• 제목/요약/키워드: Circulating

검색결과 1,825건 처리시간 0.029초

BESS의 병렬운전 시 발생되는 순환 전류 저감을 위한 드룹 제어 기법 (Droop Control Method for Circulating Current Reduction in Parallel Operation of BESS)

  • 신은석;김현준;양원모;한병문
    • 전기학회논문지
    • /
    • 제64권5호
    • /
    • pp.708-717
    • /
    • 2015
  • This paper proposes a new reduction scheme of circulating current when two units of BESS (Battery Energy Storage System) are operated in parallel with conventional droop control. In case of using conventional droop, the terminal voltage of each BESS are not equal due to the unequal line impedance, which causes the circulating current. The operation performance of BESS is critically dependant on the circulating current because it increases system losses which causes the increasement of required system rating. This paper introduces a new reduction scheme of circulating current in which the terminal voltage difference of each BESS is compensated by adding feed-forward path of line voltage drop to the droop control. The feasibility of proposed scheme was first verified by computer simulations with PSCAD/EMTDC software. After then a hardware prototype with 5kW rating was built in the lab and many experiments were carried out. The experimental results were compared with the simulation results to confirm the feasibility of proposed scheme. Two parallel operating BESS with proposed scheme shows more accurate performance to suppress the circulating current than those with the conventional droop control.

3권선 변압기 순환전류 추정 알고리즘 (Estimation of a circulating current of a three-phase Y-Y-$\Delta$ transformer)

  • 강용철;이미선;이병은;장성일;김용균
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.559-560
    • /
    • 2007
  • In the case of the transformers including the delta winding such as a three-phase Y-Y-$\Delta$ transformer, a delta winding current flows in the delta windings. The delta winding current of a three-phase Y-Y-$\Delta$ transformer is decomposed into a non-circulating current and a circulating current. The former can be estimated directly from the line currents, but the latter can not. This paper proposes an estimation method for a circulating current of a Y-Y-$\Delta$ Transformer. A first order differential equation for the circulating current is derived by applying the Kirchhoff's voltage law on the loop of the delta side. The circulating current can be estimated by solving the differential equation. Various test results indicate the algorithm can estimate the circulating current accurately even under over-excitation and magnetic inrush.

  • PDF

대용량 순환유동상 보일러 개념 비교평가 기준 정립 (Comparative Evaluation of Large-scale Circulating Fluidized Bed (CFB) Boiler Concepts)

  • 김태현;최상민;이종민
    • 한국연소학회지
    • /
    • 제14권3호
    • /
    • pp.1-15
    • /
    • 2009
  • The circulating fluidized bed (CFB) boiler has some problems to scale up. Several engineering solutions have been proposed by a few suppliers which had advanced CFB technology. Large-scale CFB design concepts from different suppliers were reviewed and compared. Points of the hydrodynamic and heat recovery were summarized and discussed for developing the guideline of the large-scale circulating fluidized bed boilers.

  • PDF

순환전류제어형 싸이크로콘버터에서 순환전류의 영향 (Effects of Circulating current on the controlled Circulating current Cycloconverter)

  • 고석진;이규종;성세진
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1988년도 전기.전자공학 학술대회 논문집
    • /
    • pp.140-143
    • /
    • 1988
  • In this study, so called high frequency cycloconverter which converts commercial so power source directly to high frequency power source is proposed. In this system, the circulating current play very important role. Its state and magnitude effects on system characteristics. This paper deals with the control method of the circulating current and side band component analysis of high frequency side current which is produced by it.

  • PDF

Comparison of the Walz Nomogram and Presence of Secondary Circulating Prostate Cells for Predicting Early Biochemical Failure after Radical Prostatectomy for Prostate Cancer in Chilean Men

  • Murray, Nigel P;Reyes, Eduardo;Orellana, Nelson;Fuentealba, Cynthia;Jacob, Omar
    • Asian Pacific Journal of Cancer Prevention
    • /
    • 제16권16호
    • /
    • pp.7123-7127
    • /
    • 2015
  • Purpose: To determine the utility of secondary circulating prostate cells for predicting early biochemical failure after radical prostatectomy for prostate cancer and compare the results with the Walz nomagram. Materials and Methods: A single centre, prospective study of men with prostate cancer treated with radical prostatectomy between 2004 and 2014 was conducted, with registration of clinical-pathological details, total serum PSA pre-surgery, Gleason score, extracapsular extension, positive surgical margins, infiltration of lymph nodes, seminal vesicles and pathological stage. Secondary circulating prostate cells were obtained using differential gel centrifugation and assessed using standard immunocytochemistry with anti-PSA. Biochemical failure was defined as a PSA >0.2ng/ml, predictive values werecalculated using the Walz nomagram and CPC detection. Results: A total of 326 men participated, with a median follow up of 5 years; 64 had biochemical failure within two years. Extracapsular extension, positive surgical margins, pathological stage, Gleason score ${\geq}8$, infiltration of seminal vesicles and lymph nodes were all associated with higher risk of biochemical failure. The discriminative value for the nomogram and circulating prostate cells was high (AUC >0.80), predictive values were higher for circulating prostate cell detection, with a negative predictive value of 99%, sensitivity of 96% and specificity of 75%. Conclusions: The nomagram had good predictive power to identify men with a high risk of biochemical failure within two years. The presence of circulating prostate cells had the same predictive power, with a higher sensitivity and negative predictive value. The presence of secondary circulating prostate cells identifies a group of men with a high risk of early biochemical failure. Those negative for secondary CPCs have a very low risk of early biochemical failure.

A Harmonic Circulation Current Reduction Method for Parallel Operation of UPS with a Three-Phase PWM Inverter

  • Kim Kyung-Hwan;Kim Wook-Dong;Hyun Dong-Suk
    • Journal of Power Electronics
    • /
    • 제5권2호
    • /
    • pp.160-165
    • /
    • 2005
  • In a parallel operation of UPS, there are two types of circulating currents between UPS. One is the low order circulating current with a fundamental frequency caused by the amplitude and phase differences of UPS output voltages, and the other is the harmonic circulating current with PWM switching frequency caused by non-synchronized PWM waveforms among UPS. The elimination of the low order circulating current is essential for optimal load sharing in parallel operations of UPS, which can be accomplished by the phase and magnitude control at each UPS. The harmonic circulating current may cause troubles and deteriorate in performance of the controller for optimal load sharing in parallel operation of UPS. This paper presents a PWM synchronizing method to eliminate the harmonic circulation current in parallel operation of UPS. The effectiveness of the proposed scheme has been investigated and verified through experiments by a 50kVA UPS.

지중송전계통에서 시스순환전류 해석 및 저감방안 (Analysis and Reduction Methods of Sheath Circulating Current in Underground Transmission Systems)

  • 정채균;이종범;강지원;장태인
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제50권11호
    • /
    • pp.537-545
    • /
    • 2001
  • This paper describes the analysis of sheath circulating current and various methods to reduce the large circulating current in case of operating cable system using EMTP/ATPDraw. And also, possible methods are proposed through a detailed analysis regarding cable systems by considering various electrical and environmental factors. It is evaluated that the proposed reduction methods can be effectively applied to reduce the large sheath circulating over current with the minimized electrical problems.

  • PDF

Power Control Method for Reducing Circulating Current in Parallel Operation of DC Distribution System

  • Shin, Soo-Cheol;Lee, Hee-Jun;Kim, Young-Ho;Lee, Jung-Hyo;Lee, Taeck Kie;Won, Chung-Yuen
    • Journal of Electrical Engineering and Technology
    • /
    • 제8권5호
    • /
    • pp.1212-1220
    • /
    • 2013
  • In general, for a large power system like DC distribution system for buildings, several power converters are modularized for parallel operation. However, in parallel operation, inconsistency of parameters in each module causes circulating current in the whole system. Circulating current is directly related to loss, and, therefore, it is most important for the safety of the power system to supply the suitable current to each module. This paper proposes a control method to reduce circulating current caused during parallel operation. Accordingly, the validity of parallel operation system including response characteristics and normal state was verified by simulation and experiment result.

지중송전시스템 해석을 통한 시스순환전류 특성 분석 (Characteristics of Sheath Circulating Current by Underground Transmission Systems Analysis)

  • 정채균;이종범;강지원
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 A
    • /
    • pp.449-451
    • /
    • 2002
  • Sheath circulating current rises from the change of sheath mutual impedance which is caused by imbalanced cable system, and different section length between joint boxes. However, mixed burying typo and imbalance section length take many parts of main reasons of sheath circulating current increment in domestic underground transmission power cables. Therefore, the increment reason and variation characteristics of sheath circulating current is analysed with simulation using EMTP/ATPDraw and measuring data of practical cable system which has a problem of exceeding sheath circulating current in this paper.

  • PDF

국내 송전 케이블 시스 순환전류 실측 및 분석 (Measurement and Analysis of Sheath Circulating Current in Domestic Underground Transmission Cables)

  • 하체웅;김정년;이수길;김동욱;이종범;강지원
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제52권4호
    • /
    • pp.193-200
    • /
    • 2003
  • The use of underground transmission tables has continuously increased in densely inhabited urban and suburban area. Due to a increasing demand of underground cables, two or more circuits are installed in parallel for several kilometers. It, however, has not been realized that the sheath circulating current is generated in the system where a large number of cables are laid in the same route. In this paper, Author studied diversely the sheath circulating current on underground cables depending on the various length rate, the phase arrangement, and the grounding resistance of the sheath in the cross-bonded section. It was clear that very large circulating current is generated in cable systems due to unbalanced length rate and phase arrangement in the cross-bonded section.