제주 ±80kV 60MW HVDC 협조 제어 방안 연구 (A cooperative control study of Jeju ±80kV 60MW HVDC for voltage stability enhancement)

  • 윤종수;서보혁
    • 전기학회논문지
    • /
    • 제61권9호
    • /
    • pp.1221-1225
    • /
    • 2012
  • This paper describes CSC(Current Sourced Converters)-based HVDC operational strategy for voltage stability enhancement in the power system. In case of CSC-based HVDC system, rectifier and inverter consume reactive power up to about 60% of converter rating. Therefore, CSC-based HVDC is basically not useful system for voltage stability even if AC filters and shunt capacitors are attached. But, If the particular power system condition is fulfilled, CSC-based HVDC also can be the rapid reactive power source for voltage stability enhancement using a cooperative control with converter and AC filters/Shunt Capacitors. In this paper, the cooperative control algorithm is presented and simulated to ${\pm}80kV$ 60MW HVDC system in Jeju island.

제주 동기조상기 교체에 따른 계통안정성 영향 연구 (The Affections of System Stability on Replacing the Synchronous Condenser in Jeju Island)

  • 장병훈;윤종수;한정열;심정운;강상균;이병준
    • 전기학회논문지
    • /
    • 제56권10호
    • /
    • pp.1715-1720
    • /
    • 2007
  • The CSC-based HVDC system links the Jeju system to the mainland system. Because CSC-based HVDC is installed in Jeju, the reactive power is needed to transfer active power through the HVDC. In order to supply reactive power, switched capacitors and synchronous condensers are installed in Jeju system. The deterioration of established synchronous condensers, however, causes a reactive power supply capability decline and high maintenance cost. It brings about the instability of Jeju system and the incremental of maintenance and repair costs. In the future the installation of wind generators and additional HVDC system would aggravate the stability of Jeju system. Therefore, it needs to consider a countermeasure against above problems. In this paper, Analysis of several contingencies of Jeju system was peformed, and some contingencies caused voltage-reactive power problem was known. CPF method was introduced in order to make countermeasures to replace the synchronous condensers and to solve the voltage-reactive power problem. The location and capacity of reactive power sources were also decided. It could guarantee medium and long term stability of Jeju system.

제주계통 전압 안정성을 위한 SVC 및 Statcom 동작특성 비교 (SVC and Stacom Characteristics for Voltage Stability in Jeju Power System)

  • 이도헌;이승민;김호민;김일환
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2014년도 전력전자학술대회 논문집
    • /
    • pp.548-549
    • /
    • 2014
  • In Jeju power sytstem, the generation of reactive power depends on the operation of CSC-HVDC filter. Thus, the grid voltage will be affected. Statcom and SVC have demonstrated that it has excellent charateristics to solve this problem. First, this paper analyzes the operation of the Statcom based on the real power system in Jeju. Then, the characteristics of Statcom will be compared to the SVC. The modelling of the Jeju power system including Statcom and SVC will be performed by using PSCAD/EMTDC program and the real data from the real Jeju power system.

  • PDF