Discussions on the Cause of Bucheon LPG Station Accident (부천 LPG 충전소 사고 원인에 대한 연구)

  • 윤재건
    • Journal of the Korean Society of Safety
    • /
    • v.16 no.3
    • /
    • pp.31-34
    • /
    • 2001
  • Cause of Bucheon LPG refueling station accident could not be clearly verified because of opposite talking of men reponsible for the accident the accident, damaged by BLEVE and fire, and no systematic fire investigation. After two and half years, recently first judgement has been carried out. But competitive arguement is going on and first leak point of massive LPG will not be clearly identified with evidences acquired by now. This accident gave us many instructions and advices. Specially, massive LPG leak can result in pool fire and safety of underground-installed storage tank is proved by no damage in the strong BLEVE.

  • PDF

A Study on Damage Effect from Major Accident of LPG Charging Facility - A case study of an LPG Charging and Automotive Outlet - (LPG 충전소 중대사고의 피해효과에 관한 연구 - 부천 LPG충전소 사고 사례를 중심으로 -)

  • Roh, Sam-Kew;Kim, Tae-Hwan;Ham, Eun-Gu;Hong, Chang-Moon
    • Korean Security Journal
    • /
    • no.2
    • /
    • pp.83-98
    • /
    • 1999
  • The LPG station's explosion at Bucheon city was a major accident which with rare frequency of occurrence but large damage effect. Therefore, to prevent similar accident in the future from LPG chargings stations which located at inner urban area, it needs to identify the damage effects of such facilities by comparing theoretically quantities risks-PHAST. The BLEVE effects from the accident showed similar level in case of heat flux, however, the over pressure level reflected at reduced distance. The structure damage to the nearby area showed comparatively large reduction of concrete strength and shape changes through by heat effect while the overpressure effect was small.

  • PDF

A Study on Damge Effect from Boiling Liquid Expanding Vapor Explosion(BLEVE) of LPG Charging Facility (LPG 충전소의 BLEVE 현상에 따른 피해효과 분석)

  • Roh Sam-Kew;Kim Tae-Hwan;Ham Eun-Gu
    • Journal of the Korean Institute of Gas
    • /
    • v.3 no.3 s.8
    • /
    • pp.45-50
    • /
    • 1999
  • The LPG refueling station's explosion at Bucheon city was a major accident which with rare frequency of occurrence and large damage effect. Therefore, to prevent similar accident in the future from LPG charging stations which located in urban area. It needs to identify the damage effects of such facilities by comparing theoretically quantities risk and actual damage. The BLEVE effects from the accident showed similar damage effect in case of heat flux, however, the overpressure level reflected at the reduced distance by $15\%$. The structure damage to the near by area showed comparatively large heat radiation damage to the concrete structure strength and shape changes through heat flux while the overpressure effect was small.

  • PDF

Qualitative Hazard Analysis for LNG Gas Stations Using K-PSR Method (K-PSR을 이용한 LNG 충진소에 대한 정성적 위험성평가)

  • Ko, Jae-Wook;Lee, Jae-Min;Yoo, Jin-Hwan
    • Journal of the Korean Institute of Gas
    • /
    • v.10 no.4 s.33
    • /
    • pp.63-69
    • /
    • 2006
  • With the increased interest in reducing air pollution, supply of natural gas for gas vehicles is increasing. Thus, the number of establishments of LNG and CNG stations is increasing as well. However, due to major gas accidents such as the fire and explosion accident of a Bucheon LPG station in 1998, it is difficult to establish a new station. In this research, we conducted qualitative hazard analysis fer LCNG/LNG multi-station by using the K-PSR method and proposed recommendations for hazard mitigation.