• Title/Summary/Keyword: Circulating current loss

Search Result 49, Processing Time 0.023 seconds

A Study on the Reduction Methods of Sheath Circulating Current using the Reduction Equipment in Underground Transmission Systems (지중송전계통에서 저감장치를 이용한 시스 순환전류 저감방안에 관한 연구)

  • Gang, Ji-Won;Yang, Hae-Won
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.9
    • /
    • pp.474-481
    • /
    • 2002
  • Sheath circulating current is increased in the change of sheath mutual impedance which is caused by unbalanced cable system, and different section length between joint boxes. If excessive current flows in sheath, sheath loss which is reduced the transmission capacity is produced. Recently, excessive sheath circulating current was partially measured in underground cable systems of KEPCO. Accordingly, actual schemes to reduce excessive sheath circulating current are urgently required for installed cable system as well as newly-installing cable systems. This paper describes the relation analysis of sheath circulating current and burying types. And also, various schemes to reduce excessive circulating current using EMTP/ATPDraw and applicable schemes are proposed through a detailed analysis regarding cable systems by considering various electrical and environmental factors. It is evaluated that the proposed reduction schemes can be effectively applied to reduce the excessive sheath circulating current with the minimized electrical problems. And reduction effect is Proved with sheath circulating current reduction equipment.

A Study on the Characteristic and Rising Cause of Sheath Circulating Current by Analysis and Measurement (해석 및 측정을 통한 시스순환전류 특성 및 상승원인 검토)

  • Gang, Ji-Won;Yang, Hae-Won
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.10
    • /
    • pp.525-533
    • /
    • 2002
  • It is common to install multiple lines in the same route. Recently, excessive sheath circulating current was partially measured in underground cable systems of KEPCO. Especially, the installation type, unbalance section length between joint boxes and zero sequence current by distribution cable have an effect on the rising of sheath circulating current in the underground transmission system. If excessive current flows in sheath, sheath loss which is reduced the transmission capacity is produced. This paper describes the relation analysis of sheath circulating current and burying types. And also, a detailed analysis on rising cause and characteristic of sheath circulating current by considering various unbalanced conditions presents using analysis and measurement regarding cable systems which have the problem of excessive sheath circulation current.

Zero-Current-Switching in Full-Bridge DC-DC Converters Based on Activity Auxiliary Circuit

  • Chu, Enhui;Lu, Ping;Xu, Chang;Bao, Jianqun
    • Journal of Power Electronics
    • /
    • v.19 no.2
    • /
    • pp.353-362
    • /
    • 2019
  • To address the problem of circulating current loss in the traditional zero-current switching (ZCS) full-bridge (FB) DC/DC converter, a ZCS FB DC/DC converter topology and modulation strategy is proposed in this paper. The strategy can achieve ZCS turn on and zero-voltage and zero-current switching (ZVZCS) turn off for the primary switches and realize ZVZCS turn on and zero-voltage switching (ZVS) turn off for the auxiliary switches. Moreover, its resonant circuit power is small. Compared with the traditional phase shift full-bridge converter, the new converter decreases circulating current loss and does not increase the current stress of the primary switches and the voltage stress of the rectifier diodes. The diodes turn off naturally when the current decreases to zero. Thus, neither reverse recovery current nor loss on diodes occurs. In this paper, we analyzed the operating principle, steady-state characteristics and soft-switching conditions and range of the converter in detail. A 740 V/1 kW, 100 kHz experimental prototype was established, verifying the effectiveness of the converter through experimental results.

A Study on the Reduction of Sheath Circulating Current in Underground Transmission Systems (지중송전계통의 시스순환전류 저감에 관한 연구)

  • Jung, C.K.;Hong, D.S.;Lee, J.B.;Kang, J.W.;Yu, C.H.;Kang, W.T.
    • Proceedings of the KIEE Conference
    • /
    • 2001.11b
    • /
    • pp.29-33
    • /
    • 2001
  • Sheath circulating current results from the change of sheath mutual impedance which is caused by unbalanced cable system, and different section length between joint boxes. If circulating over current flows in sheath, it produces much sheath loss which reduces the transmission capacity. And also such large sheath current influences severely on the operator. Recently, large sheath circulating current was partially measured in underground cable system of KEPCO. Accordingly, actual schemes to reduce sheath circulating over current is urgently required for installed cable system as well as newly-constructing cable system. This paper describes the analysis of sheath circulating current and various schemes to reduce the large circulating current in case of operating cable system using EMTP/ATPDraw. And also, possible schemes are proposed through a detailed analysis regarding cable systems by considering various electrical and environmental factors. It is evaluated that the proposed reduction schemes can be effectively applied to reduce the large sheath circulating over current with the minimized electrical problems.

  • PDF

Power Control Method for Reducing Circulating Current in Parallel Operation of DC Distribution System

  • Shin, Soo-Cheol;Lee, Hee-Jun;Kim, Young-Ho;Lee, Jung-Hyo;Lee, Taeck Kie;Won, Chung-Yuen
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.5
    • /
    • pp.1212-1220
    • /
    • 2013
  • In general, for a large power system like DC distribution system for buildings, several power converters are modularized for parallel operation. However, in parallel operation, inconsistency of parameters in each module causes circulating current in the whole system. Circulating current is directly related to loss, and, therefore, it is most important for the safety of the power system to supply the suitable current to each module. This paper proposes a control method to reduce circulating current caused during parallel operation. Accordingly, the validity of parallel operation system including response characteristics and normal state was verified by simulation and experiment result.

A Phase-Shifted Full-Bridge Converter With a New Rectifier Circuit for Reducing Circuiting Current (순환전류 감소를 위한 새로운 정류회로를 갖는 위상천이 풀브리지 컨버터)

  • Choi, Byoung-Gi;Lee, Woo-seok;Lee, Il-Oun
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.26 no.3
    • /
    • pp.237-240
    • /
    • 2021
  • This research proposes a new rectifier circuit to reduce the circulating current of a phase-shifted full bridge converter. The proposed circuit is a structure in which the output inductor of the secondary rectifier circuit is changed to a coupled inductor in the phase-shifted full bridge with the existing center-tapped rectifier. The parts are rearranged after adding a diode. After applying the proposed circuit, the circulating current to the primary current of the transformer and the voltage stress of the rectifier diode on the secondary side of the transformer are reduced. Accordingly, the snubber loss of the rectifier is improved. By reducing the circulating current and snubber loss, the circuit achieves higher efficiency than conventional circuits. In this research, we present the structure of the proposed circuit, its strengths, and the analysis results from experiments. Furthermore, its effectiveness is verified through the experimental results of a prototype converter with an input of 300-400 V and an output of 50 V/1 kW.

Modified Current Differential Relay for $Y-{\Delta}$ Transformer Protection ($Y-{\Delta}$ 변압기 보호용 수정 전류차동 계전기)

  • Jin, En-Shu;Kang, Yong-Cheol
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.3
    • /
    • pp.95-101
    • /
    • 2006
  • This paper proposes a modified current differential relay for $Y-{\Delta}$ transformer protection. The relay uses the same restraining current as a conventional relay, but the differential current is modified to compensate for the effects of the exciting current. A method to estimate the circulating component of the delta winding current is proposed. To cope with the remanent flux, before saturation, the core-loss current is calculated and used to modify the measured differential current. When the core then enters saturation, the initial value of the flux is obtained by inserting the modified differential current at the start of saturation into the magnetization cure. Thereafter, the core flux is then derived and used in conjunction with the magnetization curve to calculate the magnetizing current. A modified differential current is then derived that compensates for the core-loss and magnetizing currents. The performance of the proposed differential relay was compared against a conventional differential relay. Test results indicate that the modified relay remained stable during severe magnetic inrush and over-excitation, because the exciting current was successfully compensated. This paper concludes by implementing the relay on a hardware platform based on a digital signal processor. The relay does not require additional restraining signal and thus cause time delay of the relay.

Sheath Circulating Current Analysis of a Crossbonded Power Cable Systems

  • Jung, Chae-Kyun;Lee, Jong-Beom;Kang, Ji-Won
    • Journal of Electrical Engineering and Technology
    • /
    • v.2 no.3
    • /
    • pp.320-328
    • /
    • 2007
  • The sheath in underground power cables serves as a layer to prevent moisture ingress into the insulation layer and provide a path for earth return current. Nowadays, owing to the maturity of manufacturing technologies, there are normally no problems for the quality of the sheath itself. However, after the cable is laid in the cable tunnel and is operating as part of the transmission network, due to network construction and some unexpected factors, some problems may be caused to the sheath. One of them is the high sheath circulating current. In a power cable system, the uniform configuration of the cables between sections is sometimes difficult to achieve because of the geometrical limitation. This will cause the increase of sheath circulating current, which results in the increase of sheath loss and the decrease of permissible current. This paper will study the various characteristics and effects of sheath circulating current, and then will prove why the sheath current rises on the underground power cable system. A newly designed device known as the Power Cable Current Analyser, as well as ATP simulation and calculation equation are used for this analysis.

Proposition of Improved Neutral Grounding Method and Analytical Evaluation on Practicality in Underground Distribution System (지중배전시스템의 개선된 중성점 접지방식 제안과 실효성에 대한 해석적 평가)

  • Jeong, Seok-San;Lee, Jong-Beom;Jang, Seong-Whan;Kim, Yong-Kap;Kwon, Shin-Nam
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.3
    • /
    • pp.479-485
    • /
    • 2011
  • In 22.9kV underground distribution system, power cables are provided with multiple-point ground in which each neutral line of the distribution cable(A, B, C phases) and three-wire common grounded at every connecting section. But in such grounding methods, circulating current flows between the neutral wire and grounding wire. And power loss due to circulating current also occurs in all conductors. Therefore it is getting necessary reducing circulating current in underground distribution system. This paper presents improved grounding method to overcome such problems. The proposed grounding method eliminates circulating current in the neutral line effectively and is verified that there is no electrical problem or any ineffectiveness of operating protection systems. These analyses are carried out by EMTP/ATPDraw to compare each grounding methods in steady and transient state. This grounding method suggested in this paper can be applied on real distribution system after field tests considering elimination of circulating current was implemented.

A Study on the Protection Methods of Sheath Circulating Current Reduction Device in Transient State (과도상태에서의 시스순환전류 저감장치 보호방안에 관한 연구)

  • Kang, Ji-Won;Jung, Chae-Kyun;Lee, Jong-Beom;Lee, Dong-Il;Jung, Gil-Jo
    • Proceedings of the KIEE Conference
    • /
    • 2002.11b
    • /
    • pp.53-58
    • /
    • 2002
  • Sheath circulating current is increased as the change of sheath mutual impedance which is caused by imbalance of cable system, and different section length between joint box. If excessive current flows in sheath. sheath loss will be increased and then transmission capacity of underground transmission system is reduced. Accordingly, This paper proposed sheath current reduction device using resistor and reactor and proved the reduction effect of that device using EMTP/ATP. And also in this paper, when transients are occurred at the underground system with reduction device by ground fault and lightning surge. we analyzes transient effect of system variously. From this result. authors establish the protection methods of sheath circulating current reduction device.

  • PDF