• Title/Summary/Keyword: Brine inlet temperature

Search Result 19, Processing Time 0.021 seconds

Ice Making Characteristics at Ice-on-coil Type Following Change of Ice Making Environment (제빙환경 변화에 따른 아이스 온 코일의 제빙특성)

  • Jung, Eun-Ho;Park, Ki-Won
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.319-323
    • /
    • 2008
  • The study experimented to understand the ice making characteristics on to kinds of round tube type and oval tube type using ice maker. The experiment were carried out under various conditions, that used brine temperature $-10{\sim}-6^{\circ}C$, brine flow rate $1.0{\sim}1.8\;m/s$ and inlet water temperature $6{\sim}-12^{\circ}C$ etc. Mass of ice per making area increased according to the decrease of the brine temperature and inlet water temperature, but that was increased according to the increase of the brine flow rate.

  • PDF

A Numerical Study for the Maximizing Water Vapor Flux and Thermal Efficiency in Direct Contact Membrane Distillation (DCMD) Process (직접 접촉식 막증류 공정에서 담수 투과량 및 열효율 극대화를 위한 수치적 연구)

  • Kim, Sang-Hun;Lee, Jung-Gil;Kim, Woo-Seung
    • Membrane Journal
    • /
    • v.22 no.5
    • /
    • pp.369-380
    • /
    • 2012
  • A one-dimensional numerical model based on the energy and mass equations have been developed to predict the trans membrane water vapor flux and thermal efficiency under various operating conditions in Direct Contact Membrane Distillation (DCMD) process. The model validation have been carried out by experimental data from literature and showed good agreement. The effect of operating parameters such as brine inlet temperature and velocity, and distillate inlet temperature and velocity to increase water vapor flux and thermal efficiency were predicted by the steady-state model. The results showed that the inlet temperature and velocity in brine side are dominant factors to control the water vapor flux and thermal efficiency because the effect of inlet temperature and velocity in brine side showed the higher water vapor flux and thermal efficiency than that of inlet temperature and velocity in distillate side. The water vapor flux was increased 3.4 times in the range of 21.22 $kg/m^2h$ to 71.26 $kg/m^2h$ and the thermal efficiency was increased 37.5% in that of 0.556 to 0.765 with increasing brine inlet temperature from $60^{\circ}C$ to $95^{\circ}C$. Meanwhile, the water vapor flux was increased 30% in that of 27.91 $kg/m^2h$ to 36.33 $kg/m^2h$ and thermal efficiency increased 7.5% in that of 0.6 to 0.646 as the brine inlet velocity was increased from 60 m/h to 300 m/h.

Ice Making Characteristics according to Shape and Diameter on Ice-on-Coil Tube (관외착빙형 제빙관의 형태 및 관경 변화에 따른 제빙 특성)

  • Park, K.W.;Jeong, E.H.;Hwang, S.S.
    • Journal of Power System Engineering
    • /
    • v.16 no.5
    • /
    • pp.32-39
    • /
    • 2012
  • The study experimented to understand ice-on-coil type ice making characteristics on to 3 kinds of circular tube, oval tube and small diameter tube using ice maker. The experiment were carried out under various conditions, that used brine temperature($-10^{\circ}C$, $-6^{\circ}C$), brine flow rate(1.0m/s, 1.8m/s) and inlet water temperature ($6^{\circ}C$, $12^{\circ}C$) etc. Mass of ice per ice making area increased according to the decrease of the brine temperature and inlet water temperature, but that was increased according to the increase of the brine flow rate. Oval ice making tube produced ice 1.11 to 2.46 times that of 9mm circular ice making tube, and 3mm small diameter ice making tube produced ice 1.06 to 1.51 times that of 9mm circular ice making tube.

Ice Making Characteristics According to Changing Shape of Ice Making Tube (제빙관의 형태변화에 따른 제빙특성)

  • Jung, Eun-Ho;Park, KI-Won
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.5
    • /
    • pp.291-296
    • /
    • 2009
  • Ice accumulating system patterned ice-an-coil is the way of refrigerating regenerative materials on the surface of copper-tube inserted into the inside of ice-storage. The study experimented to understand ice-an-coil type ice making characteristics according to changing shape of ice making tube. The experiment were carried out under various conditions, that used brine temperature($-l0^{\circ}C$, $-6^{\circ}C$) brine flow rate(l.0m/s, 1.8m/s) and inlet water temperature($6^{\circ}C$, $12^{\circ}C$) etc. Mass of ice per making area increased according to the decrease of the brine temperature and inlet water temperature, but that was increased according to the increase of the brine flow rate. And I set up two hypotheses and compared the capacity of ice-making of the two cases; each had the same thermal area and one had an round-shaped copper tube but the other had an oval-shaped copper tube.

An Experimental Study on the Performance of Cool Storage System using R141b Clathrate (R141b 포접화합물을 이용한 축냉시스템의 성능에 관한 실험적 연구)

  • Jung, I.S.;Kim, Y.G.;Lee, J.S.;Ro, S.T.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.6 no.4
    • /
    • pp.354-364
    • /
    • 1994
  • Experiments have carried out to investigate the effects of parameters, such as mass ratio of R141b-to-water, stirrer speed, brine inlet temperature, brine flowrate, and additives, on the performance of the cool storage system using R141b clathrate. The cool storage system in this experiment was composed of storage tank, refrigerator, and heater. The results show that the mass ratio of R141b-to-water, 1 : 3~1 : 3.5 gives the best performance and the stirring speed has optimum point as 600rpm. At this speed impeller Reynolds number is $1.01{\times}10^5$. The lower the inlet brine temperature and the highter the brine flowrate, the better performance. The addition of metal powder turned out to reduce the degree of supercooling. The supercooling reduction was proportional to the amount of the metal power. However when metal powder was added more than 0.1 wt%, there was no additional supercooling reduction. The surfactants shortened the time consumed for cool storage to the half of no surfactant added case.

  • PDF

Study of the local heat transfer characteristic on the louver fin by using the expansion model (확대 모델을 이용한 루버 휜의 국부 열전달 특성변화에 관한 연구)

  • Kim, Jung-Kuk;Koyama, Shigeru;Kuwahara, Ken;Park, Byung-Duck;Kim, Dong-Hwi;Sa, Yong-Cheol
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.227-232
    • /
    • 2008
  • The present study was investigated the local heat transfer characteristics and temperature distribution on the louver fin by using the expansion model. Heat transfer rate, frost mass and temperature distribution of the louver fin under frosting condition were experimentally investigated. Local heat transfer rate and heat flux on the louver were analyzed by the conduction heat transfer between top and lower part of the louver. The experimental key parameter was brine inlet temperature(-5, -10, $-15^{\circ}C$). The heat transfer performance and frost mass at brine temperature of $-15^{\circ}C$ were increased by maximum 3 time than the brine temperature of $-5^{\circ}C$. At all experimental case, local heat transfer rate and heat flux of the louver were almost symmetry at the louver number of 6. Especially, local heat transfer rate and heat flux were maximum increased on the louver number of 4 and 8.

  • PDF

An Experimental Study on the Performance Characteristic with Height of a Fin-Tube Liquid Desiccant Dehumidifier (핀-튜브형 액체건조제 제습기의 높이에 따른 성능특성에 관한 실험적 연구)

  • Lee, Su-Dong;Park, Moon-Soo;Chung, Jin-Eun;Lee, Jin-Soo
    • Proceedings of the KSME Conference
    • /
    • 2003.11a
    • /
    • pp.25-30
    • /
    • 2003
  • Several desiccant cooling systems have been developed in terms of cost and performance. In this study a fin-tube exchanger has been used for liquid desiccant dehumidification system. This dehumidifier has been designed to study the absorption characteristic of the aqueous triethylene glycol(TEG) solution which has the flow range from 20 to 50 LPM. The dehumidifier performance characteristic of working factor variables such as inlet solution flow rate, air flow rate, solution concentration, solution temperature, brine temperature, air temperature and inlet air relative humidity has been analyzed. The result of this experiment can provide useful data for hybrid air conditioning system.

  • PDF

Study on the Frosting Phenomenon of the Fin and Tube Heat Exchanger with a Louvered Fin (루버형 휜을 가진 휜관형 열교환기의 착상현상 연구)

  • Kim, Jung-Kuk;Kuwahara, Ken;Koyama, Shigeru;Park, Byung-Duck
    • Journal of the Korean Society of Industry Convergence
    • /
    • v.11 no.4
    • /
    • pp.157-163
    • /
    • 2008
  • The present study investigated the pressure drop and the total frost mass of the louvered fin type heat exchanger, which is widely used at the air-conditioning system. The pressure drop due to the frosting phenomenon and the total frost mass were investigated by changing the wet bulb temperature condition of the inlet air. Hence the brain of 55wt% was used as a cooling solution instead of a common refrigerant. The temperature difference between the brine and the tube outside wall at the outlet of heat exchanger was $10^{\circ}C$, at maximum, higher than that at the inlet of heat exchanger. As the wet bulb temperatures were increased, the pressure drop was linearly increased due to the increment of frost mass. And the increment of heat exchange rate was smaller than that of inlet air enthalpy due to the increment of frost mass. The pressure drop of air side was rapidly increased due to the progress of frosting phenomena. The run time that the pressure drop occurred rapidly was decreased by the growth of frost.

  • PDF

Study on the Performance Characteristics with the Height of a Regenerator and Dehumidifier for Liquid Desiccant Dehumidification System (액체식 제습시스템을 위한 재생기와 제습기의 높이에 따른 성능특성에 관한 연구)

  • 이수동;박문수;정진은;최영석
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.7
    • /
    • pp.630-638
    • /
    • 2004
  • Liquid desiccant dehumidification systems have the ability to provide efficient humidity and temperature control while saving the electrical energy requirement for air conditioning as compared to a conventional system. The dehumidifier and the regenerator form the heart of this system. The latent part of the cooling load is overcome using liquid desiccant. The model regenerator has been designed to study the absorption characteristic of the aqueous triethylene glycol (TEG) solution which is in the flow range from 20 to 50 LPM. Also, this system designed that was able to change the height of the regenerator and dehumidifier. Because the effect of performance have different result according the height. The effect of performance factors of the regenerator with inlet solution flow rate, air flow rate, solution concentration, solution temperature, brine temperature, air temperature and inlet air relative humidity have been analyzed. Data obtained are useful for design guidance and performance analysis of the hybrid air conditioning system.

Influence of the Supercooling Degree and Cooling Rate on a Continuous Ice Formation by a Supercooled Aqueous Solution in Flow Using a Plate Heat Exchanger (판형 열교환기를 이용한 과냉각수용액에서 유동과냉도 및 냉각속도가 연속제빙에 미치는 영향)

  • Lee, Dong-Gyu;Peck, Jong-Hyeon;Hong, Hi-Ki;Kang, Chae-Dong
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.9
    • /
    • pp.647-653
    • /
    • 2007
  • In dynamic ice storage system(DISS), ice slurry is formed not only from solution freezing by mechanical removing parts but also supercooled solution. However, in order to perform continuous ice formation in the system without mechanical moving parts, supercooled aqueous solution should be formed stable through cooling heat exchanger and be dissolved uniformly in storage tank. In previous study, the time of ice slurry increased as the pressure of the cooling heat exchanger(PHX) increased. In this study, a cooling experiment of an ethylene glycol 7mass% solution was performed with various inlet temperature of the PHX, which has constant brine inlet temperature of $-7^{\circ}C$. The temperature in the storage tank maintained to freezing point of the solution. At results, the time of ice slurry formation increased as the supercooling degree decreased and the cooling rate increased.