This paper proposes a novel active frequency drift (AFD) method to improve the islanding detection performance with minimum current harmonics. To detect the islanding phenomenon of grid-connected photovoltaic (PV) inverters concerning the safety hazards and possible damage to other electric equipment, anti-islanding methods have been described. The AFD method that uses chopping fraction (cf) enables the islanding detection to drift up (or down) the frequency of the voltage during the islanding situation. However, the performance of the conventional AFD method is inefficient and causes difficulty in designing the appropriate cf value to meet the limit of harmonics. In this paper, the periodic chopping fraction based on a novel AFD method is proposed. This proposed method shows the analytical design value of cf to meet the test procedure of IEEE Std. 929-2000 with power quality and islanding detection time. To verify the validation of the proposed method, the islanding test results are presented. It is confirmed that the proposed method has not only less harmonic distortion but also better performance of islanding detection compared with the conventional AFD method.
Keywords
islanding; grid-connected PV systems; active frequency drift method; non-detection zone;
Citations & Related Records

Times Cited By Web Of Science : 6  (Related Records In Web of Science)
연도 인용수 순위
  • Reference
1 Z. Ye, A. Kolwalkar, Z. Yu, P. Du, and R. Walling, 'Evaluation of anti-islanding schemes based on nondetection zone concept,' IEEE Trans. Power Electronics, vol. 19, no. 5, pp. 1171-1176, Sept. 2004   DOI   ScienceOn
2 Y. Jung, J. So, G. Yu, and J. Choi, 'Modeling and analysis of active islanding detection methods for photovoltaic power conditioning systems,' 2004 Canadian Conference of Electrical and Computer Engineering, vol. 2, pp. 979-982, May 2004
3 H.S. Heo, H.S. Kim, H.G. Kim, G.H. Choe, Y.H. Choi, and J.C. Kim, 'The Analysis and design of AFD Method for Anti-Islanding of single-phase UIPV System,' 2006 Autumn Conference of Korean Institute of Power Electronics, pp. 127-130, Nov. 2006
4 M.E. Ropp, M. Begovic, and A. Rohatgi, 'Analysis and performance assessment of the active frequency drift method of islanding prevention,' IEEE Trans. on Energy Conversion, vol. 14, no. 3, pp. 810-816, Sept. 1999   DOI   ScienceOn
5 V. John, Z. Ye, and A. Kolwalkar, 'Investigation of anti-islanding protection of power converter based distributed generators using frequency domain analysis,' IEEE Trans. on Power Electronics, vol. 19, no. 5, pp. 1177-1183, Sept. 2004   DOI   ScienceOn
6 Jun Yin, Liuchen Chang, and Diduch, C., 'Recent developments in islanding detection for distributed power generation,' 2004 Large Engineering systems Conference of Power Engineering, pp. 124-128, July 2004
7 G.A. Kern, 'SunSine300, utility interactive AC module anti-islanding test results,' IEEE Photovoltaic Specialists Conference, pp.1265-1268, Sept. 1997
8 Y. Jung, J. Choi B. Yu, J. So, and G. Yu, 'A Novel Active Frequency Drift Method of Islanding Prevention for the grid-connected Photovoltaic Inverter,' 2005 IEEE 36th Conference on Power Electronics Specialists, pp. 1915-1921, Sept. 2005
9 IEEE Std. 929-2000, IEEE Recommended Practice for Utility Interface of Photovoltaic (PV) Systems, April, 2000