회 논문집
    • /
    • pp.128-131
    • /
    • 2000
  • The main objective of this paper is to design and test a new type of polymer ZnO surge arrester for DC power system of railroad vehicles. The rated voltage is 1500V direct current. The main research works are focused on structure design by finite element method, rating voltage, temporary over voltage and studies of characteristics of polymeric surge arrester.

  • PDF

직류전동차 탑재용 피뢰기의 최적선정에 관한 연구 (A Study on the Optimal Selection of Lightning Arresters for DC Electric Traction Vehicles)

  • 길경석;류길수;송재용;김일권;박대원;한문섭
    • 한국철도학회논문집
    • /
    • 제10권2호
    • /
    • pp.112-116
    • /
    • 2007
  • In this paper, we proposed a selection and application recommendations of ZnO arresters for DC electric traction vehicles. To decide the Continuous Operating Voltage($U_C$), the Rated Voltage($U_r$), and the Nominal Discharge Current(In), we measured and analyzed system voltages and surge currents flowing the arrester installed on a DC electric traction vehicle under running state. System voltages measured up to 1,800 V in 1,500 V-system, and surge currents were recorded up to 3 times per a running-service-route and their magnitudes were ranges of $150A{\sim}2kA$. From these results and a standard EN50163, we could proposed $U_C$, $U_r$, and In available for the 1,500 VDC electric traction vehicles.

지락고장에 의해 금속제 유연전선관에 유도된 개폐서지전압의 특성 (Characteristics of the Switching Surge Voltages Induced at Metal Flexible Conduits Due to Ground Faults)

  • 이복희;신건진;박희열;엄상현;김유하
    • 조명전기설비학회논문지
    • /
    • 제27권5호
    • /
    • pp.74-80
    • /
    • 2013
  • This paper presents the transient behavior of the switching surge voltages generated by interruption of DC ground fault currents flowing through metal flexible conduits. All fault circuits consist of line parameters such as resistance, inductance, capacitance and conductance. The use of nonmagnetic metal conduits should be taken into account in order to reduce the inductance of battery charger distribution circuits. The frequency-dependent circuit parameters of metal flexible conduits were measured. The switching surge voltages generated at the ground fault circuit consisted of steel-galvanized alloy and aluminium conduits were investigated. As a result, the impedances of metal flexible conduits are significantly increased over the range of the frequency above 10 kHz and the switching surge voltages generated along aluminium flexible conduit are lower than those along steel-galvanized alloy conduit when DC fault current is interrupted.

전력용 피뢰기의 임펄스에 의한 파손과 대척 기술 (Fracture and Protection Technologies against Impulse of Power Arresters)

  • 한세원;조한구;김석수
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 하계학술대회 논문집
    • /
    • pp.190-193
    • /
    • 2001
  • ZnO varistors have been widely used to protect power system and electronic system against overvoltages based on their excellent nonlinearity. In order to increase their protection capability, the fracture and protection technologies of arresters have to study according to their applications, namely ImA DC voltage, leakage currents, impulse residual voltages, withstanding capability to impulse surge, and energy absorption capability. ZnO varistors which have nonlinear current-voltage characteristic name a number of failure mechanism when ZnO elements absorb surge energies. Failure mode by thermal stress and Pin hole are among the most common failure mechanism at the high current surge current. In this study, the fracture mechaism of power arresters are introduced and protection technologies are researched. In particular the effect of thermal stress by surge currents to ZnO elements and methods against arc surge energy through withstand structure design of arrester are discussed.

  • PDF

새로운 소용량 승압형 PWM 초퍼 회로의 특성 (Characteristics of New Small Scale Boost PWM Chopper Circuit)

  • 김휘칠;박한석
    • 조명전기설비학회논문지
    • /
    • 제23권9호
    • /
    • pp.98-107
    • /
    • 2009
  • 기존의 하드 스위칭 고주파 PWM DC-DC 컨버터는 펄스 변조 캐리어 주파수의 고주파화를 수반하고, 전력용 반도체 스위칭 소자의 스위칭 손실의 증대나 스위칭 과도현상이 수반된 전압 서지나 전류 서지에 의한 EMI 등의 문제점들이 있다. 이러한 문제를 효과적으로 해결하기 위해 본 논문에서는 새로운 소용량 승압형 PWM 쵸퍼 회로의 동작원리를 서술하고, 시뮬레이션과 실험을 통하여 특성을 도출하였다.

인버터 서지와 온도스트레스 하에서 PAI/Nano Silica 에나멜와이어의 가속절연수명 평가 (Accelerated Insulation Life Estimation for PAI/Nano Silica Enamelled Wire under Inverter Surge and Temperature Stress)

  • 박재준
    • 전기학회논문지
    • /
    • 제65권10호
    • /
    • pp.1712-1720
    • /
    • 2016
  • AC and DC insulation breakdown voltage was studied for magnet wire coated with double layers of high flexural PAI layer and high anti-corona PAI/nanosilica (15 wt%) layer. The specimens were prepared at various drying temperatures (T/D): $22^{\circ}C$, $240^{\circ}C$, and $260^{\circ}C$, respectively. The increase effects of nanosilica on AC and DC insulation breakdown voltage were not so significant compared to that of magnet wire coil coated with original PAI. And the AC and DC insulation breakdown voltage was improved by decreasing diameter of winding coil. As T/D temperature increased, AC and DC insulation breakdown voltage decreased.