• Title/Summary/Keyword: Assessment Partial Discharge

Search Result 29, Processing Time 0.027 seconds

A Study on the New Criteria for Assessing the Insulation Deterioration of Generator Stator Winding (발전기 고정자 권선의 새로운 절연열화 판정기준 설정에 관한 연구)

  • Hwang, D.H.;Kim, Y.J.;Kim, J.B.;Jeon, J.W.;Kim, H.G.;Park, J.J.
    • Proceedings of the KIEE Conference
    • /
    • 1997.07e
    • /
    • pp.1692-1695
    • /
    • 1997
  • This paper describes the relationship between the various non-destructive parameters and the breakdown voltage for the 17 kV, 300 MVA and the 22 kV, 500 MVA generators stator bars with polyester and epoxy/mica insulation respectively. Also, this study reports the results of an investigation into the factors which can assess the insulation condition of generator stator winding. Furthermore, a new parameter, Partial Discharge Index(PDI), is introduced as the valuable parameter for the assessment of insulation condition. The ratio between partial discharge increment and the stepwise voltage increment from the Discharge Inception Voltage (DIV) at the characteristic or resonant frequency band shows the close relationship between the breakdown voltage and PDI.

  • PDF

Evaluation of Reliability on the 6.6kV Class Ceramic Coupler for On-line Partial Discharge Measurement in Winding Machines (권선형기기 On-line 부분방전 측정용 6-6kV급 Ceramic Coupler의 신뢰성 평가)

  • Kang Dong-Sik;Kim Yong-Joo;Yun Youn-Ho
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.2
    • /
    • pp.69-75
    • /
    • 2005
  • In order to improve the reliability of high voltage rotating machines and mold transformers, it is necessary to understand the breakdown mechanism and life assessment of the high voltage winding parts. Especially the on-line PD test provides the ability to monitor effects, such as slot discharge, internal discharge, and end-winding discharge without interrupting the electrical machines, this method has been proven the major testing technology. Capacitive couplers have been the most widely used sensors for the on-line partial discharge detection in rotating machines nowadays. This paper deals with the electrical characteristics and long-term reliability of a ceramic coupler(CC), which can be easily mounted into high voltage input terminal part, has been developed and tested to continuously measure PD activity during operating condition. This paper presents electrical characteristics (dielectric loss angle, capacitance, PD inception level, breakdown voltage, and frequency response bandwidth) and long-term life test result of the developed 6.6 kV class on-line ceramic coupling sensor. It was found that this sensor had good electrical characteristics to detect PD activity during the operating condition with its detection frequency band is between several and several tens MHz. Also, the voltage life of the 6.6kV class ceramic coupler was calculated over 60 years.

Development and Site Evaluation of the On-line Partial Discharge Measuring System on the 13 kV Class Stator Windings for Hydro Generator (13 kV급 수력발전기 고정자 권선용 On-line 부분방전 측정 시스템 개발 및 현장적용 평가)

  • Sun, Jong-Ho;Hwang, Don-Ha;Yun, Young-Ho;Shin, Byoung-Chol;Oh, Bong-Keun;Kang, Dong-Sik
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.4
    • /
    • pp.189-198
    • /
    • 2006
  • In order to improve the reliability of stator windings for hydro generators, it is necessary to detect the defective point and life assessment of the high voltage windings. Especially the on-line partial discharge (PD) test provides the ability to monitor effects, such as slot discharge, internal discharge, and end-winding discharge without interrupting generators, this method has been proven the major testing technology in high voltage rotating machines nowadays. The purpose of this paper is to describe the method of the on-line PD measurement on stator windings for hydro-generator with 13 [kV] class ceramic coupler (CC), on-line PD measuring system, terminal box, and index parameters. Also, the developed PD measuring system and 13 [kV] class CC were installed Daechung-dam generator #2. It was found that this installed sensor and system had good electrical characteristics to detect PD activity during the operating condition with its detection frequency band is between several and several tens MHz.

Assessment of 23 kV Capacitive Coupler for On-line Partial Discharge Measurements

  • Jeong, J.Y.;Kang, D.S.;Sun, J.H.;Heo, J.C.;Park, C.H.
    • Journal of Electrical Engineering and Technology
    • /
    • v.4 no.1
    • /
    • pp.123-130
    • /
    • 2009
  • The partial discharge (PD) measurement is a very effective method to assess the winding insulation condition of high-voltage machines, since most of the insulation failure processes are directly or indirectly caused by PD. On-line PD measurements, which can detect insulation defects of winding in the early stages on rotating machines in operation, have been accepted as the most important technique. The epoxy mica capacitive coupler is currently and extensively used for on-line detection of PD pulses of high-voltage rotating machines. To evaluate the feasibility of developing a capacitive coupler that is easier to manufacture at a lower cost compared to epoxy mica couplers, a 100pF capacitive coupler made of ceramic material is designed, fabricated and tested for on-line PD measurements of 23 kV electrical machines. A series of electrical tests and accelerated aging tests are performed on the ceramic coupler to evaluate the performance requirements, long-term reliability and thermal stability for in field application. The test results show that the newly developed ceramic coupler provides equal and improved performance at a lower cost compared to epoxy mica couplers, and estimated voltage life is anticipated to surpass 100 years.

Partial Discharge Tests for Traction Motor Using 1000 pF Couplers (1000 pF 커플러를 이용한 견인전동기 부분방전특성)

  • Ko, Byeong-Hun;Park, Hyun-June;Kwon, Sam-Young;Na, Hae-Kyung;Lee, Hyung-Woo
    • Proceedings of the KSR Conference
    • /
    • 2007.05a
    • /
    • pp.214-218
    • /
    • 2007
  • With the development of high speed railway, traction motors play a critical role in the operation of railway vehicle. This paper describes the use of 1000 pF coupler as a on-line partial discharge (PD) measurement for the assessment of railway traction motor. The PD tests are performed with developed PD analyzer and the 5 model coils such as thermal, electrical, mechanical and environmental aging respectively at various AC voltages. On-line PD tests using 1000 pF couplers show that PD patterns can be detected successfully at 2.3 kV.

  • PDF

UHF Partial Discharge Measurement Technology using a Dual Bands Methods to have the Frequency Characteristics in GIS (GIS에서 주파수 특성을 갖는 이중 대역법에 의한 UHF 부분방전 측정기술)

  • Yi, Sang-Hwa;Sun, Jong-Ho;Kang, Dong-Sik;Kim, Kwang-Hwa
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.3
    • /
    • pp.127-133
    • /
    • 2006
  • This Paper describes a dual bands PD measurement method which has two different bandwidths. The one bandwidth is 0.5 - 2 GHz and the other is 1 - 2GHz. This method is used for GIS diagnosis. In the experiment, it shows that the ratios between two PD quantities in dual bands depend on the defect types and gas pressures. The variations of ratios in different pressures are more sensitive than ones in defect types. And These ratios increase with increasing SF6 gas pressures. As these ratios give us additive information of PD we can analyze the defect type as well as risk assessment for the GIS reliably. Therefore the above result shows that these ratios are one of parameters for diagnosing GIS.

A Study of On-line Monitoring System for a KEPCO Pumped Storage Generator/Motor

  • Kim Hee-Dong;Ju Young-Ho;Kim Yong-Joo;Cho Kyu-Bock
    • Transactions on Electrical and Electronic Materials
    • /
    • v.7 no.2
    • /
    • pp.90-95
    • /
    • 2006
  • An on-line diagnostic test has been studied and performed for the pumped storage generator/motor. This study aims at reducing the diagnostic cost, minimizing the technical dependency on third party manufactures. Further design of on-line diagnostic system such as shorted-turn of rotor winding, partial discharge (PD) of stator winding and air-gap between stator and rotor for pumped storage generator/motor has been verified. In addition, it needs to be validated on site performance of the developed continuous on-line monitoring system for corresponding tasks for the improvement of the availability & reliability during operation.

Assessment of Insulation Condition in High Voltage Motor Stator Windings (고압전동기 고정자 권선의 절연상태 평가)

  • Kim, Hee-Dong;Park, Eui-Gab;Park, Wan-Jo
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2392-2395
    • /
    • 1999
  • This paper describes to access the insulation deterioration condition of the stator windings in six high voltage motors. Nondestructive tests have been carried out on stand-still motors. These tests include ac current increase rate($\Delta$I), delta tan delta(${\Delta}tan{\delta}$), and maximum partial discharge(PD). AC current and $tan{\delta}$ were measured by Schering bridge. The measurement of PD patterns were conducted using digital partial discharge detector. PD patterns were observed treeing and internal discharges in Motor 1 and 2. The stator windings of two motors were found to be in a poor condition and their were recommended to rewind. The stator. windings of four motors were judged to be in serviceable condition.

  • PDF

Electrical Characteristic Assessment of Nomex Paper for Distribution Transformers

  • Song, Il-Keun;Jung, Jong-Wook;Lee, Byung-Sung;Kwak, Hee-Ro
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.3C no.3
    • /
    • pp.86-90
    • /
    • 2003
  • This paper describes the electrical characteristics of Nomex paper employed as an insulating material for distribution transformers. The relative permittivities (dielectric constants) and tan$\delta$ (dielectric dissipation factors) were measured as dielectric characteristics and the partial discharge inception voltages (PDIVs) and breakdown voltages were also measured as electrical strength characteristics of Nomex paper. As a result, the permittivity and tan $\delta$ of Nomex paper demonstrated both temperature and frequency dependency. Of particular note, the permittivity of 0.18 mm Nomex paper was 2.4 according to the ASTM condition, The PDIVs and breakdown voltages were almost linearly increased with the thickness of Nomex paper. Furthermore, its electrical strength was superior to conventional Kraft paper.

Assessment of Insulation Condition in Large Transformers (대형변압기 절연상태 평가)

  • Kim, Hee-Dong;Kong, Tae-Sik;Lee, Young-Jun;Park, Jae-Jun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07a
    • /
    • pp.499-502
    • /
    • 2004
  • In order to detect of insulation problems an early, transformer has to be performed the several tests. The ac current and tan6 of transformer winding insulation were investigated by Schering bridge. Partial discharge(PD) tests are used to evaluate the insulation condition of transformer. The moisture content measurement was conducted using RVM(recovery voltage meter). The RVM test can show that the problem is affecting the paper insulation of transformer. The value of moisture content was 2.3% in main transformer. The insulations of four transformers were judged to be in good condition.

  • PDF