• 제목/요약/키워드: DC leakage current sensor

검색결과 10건 처리시간 0.022초

태양광발전시스템용 직류 누설전류 센서 개발 (Development of DC Leakage Current Sensor for Solar Power Generation System)

  • 김희선;한송엽;한후석
    • 전기학회논문지
    • /
    • 제63권6호
    • /
    • pp.828-833
    • /
    • 2014
  • Grid connected transformerless solar power generation system is frequently used with the benefits of cost and efficiency. However, significant DC leakage current can flow from the DC line into the ground with dielectric breakdown in the transformerless solar power generation system. The leakage current occurred in the DC line causes accidents such as fire and electric shock on human. To resolve this problem, high sensitivity DC leakage current sensor is needed. But recently the studies on safety of DC line are not performed. In this paper, a high sensitivity DC leakage current sensor that can detect DC leakage current in solar power generation system, is proposed. Based on the studies, DC leakage current sensor is fabricated and characteristic tests are carried out. Finally, the accuracy of sensor performance is verified by leakage current experiments in solar power generation system.

절연유(絶緣油) 열화(劣化)센서 특성(特性) 연구(硏究) (A Study on the characteristics of degradation sensor for insulation oil)

  • 전영갑;선종호;강동식;주병수;윤진열;정상진
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1995년도 하계학술대회 논문집 C
    • /
    • pp.1371-1374
    • /
    • 1995
  • It is well known that the degradation of transformer oil conseqently lead to the failure of transformer. This paper discussed the characteristics of the degradation sensor checking transformer oil condition in live line. The degadation sensor is composed of base ring, electrodes and porous ceramic, passed through the transformer oil and checks the transformer oil condition through sensor's leakage current. So it is important to minimize the leakage current of base ring and connection parts. To investigate the leakage current of base ring and connection parts the characteristics of V-T-I and DC 2 KV and other examinations were performed. It is verified that ionized transformer oil caused by the expansion of temperature increases in the leakage current of porous ceramic sensor. It is certification that the leakage current of other parts of porous ceramic is very small(about 2%) compared with the porous ceramic body and it is confirmed that the leakage current in porous ceramic is changed sensitively according to the new oil(NO) and and the degradation oil(DO).

  • PDF

변압기(變壓器) 절연유(絶緣油) 열화(劣化)센서의 특성연구(特性硏究) (A study on the characteristics of degradation sensor for transformer insulation oil)

  • 전영갑;선종호;강동식;김문덕;권동진
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 C
    • /
    • pp.1765-1768
    • /
    • 1996
  • It is well known that the degradation transformer oil is mainly effected to the failure of transformer. In this paper it is discussed the characteristics of the degradation sensor checking transformer oil condition in live line. The degadation sensor composed with base ring, electrodes and porous ceramic passed through the transformer oil and checked the transformer oil condition with sensor's leakage current. It is important to minimize the leakage current of base ring and connection parts. To investigate the leakage current of base ring and connection parts it is examined the characteristics of V-T-I and DC 2 KV and other examinations. It is verified that ionized transformer caused by the expansion of oil temperature increase in the leakage current of porous ceramic sensor. It is certificated that the leakage current of other parts of porous ceramic is very small (about 2 %) than the porous ceramic and it is confirmed that the leakage current in porous ceramic is changed sensitively according to the new oil(NO) and and the degradation oil(DO).

  • PDF

포화자성코어를 이용한 직류전류측정 트랜스듀서 (DC Current Transducer Using Saturable Magnetic Cores)

  • 박영태;정재갑;강전홍;유권상;유광민
    • 한국자기학회지
    • /
    • 제14권4호
    • /
    • pp.138-142
    • /
    • 2004
  • 본 연구는 누설전류와 같은 직류 저 전류를 측정하기 위한 센서 개발에 관한 것이다. 2개의 동일한 링 형태의 자성체 코어를 이용하여 전류센서를 개발하였으며 센서에 대한 특성과 불확도에 대하여 기술하였다. 이 트랜스듀서는 변성기형의 센서, 피크검출기, 기준저주파발진기 그리고 고조파를 함유한 센서의 출력을 측정할 수 있는 정밀 측정회로들로 구성되며 DC 2A까지 측정할 수 있다. 분해능과 감도는 0.㎃. 10㎷/㎃로. 각각 평가되었다.

DC 누설 전류 검출 알고리즘을 내장한 누전 차단기 개발 (Development of ELCB with Built-in Algorithm for DC Leakage Current Detection)

  • 주남규;김남호
    • 한국항행학회논문지
    • /
    • 제18권2호
    • /
    • pp.165-169
    • /
    • 2014
  • 손쉬운 제어성, 운용성 등 다양한 이유로 디지털 부하가 급증하고 있고 이와 함께 부하의 소비 패턴은 직류화 되고있다. 그러나 공급되는 전력은 교류 전원이므로 실질적으로 필요로 하는 부하의 공급 전원인 직류 전원을 만족하기 위하여 교류 전원을 다시 직류로 변환하여 사용하고 있다. 태양광, 풍력, 연료전지 등 신재생 에너지원의 경우 직류 발전을 하는 발전원으로 교류로 변환을 통해 계통에 유입되고 다시 직류로 변환되어 부하에 공급하게 되는 다단 변환을 하게 되어 손실은 지속적으로 증가하게 된다. 에너지원의 효율적인 사용을 위한 직류 기반의 배전 시스템이 필요로 하나, 부하뿐만 아니라 보호 기능을 구현하기 위한 직류 배선용 누전 차단기의 개발이 필요하다. 이에 본 연구에서는 직류 누설 전류에 대한 검출 알고리즘을 구현하고, 이를 위하여 센서에 대한 성능을 검증하고 이를 활용하여 직류를 기반으로 하는 누전 차단기에 적용함으로써 직류 배전 시스템 운용에 있어 보호가 가능할 것으로 기대된다.

실시간 Igr 검출을 위한 센서 모듈의 제작 및 신뢰성 평가에 관한 연구 (A Study on the Fabrication of the Sensor Module for the Detection of Resistive Leakage Current (Igr) in Real Time and Its Reliability Evaluation)

  • 이병설;최충석
    • 한국안전학회지
    • /
    • 제33권1호
    • /
    • pp.28-34
    • /
    • 2018
  • The purpose of this study is to fabricate a sensor module to detect the resistive leakage current (Igr) in real time that occurs to low voltage electric lines and to verify its reliability. In the case of the developed sensor module, wires are inserted into the zero current transformer (ZCT) and current transformer (CT) in advance and then the branch line is connected to the circuit breaker. The measurement result of the resistance of the distribution panel equipped with the developed sensor module shows that the resistance is $0.151m{\Omega}$ between the R and R phases, $0.169m{\Omega}$ between the S and S phases, and $0.178m{\Omega}$ between the T and T phases, respectively. The insulation resistance measured at AC 500 V and 1,000 V is $0.08m{\Omega}$ between the R, S, T and N phases, respectively. Then, the insulation resistance measured at DC 500 V is $83.3G{\Omega}$ between the R, S, T and G terminal, respectively. In addition, the applied withstanding voltage is AC 220 V/380 V/440 V and it was found that characteristics between all phases are good. This study measured the standby power by installing the developed sensor module at the rear of the MCCB and switching the circuit breaker on sequentially. The standby power is 1.350 W when one circuit breaker is turned on, 1.690 W when 2 circuit breakers are turned on, and 4.371 W when 10 circuit breakers are turned on. This study also verified the reliability of the standby power of the distribution panel equipped with the developed sensor module using the Minitab Program (Minitab PGM). Since the analysis shows the statistical average of 1.34627 in the reliable range of normal distribution, standard deviation of 0.001874, AD of 0.554, and P value of 0.140, it is found that the distribution panel equipped with the developed sensor module has high reliability.

규격화된 분전반 제작을 위한 표준작업절차(SOP)의 공정 개발 (Process Development of a Standard Operating Procedure (SOP) for the Manufacturing of Standardized Distribution Boards)

  • 고완수;이병설;최충석
    • 한국안전학회지
    • /
    • 제33권5호
    • /
    • pp.21-27
    • /
    • 2018
  • The purpose of this study is to develop a SOP (Standard Operating Procedure) for a distribution board that can monitor the leakage current of a load distribution line in real time. The developed distribution board was fabricated by applying IEC 61439-1. It consists of the distribution board and an alarm device. The work process for making the distribution board was compliant with the KEMC (Korea Electrical Manufacturers Cooperative) regulations. And the AC distribution board range is 1,000 V. In addition, the voltage in DC is less than 1500 V. The distribution board receives a 3-phases and 4-wires power supply system and can supply power to the load of a maximum of 32 single or three phase distribution circuits. Also, leakage current measured on the power distribution board was used by sensors installed. The SOP of the developed distribution board consists of the installation standards for the short circuit alarm device and sensor, the surge protection device, switches and indication lamps, and other devices. The operation procedure was prepared so that each manufacturing step of the distribution board must be confirmed by the persons in charge of preparation, production, quality control and approval before moving forward to the next step.

스마트 분전반 제작을 위한 작업 공정도 개발에 관한 연구 (A Study on the Development of a Work Operation Process Chart for Smart Distribution Board Fabrication)

  • 이병설;최충석
    • 한국안전학회지
    • /
    • 제32권3호
    • /
    • pp.15-20
    • /
    • 2017
  • This study presented the strength of the materials and parts for smart distribution board fabrication, and developed a work operation process chart for smart distribution board fabrication. This work operation process chart for smart distribution board fabrication complied with SPS-KEMC regulations, and the applicable range and object are less than 1,000 V and 1,000 Hz for the AC distribution board and less than 1,500 V for the DC distribution board. The power supply is 3 phase 4 wires ($3{\Phi}$ 4W), divided into a single phase circuit and a 3 phase circuit. In addition, the circuit was configured so that the leakage current flowing through the distribution line of the load could be monitored in real time by using the sensor module installed at the rear end of the circuit breaker. Therefore, the administrator can easily find the risk factor of the load since engineer can check the leakage current of each distribution line. In addition, if a leakage current greater than standard value flows, it is possible to generate an alarm against a short circuit and cut off the leakage current. The work operation process chart for the smart distribution board fabrication consists of the following steps: raw and subsidiary materials, sheet metal work, tube making, welding, painting, busbar fabrication, assembly and wiring, product inspection, shipment, etc. Moreover, symbols, ${\Delta}$, ${\nabla}$, ${\bigcirc}$, ${\Rightarrow}$, etc. were used according to the type of work and work progress so that workers can easily understand the progress of the work.

Performance Improvement of Isolated High Voltage Full Bridge Converter Using Voltage Doubler

  • Lee, Hee-Jun;Shin, Soo-Cheol;Hong, Seok-Jin;Hyun, Seung-Wook;Lee, Jung-Hyo;Won, Chung-Yuen
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권6호
    • /
    • pp.2224-2236
    • /
    • 2014
  • The performance of an isolated high voltage full bridge converter is improved using a voltage doubler. In a conventional high voltage full bridge converter, the diode of the transformer secondary voltage undergoes a voltage spike due to the leakage inductance of the transformer and the resonance occurring with the parasitic capacitance of the diode. In addition, in the phase shift control, conduction loss largely increases from the freewheeling mode because of the circulating current. The efficiency of the converter is thus reduced. However, in the proposed converter, the high voltage dual converter consists of a voltage doubler because the circulating current of the converter is reduced to increase efficiency. On the other hand, in the proposed converter, an input current is distributed when using parallel input / serial output and the output voltage can be doubled. However, the voltages in the 2 serial DC links might be unbalanced due to line impedance, passive and active components impedance, and sensor error. Considering these problems, DC injection is performed due to the complementary operations of half bridge inverters as well as the disadvantage of the unbalance in the DC link. Therefore, the serial output of the converter needs to control the balance of the algorithm. In this paper, the performance of the conventional converter is improved and a balance control algorithm is proposed for the proposed converter. Also, the system of the 1.5[kW] PCS is verified through an experiment examining the operation and stability.

$Ta_2O_{5}$ 박막의 누설전류 및 유전특성과 박막응력 (Leakage Current, Dielectric Properties and Stresses of $Ta_2O_{5}$ Thin Films)

  • 이재석;양승기;신상모;박종완
    • 한국재료학회지
    • /
    • 제5권6호
    • /
    • pp.633-638
    • /
    • 1995
  • 열산화 및 PECVD법으로 p-type(100)Si wafer위에 $Ta_2O_{5}$, 박막을 형성한 후 이들 박막의 전기적 특성과 박막응력 상호간의 관계를 연구하였다 열산화 시편의 경우 dc magnetron sputtering법으로 Ta을 증착시킨 후에 산화온도와 시간을 변수로 열산화시켜 박막을 형성시켰으며 PECVD 시편의 경우 RF power density를 변화시켜가면서 박막을 형성시켰다. 이들 박막의 전기적 특성과 박막응력을 조사하여 전기적 특성과 박막응력 상호간의 관계를 조사한 결과 열산화 박막의 경우 누설전류와 박막응력은 독립적인데 반해 PECVD 박막의 경우 박막응력의 절대값은 누설전류가 증가함에 따라 증가하였다.

  • PDF