• Title/Summary/Keyword: Compartment Fire Test

Search Result 50, Processing Time 0.026 seconds

A Study on the Fire Safety Design and Predicting Fire Behavior Using Compartment Fire Test (단일화재실험을 통한 화재성상예측 및 건축구조물의 화재안전 설계에 관한 연구)

  • Yoon, Ung-Gi;Seo, Dong-Goo;Kim, Dong-Eun;Kwon, Young-Jin
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2013.05a
    • /
    • pp.107-108
    • /
    • 2013
  • In this study, combustibles investigation and fire growth rate experiment were performed for predicting initial fire behavior in buildings. Combustibles investigation was performed for residential buildings, which is most frequently affected by fire in Korea. Spatial characteristics and combustibles properties were separately investigated, and occupied area and layout characteristics of combustibles were identified to produce general layout models. Of the layout models, room was selected for fire test of a single compartment. From this test, fire propagation for each combustible was identified, which was delayed compared to the summed heat release rate of a single combustible.

  • PDF

Numerical analysis to determine fire suppression time for multiple water mist nozzles in a large fire test compartment

  • Ha, Gaghyeon;Shin, Weon Gyu;Lee, Jaiho
    • Nuclear Engineering and Technology
    • /
    • v.53 no.4
    • /
    • pp.1157-1166
    • /
    • 2021
  • In this study, a numerical sensitivity analysis was performed to determine the fire suppression time for a large number of water mist nozzles in a large fire compartment. Fire simulations were performed using FDS (Fire dynamics simulator) 6.5.2 under the same condition as the test scenario 5 of the International Maritime Organization (IMO) 1165 test protocol. The sensitivities of input parameters including cell size, extinguishing coefficient (EC), droplets per second (DPS), and peak heat release rate (HRR) of fuel were investigated in terms of the normalized HRR and temperature distribution in the compartment. A new method of determining the fire suppression time using FDS simulation was developed, based on the concept of the cut-off time by cut-off value (COV) of the heat release rate per unit volume (HRRPUV) and the cooling time by the HRR cooling time criteria value (CTCV). In addition, a method was developed to determine the average EC value for the simulation input, using the cooling time and cut-off time.

Characteristics of Heat Flux in a Compartment Fire - Reduced Scale Test (구획공간 화재의 열유속 특성 - 축소 실험)

  • Kim, Sung-Chan;Ko, Gwon-Hyun
    • Fire Science and Engineering
    • /
    • v.25 no.5
    • /
    • pp.128-133
    • /
    • 2011
  • The present study performs a series of 40 % reduced scale of ISO-9705 fire test to investigate the characteristics of heat flux on the floor level in terms of fire characteristics and location in the compartment. The heat flux was measured with Schmidt-Boelter type heat flux gauge at two locations on the floor level of inside and doorway side of the compartment. Different types of fuel - methane, heptane, toluene, ethanol, polystyrene - were burned in this test series. The measured heat flux inside of the compartment was relatively higher than that of front side as the heat release rate of fire and upper layer temperature increased. The difference of measured heat flux at inside and doorway side increased for high sooty fire. The present study shows that the heat flux distribution at lower layer greatly depend on the thermal radiation from fire and upper layer, not only the upper layer temperature but also various fire characteristics such as composition of combustion gases, soot concentration, ventilation condition and so on.

Thermal Characteristics of Under Ventilated Compartment Fire (환기부족 구획화재의 열적 특성)

  • Kim, Sung-Chan;Hamins, Anthony
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.1
    • /
    • pp.41-48
    • /
    • 2009
  • The present study has been performed to investigate the thermal characteristics of under-ventilated compartment fire which is a typical fire condition in structures. A series of fire experiments was conducted to characterize the thermally driven flow in a 2/5 scale ISO 9705 fire compartment. Three different fuels were used in this test series, methane gas, heptane pool, and polystyrene pellets fire. In order to measure accurate temperature, double shield aspirated thermocouples reducing the effect of radiative energy exchange on temperature measurement were used in addition to bare bead thermocouples. The upper layer temperature for well ventilated fire was increased with increasing heat release rate, but it was slightly decreased for under-ventilated fire. The measured temperatures in the upper layer at the front sampling location were higher than at the rear. Thermal characteristics through the doorway were also analysed for a wide range of heat release rates. This study provides a comprehensive and quantitative assessment of fire behavior for under-ventilation condition of fire.

Numerical Analysis of Heat Flow in Fire Compartment using SIMPLE Algorithm (SIMPLE Algorithm을 이용한 화재실의 열 유체의 수치해석)

  • 김광선;손봉세
    • Fire Science and Engineering
    • /
    • v.6 no.1
    • /
    • pp.17-22
    • /
    • 1992
  • We have derived the general transfer equation for governing the continuity, energy transfer, mass and momentum transfer, and turbulent energy dissipation rate within the fire compartment which has the 800t fire source at the center of the floor. The governing transfer equations have been descretized using the finite volume approach and numerically experimented under the SIMPLE algorithm. In order for the SIMPLE algorithm approach to be physically reliable, the test results are compared with those of Morita's SOR Method using Conjugate Residual Method and found to be close to physical values though the computational convergence time still remains to be upgraded. The treatment of source terms in the system of finite difference equations has been critical in order to converge the governing equations within the appropriate time steps. The criteria of convergence allowance for the whole domain have been checked and the sudden change of the non-linear effects from the source term have been avoided. The criteria has been allowed to be for 5$\times$10$^{-5}$ .

  • PDF

A Experimental Study on Window Glass Breakage in Compartment Fires (구획 화재시 창유리 파괴 현상에 관한 실험적 연구)

  • 이수경;김종훈;최종운;이정훈
    • Fire Science and Engineering
    • /
    • v.12 no.3
    • /
    • pp.21-30
    • /
    • 1998
  • This is a study on the relation of window glass breaking time, shape, and vent condition in a compartment fire through the experiment. We recognize the phenomenon that window glass breakage in a compartment fire be arose from the thermal stresses due to the temperature temperature difference was 233.4$^{\circ}C$ for test 1-3, 138$^{\circ}C$ for text 2-1, 83.6$^{\circ}C$ for test 2-2. The interior test 2-2, 400.9$^{\circ}C$ for test 2-3. so if the flame didn't reach at the surface of window glass, the breakage of glass occure at 40$0^{\circ}C$~50$0^{\circ}C$. when the fire size reached to 1541.14kW, the window might be broken by thermal stress. But window glass was not collapsed.

  • PDF

Numerical predictions of the time-dependent temperature field for the 7th Cardington compartment fire test

  • Lopes, Antonio M.G.;Vaz, Gilberto C.;Santiago, Aldina
    • Steel and Composite Structures
    • /
    • v.5 no.6
    • /
    • pp.421-441
    • /
    • 2005
  • The present work reports on a numerical simulation of a compartment fire. The fire was modeled using a simplified approach, where combustion is simulated as a volumetric heat release. Computations were performed with the commercial code CFX 5.6. Radiation was modeled with a differential approximation (P1 model), while turbulence effects upon the mean gas flow were dealt with a SST turbulence model. Simulations were carried out using a transient approach, starting at the onset of ignition. Results are provided for the temperature field time evolution, thus allowing a direct comparison with the analytical and experimental data. The high spatial resolution available for the results proved to be of great utility for a more detailed analysis of the thermal impact on the steel structure.

A Comparison of the Prediction of Sprinkler Response Time Applying Fire Models (스프링클러 반응시간 예측에 대한 화재모델의 비교)

  • 김종훈;김운형;이수경
    • Fire Science and Engineering
    • /
    • v.15 no.2
    • /
    • pp.46-52
    • /
    • 2001
  • To evaluate the usability of compartment fire models for predicting sprinkler response time, fire experiment was conducted and measured sprinkler response time. The experimental data was compared with zone model "FASTLite"and field model "FDS"and field Model "SMARTFIRE" A Compartment fire conducted in a 2.4 m by 3.6 m by 2.4 m ISO 9705 room and measured H.R.R was approximately 100.3 kW. In test, Sprinkler activation temperature used is $72^{\circ}c$ and responded at 198s. The output of FASTLite, SMARTFIRE and, FDS for this fire scenario were 209s, 183s, and 192s, respectively. As a results, prediction using FDS model approached to that of test very closely and other models showed good approximated results also.

  • PDF

APPLICATIONS OF A MODEL TO COMPARE AFLAME SPREAD AND BEAT RELEASE PROPERTIES OF INFERIOR FINISH MATERIALS IN A COMPARTMENT

  • Kim, Woon-Hyung;James G. Quintiere
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1997.11a
    • /
    • pp.193-200
    • /
    • 1997
  • Flame spread and heat release properties and incident heat flux of interior materials subject to an igniter heat flux in a compartment are investigated and compared by using computer model. A comer fire ignition source is maintained for 10 minutes at 100 kw and subsequently increased to 300kw. In executing the model, base-line material properties are selected and one is changed for each run. Also 4 different igniter heat flux conditions and examined. Results are compared for the 12 different materials tested by the ISO Room Comer Test (9705). The time for total energy release rate to reach 1MW is examined. The parameters considered include flame heat flux and thermal inertia, lateral flame spread parameter, heat of combustion and effective heat of gasfication. The model can show the importance of each property in causing fire growth on interior Hnish materials in a compartment. The effect of ignitor heat flux and material property effects were demonstrated by using dimensionless parameters a, b and Tb. Results show that for b greater than about zero, flashover time in the ISO Room-Corner test is principally proportional to ignition time and nothing more.

  • PDF