• Title/Summary/Keyword: Anti-Islanding Method

Search Result 68, Processing Time 0.021 seconds

A Novel Active Anti-islanding Method for Grid-connected Photovoltaic Inverter

  • Jung, Young-Seok;Choi, Jae-Ho;Yu, Gwon-Jong
    • Journal of Power Electronics
    • /
    • v.7 no.1
    • /
    • pp.64-71
    • /
    • 2007
  • This paper proposes a novel active frequency drift (AFD) method to improve the islanding detection performance with minimum current harmonics. To detect the islanding phenomenon of grid-connected photovoltaic (PV) inverters concerning the safety hazards and possible damage to other electric equipment, anti-islanding methods have been described. The AFD method that uses chopping fraction (cf) enables the islanding detection to drift up (or down) the frequency of the voltage during the islanding situation. However, the performance of the conventional AFD method is inefficient and causes difficulty in designing the appropriate cf value to meet the limit of harmonics. In this paper, the periodic chopping fraction based on a novel AFD method is proposed. This proposed method shows the analytical design value of cf to meet the test procedure of IEEE Std. 929-2000 with power quality and islanding detection time. To verify the validation of the proposed method, the islanding test results are presented. It is confirmed that the proposed method has not only less harmonic distortion but also better performance of islanding detection compared with the conventional AFD method.

A novel anti-islanding method using Goertzel Algorithm (Goertzel 알고리즘을 이용한 새로운 단독운전 방지 기법)

  • Won, Dong-Jo;Kim, Jae-Hyung;Kim, Jun-Gu;Won, Chung-Yuen;Lee, Tae-Won
    • Proceedings of the KIPE Conference
    • /
    • 2009.11a
    • /
    • pp.299-301
    • /
    • 2009
  • In this paper, a novel anti-islanding method of DC-AC single phase inverter is proposed. The inverter injects a little harmonic current with the output current of a PCS(Power Conditioning System). When the islanding condition is occurred, the voltage harmonic components appear on the output voltage of the PCS due to the injection of a little harmonic current. So, the PCS detects the voltage harmonic components using the Goertzel algorithm, and then the PCS decides that the islanding condition is occurred. When the PCS recognizes the islanding condition, the PCS are stopped. The proposed a novel anti-islanding method is analyzed, and its validity is proven through simulation.

  • PDF

Active Frequency with a Positive Feedback Anti-Islanding Method Based on a Robust PLL Algorithm for Grid-Connected PV PCS

  • Lee, Jong-Pil;Min, Byung-Duk;Kim, Tae-Jin;Yoo, Dong-Wook;Yoo, Ji-Yoon
    • Journal of Power Electronics
    • /
    • v.11 no.3
    • /
    • pp.360-368
    • /
    • 2011
  • This paper proposes an active frequency with a positive feedback in the d-q frame anti-islanding method suitable for a robust phase-locked loop (PLL) algorithm using the FFT concept. In general, PLL algorithms for grid-connected PV PCS use d-q transformation and controllers to make zero an imaginary part of the transformed voltage vector. In a real grid system, the grid voltage is not ideal. It may be unbalanced, noisy and have many harmonics. For these reasons, the d-q transformed components do not have a pure DC component. The controller tuning of a PLL algorithm is difficult. The proposed PLL algorithm using the FFT concept can use the strong noise cancelation characteristics of a FFT algorithm without a PI controller. Therefore, the proposed PLL algorithm has no gain-tuning of a PI controller, and it is hardly influenced by voltage drops, phase step changes and harmonics. Islanding prediction is a necessary feature of inverter-based photovoltaic (PV) systems in order to meet the stringent standard requirements for interconnection with an electrical grid. Both passive and active anti-islanding methods exist. Typically, active methods modify a given parameter, which also affects the shape and quality of the grid injected current. In this paper, the active anti-islanding algorithm for a grid-connected PV PCS uses positive feedback control in the d-q frame. The proposed PLL and anti-islanding algorithm are implemented for a 250kW PV PCS. This system has four DC/DC converters each with a 25kW power rating. This is only one-third of the total system power. The experimental results show that the proposed PLL, anti-islanding method and topology demonstrate good performance in a 250kW PV PCS.

An Improved SMS Anti-islanding Method for Utility Interconnection of Multiple Distributed Power Generations (Multi-inverter 환경에 적합한 SMS기법을 이용한 Anti-islanding 방법)

  • Kim, Tae-Won;Park, Tae-Joon;Lee, Seung-Hee;Han, Mu-Ho
    • Proceedings of the KIPE Conference
    • /
    • 2008.10a
    • /
    • pp.36-38
    • /
    • 2008
  • 본 논문에서는 여러 대의 인버터를 동시에 사용하는 분산전원 환경하에서 Anti-islanding을 효과적으로 할 수 있는 방안을 제안한다. 제안하는 Anti-islanding기법은 SMS(Sliding Mode Frequency Shift)를 근간으로 하면서 공진 Q가 높을 때 검출이 어려운 단점을 해결하는 방법을 제시한다. SMS위상의 변동 값을 판단근거를 사용하지 않고 SMS위상의 적분 값을 판단근거로 사용한다. Run on시간이 0.5초 이내로 국내외 규격을 모두 만족시킨다. 여러 대의 인버터를 병렬로 접속해도 islanding 검출이 탁월하다. 출력전력의 품질 면에 있어서도 다른 Anti-islanding기법에 비해 우수하다. 본 알고리즘의 우수성을 시뮬레이션과 실험을 통해 검증하였다.

  • PDF

Modeling and Evaluation of Slip-Mode Frequency Shift Method for Anti-islanding Method (슬립모드 방식을 이용한 단독운전 검출기법의 모델링과 평가)

  • Yu, Byung-Gyu;Jung, Young-Seok;So, Jung-Hun;Yu, Gwon-Jong
    • Proceedings of the KIPE Conference
    • /
    • 2005.07a
    • /
    • pp.520-522
    • /
    • 2005
  • Islanding phenomenon is undesirable because it lead to a safety hazard to utility service personnel and may cause damage to power generation and power supply facilities as a result of unsynchronized reclosure. In order to prevent this phenomenon, various anti-islanding methods have been studied. Even though the slip mode frequency shift (SMS) method has been regarded as a highly effective anti-islanding method, the analytical design method of that was not cleared. This paper proposes a modeling of the SMS method using non-detection zone (NDZ) and evaluation of the method according to the test conditions of IEEE Std. 929-2000. The SMS method is derived analytically through the modeling and verified visually by simulation and experiment.

  • PDF

Analysis and Modeling of Slip Mode Frequency Shift Method for Anti-islanding (슬립모드 주파수변이 방식의 단독운전 검출법의 분석과 모델링)

  • Yu, Byung-Gyu;Jung, Young-Seok;So, Jung-Hun;Yu, Gwon-Jong
    • Proceedings of the KIEE Conference
    • /
    • 2005.07b
    • /
    • pp.1699-1701
    • /
    • 2005
  • Islanding phenomenon is undesirable because it lead to a safety hazard to utility service personnel and may cause damage to power generation and rower supply facilities as a result of unsynchronized reclosure. In order to prevent this phenomenon, various anti-islanding methods have been studied. Even though the slip mode frequency shift(SMS) method has been regarded as a highly effective anti-islanding method, the analytical design method of that was not cleared. This paper proposes a modeling of the SMS method using non-detection tone(NDZ) and evaluation of the method according to the test conditions of IEEE Std. 929-2000. The SMS method is derived analytically through modeling and verified visually by simulation and experiment.

  • PDF

Anti-islanding Method by Harmonic Injection for Utility Interactive Inverter with Critical Load (중요부하를 갖는 계통연계형 인버터의 고조파주입에 의한 단독운전방지 기법)

  • Oh, Hyeong-Min;Choi, Se-Wan;Kim, Tae-Hee;Lee, Gi-Pung;Lee, Tae-Won
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.17 no.4
    • /
    • pp.315-321
    • /
    • 2012
  • The utility-interactive inverter with critical loads should supply continuous and stable voltage to critical loads even during the grid fault. The conventional control method which performs current control for grid-connected mode and voltage control for stand-alone mode undergoes the critical load voltage variation during grid fault. The critical load voltage may have large transient when the inverter performs mode transfer after the islanding detection. Recently, the indirect current control method which does not have the transient state during not only islanding detection but also the mode transfer has been proposed. However, since the voltage control is maintained even during the grid-connected mode it is difficult to detect the islanding. This paper proposes an active anti-islanding method suitable for the indirect current control method which does not have NDZ(Non-Detection Zone).

A New Anti-Islanding Method for Utility Interconnection of Distributed Power Generation System (분산전원시스템의 계통연계를 위한 새로운 단독운전 방지기법)

  • Hwang In-Ho
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.9 no.6
    • /
    • pp.568-576
    • /
    • 2004
  • This paper presents a new anti-islanding method for distributed power generation system (DPGS) using renewable energy. Based on the concept of real and reactive power mismatch, three different islanding conditions are analyzed. It is shown via analysis that islanding voltage is a function of real power alone, where as its frequency is a function of both real and reactive power. Using this analysis, a new anti-islanding method is developed. The proposed protection algorithm continuously perturbs ($\pm$5%) the reactive power supplied by DPGS while simultaneously monitoring the utility voltage and frequency. If a measurable frequency deviation took place by islanding, the real power of DPGS is further reduced to 80%. This detection method is shown to be fast acting under resonant loads. Possible islanding conditions are simulated and verified with analysis. Experimental results on a 0.5kW utility-interactive fuel cell system are suggested.

The Anti-Islanding Method with Compensation of Load Reactive Power for Grid-connected Photovoltaic Generation System (계통 연계형 태양광 발전 시스템의 부하 무효전력 보상이 적용된 단독운전 인지법)

  • Jeong, Jin-Beom;Shin, Dong-Hyun;Kim, Hee-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.1
    • /
    • pp.58-64
    • /
    • 2008
  • In this paper, we present an active anti-islanding method with a load monitoring system using reactive power control. The proposed method, which is based on reactive power control, has fewer harmonics components than those in conventional methods, and it can minimize the reactive power component of the grid because it compensates the reactive power component with the load monitoring. The proposed quick islanding detection method was confirmed from the experimental results with an inverter for a 3kW photovoltaic system.

THD Analysis of Output Current for Active Frequency Drift Method in Anti-islanding (능동적 주파수 변환기법의 출력전류 고조파 왜형율 분석)

  • Lee, Ki-Ok;Choi, Ju-Yeop;Choy, Ick;Yu, Gwon-Jong;An, Jin-Ung
    • Journal of the Korean Solar Energy Society
    • /
    • v.30 no.1
    • /
    • pp.7-12
    • /
    • 2010
  • As many grid-connected photovoltaic power conditioning systems (PVPCS)are installed in many residential areas simultaneously, these have raised potential problems of network protection on electrical power system. One of the numerous problems is an Islanding phenomenon. In this paper, active frequency drift (AFD) method, one of the anti-islanding methods which is analyzed by current magnitude compensation and calculation of the fundamental component. Both harmonic component and RMS value of the output current for THD analysis are provided and verified by simulation.