• Title/Summary/Keyword: Cable Aging

Search Result 126, Processing Time 0.033 seconds

Properties on the Distribution Pattern of Discharge Signals Generated in the Power Cable (전력 케이블에서 발생되는 방전 신호의 분포패턴에 관한 특성 분석)

  • 소순열;홍경진;이우기;이동인;김태성
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1998.06a
    • /
    • pp.13-18
    • /
    • 1998
  • After Computer-based PD measurement was referred in the 1970's, the new technology and a number of digital system have been studied. And the selection of PD patterns, extraction of relevant information for PD recognition are discussed because the number of pulse as a function of discharge magnitude and discharge pulse as a function of the power frequency cycl4e offer the information of the aging insulation. This paper investigates the discharge phase($\phi$) and magnitude(q), as well as the number of discharge(n) with regard to discharge signals generated in power cable. Therefore, according to properties analysis on the distribution of $\phi$ , q and n, it is able to apply in the aging analysis of power cable which visual observation is impossible and distribution change of discharge signals offers much information for risk degree on aging progress of insulation materials.

  • PDF

Estimation of Electrical & Physical Characteristics by Thermal History in XLPE Insulation (XLPE 절연체에서의 열이력에 의한 전기, 물리적 특성 평가)

  • Lee, Sang-Jin;Shim, Sung-Ik;Jeon, Seung-Ik
    • Proceedings of the KIEE Conference
    • /
    • 2008.05a
    • /
    • pp.183-184
    • /
    • 2008
  • The aim of this study is to find out the effects of thermal aging condition on dielectric strength and degree of crtstallinity of XLPE insulation. Thermal properties of XLPE insulation were investigated by DSC(differential scanning calorimetry) and dielectric strength were analyzed using AC BDV tester. Aging of XLPE samples were conducted through different four conditions. The degree of crtstallinity and AC BDV were changed by thermal history. From these results, it can be suggested that DSC and AC BDV test are suitable for diagnostic method of extra high voltage XLPE cable.

  • PDF

Developing a fault diagnosis algorithm on a high current cable of arc furnace (전기로 High Current Cable 고장진단 알고리즘 개발)

  • Choi, Seong-Jin;Jang, Yu-Jin;Kim, Sang Woo
    • Proceedings of the KIEE Conference
    • /
    • 2005.10b
    • /
    • pp.573-575
    • /
    • 2005
  • In the steel industry, a steel melting electric arc furnace is used to produce both carbon and alloy steels. Steel scrap which is charged into the furnace is heated by means of electric arc between graphite electrodes and the scrap. In this melting process, current is supplied to the furnace through HCC(high current cable) which connect the furnace and transformer. Four HCCs are assigned to each phase in our system to divide the current. Since a sudden cable breaking result in the shutdown of melting process, an aging detection of HCC is very important for both an improvement of productivity and cost reduction. In this paper, the aging of the HCC is estimated by using the current ratio between four HCCs.

  • PDF

Crosslinked Characteristics of XLPE Cables by Aging (지중배전 케이블의 노화에 의한 가교도 특성)

  • Lee, Woo-Sun;Cho, Jun-Ho;Choe, Gwon-U;Chung, Chang-Soo;Chung, Yong-Ho;Kim, Sang-Yong
    • Proceedings of the KIEE Conference
    • /
    • 2000.07c
    • /
    • pp.1566-1568
    • /
    • 2000
  • This study refers to the crosslinked characteristics of XLPE cables by aging. The cable failure brings about an enormous loss of power supply and the immense expense for cable replacement. These characterization techniques can be used for identifying a cause of failure and for improving a quality of equipments Also, these play an important role in the detection of premature failure. In order to maintain a cable reliability, quality control is needed strictly. It can be possible to estimate a residual lifetime of power cable using characterization techniques.

  • PDF

Efficiency appraisal of 22.9kV tree retardant power cable (22.9kV 트리억제형 전력케이블의 성능평가)

  • Kim, We-Young;Yun, Dae-Hyuk;Park, Tae-Gone
    • Proceedings of the KIEE Conference
    • /
    • 2002.11a
    • /
    • pp.179-182
    • /
    • 2002
  • XLPE compound have used for insulation of 22.9(kV) power cable. But tree retardant power cable has developed and is going to br used commonly. TR XLPE compound retard production and growth of water tree. In this paper, tensile strength, elongation at break, degree of crosslinking, lightning impulse test, AC breakdown test, cyclic aging for 14days and accelerated water treeing test of TR XLPE insulated power cable were examined according to the KEPCO buying spec. & AEIC CS 5-94 standards. before and after As the result, tensile strength, elongation at break and degree of crosslinking test results of TR XLPE insulation were higher than requirement values. After accelerated water treeing test for 120 days, 240 days and 360 days, AC breakdown voltages were not decreased for accelerated water treeing aging duration

  • PDF

Effects of Hot Water on the Aging of URD Power Cables (지중 배편케이블의 열화에 미치는 온수의 영향)

  • 한재홍;송일근;김주용;이병성;정종욱
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.15 no.7
    • /
    • pp.609-614
    • /
    • 2002
  • In this study, we investigated the effects of hot water on the aging of URD power cables due to the hot water ingress to power distribution lines. Hot water contacted and non-contacted cables extracted from 2 distribution lines were characterized by the measurement of oxidation induction time(OIT) and chemical structure. In OIT measurement, hot water contacted cables showed the shorter OIT than non-contacted ones. Especially, hot water contacted insulation layer near insulation shield showed the shortest OIT. In chemical structure analysis, the antioxidant content was decreased and the acid concentration was increased by hot water ingress. From this results, it can be concluded that the hot water ingress to power cable may be accelerate the aging by means of antioxidant consumption.

Development of Global Insulation Assessment System for Medium Voltage power Cable System (배전용 전력케이블 시스템 포괄진단 설비 개발)

  • 이동영
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.2
    • /
    • pp.66-72
    • /
    • 2003
  • The global assessment system for medium voltage power cable systems has been developed The minimum purpose of diagnostic activity is the economic discrimination and maintenance of bad cables which is likely to cause cable system failure. I have adapted the Aging Time Constant Method to construct the power cable assessment system for the diagnostic purpose. From the field application test and breakdown test results, it could be concluded that the diagnostic system was successful art convenient for the discrimination and maintenance of the bad cables, which is likely to fail sooner or later, economically.

A Study on Insulation Degradation Phenomena in 22kV CV Power Cable (22kV CV케이블에 있어서 절연열화현상의 고찰)

  • Kang, Moo-Seong;Kim, Dong-Shik;Jung, Seong-Yong;Park, Dae-Hee
    • Proceedings of the KIEE Conference
    • /
    • 1996.07c
    • /
    • pp.1797-1800
    • /
    • 1996
  • In this study, the insulation selected in degra-dated-power cable has been observed and aging process about the insulation has been investigated. Most Insulation aging process initiates in the interface of semiconducting layer and the type of the process is the fractal form that was observed between the the semiconducting layer and insulation layer. It is possible to estimate degree of the degration of cable with breakdown test and obtained data have been used to get parameters in order to use Weibull distribution. With this method it is considered to be possible to estimate situation of degration and life prediction.

  • PDF

Development of a Fault Diagnosis Algorithm on a High Current Cable of Arc Furnace (전기로 대전류 케이블 고장진단 알고리즘 개발)

  • Kim, Sang-Woo;Jang, Yu-Jin
    • The Transactions of the Korean Institute of Electrical Engineers D
    • /
    • v.55 no.3
    • /
    • pp.115-118
    • /
    • 2006
  • In the steel industry, a steel melting electric arc furnace is used to produce both carbon and alloy steels. Steel scrap which is charged into the furnace is heated by means of electric arc between graphite electrodes and the scrap. In this melting process, current is supplied to the furnace through HCC(high current cable) which connect the furnace and transformer. Four HCCs are assigned to each phase in our system to divide the current. Since a sudden cable breaking result in the shutdown of melting process, an aging detection of HCC is very important for both an improvement of productivity and cost reduction. In this paper, the aging of the HCC is estimated by using the current ratio between four HCCs.

Analysis of Influence for High Frequency Accelerated Aging of XLPE Cable (XLPE Cable의 고주파 가속열화에 대한 영향 분석)

  • Kim, We-Young;Kang, Dong-Sik;Yun, Dae-Hyuk;Park, Tae-Gone
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1460-1462
    • /
    • 2003
  • XLPE compound have used for insulation of 22.9 [kV] power cable. XLPE compound is aged for use long time in distribution line. The cause of aging is water tree is happening and growth. Accelerated water tree test method are Accelerated volatge method and high frequency method. In this paper, high frequency accelerated water tree was performed. And the result was analysed AC breakdown voltage and size and number of water trees.

  • PDF