Output Power Analysis of Active Frequency Drift Method for Anti-Islanding (단독운전방지를 위한 능동적 주파수 변환기법의 출력전력 분석)

  • Lee, Ki-Ok;Choi, Ju-Yeop;Choy, Ick;Yu, Gwon-Jong;An, Jin-Ung
    • Journal of the Korean Solar Energy Society
    • /
    • v.29 no.6
    • /
    • pp.75-80
    • /
    • 2009
  • Recently, as the grid-connected photovoltaic power conditioning systems (PVPCS) are installed in many residential areas, these have raised potential problems of network protection on electrical power system. One of the numerous problems is an Islanding phenomenon. In this paper, active frequency drift (AFD) method, one of the anti-islanding methods which is analyzed by current magnitude compensation and calculation of RMS value of the output power is proposed and verified by simulation.

Modeling and Evaluation of Slip-Mode Frequency Shift Method for Anti-islanding Method (슬립모드 방식을 이용한 단독운전 검출기법의 모델링과 평가)

  • Yu, Byung-Gyu;Jung, Young-Seok;So, Jung-Hun;Yu, Gwon-Jong
    • Proceedings of the KIPE Conference
    • /
    • 2005.07a
    • /
    • pp.520-522
    • /
    • 2005
  • Islanding phenomenon is undesirable because it lead to a safety hazard to utility service personnel and may cause damage to power generation and power supply facilities as a result of unsynchronized reclosure. In order to prevent this phenomenon, various anti-islanding methods have been studied. Even though the slip mode frequency shift (SMS) method has been regarded as a highly effective anti-islanding method, the analytical design method of that was not cleared. This paper proposes a modeling of the SMS method using non-detection zone (NDZ) and evaluation of the method according to the test conditions of IEEE Std. 929-2000. The SMS method is derived analytically through the modeling and verified visually by simulation and experiment.

  • PDF

Analysis and Modeling of Slip Mode Frequency Shift Method for Anti-islanding (슬립모드 주파수변이 방식의 단독운전 검출법의 분석과 모델링)

  • Yu, Byung-Gyu;Jung, Young-Seok;So, Jung-Hun;Yu, Gwon-Jong
    • Proceedings of the KIEE Conference
    • /
    • 2005.07b
    • /
    • pp.1699-1701
    • /
    • 2005
  • Islanding phenomenon is undesirable because it lead to a safety hazard to utility service personnel and may cause damage to power generation and rower supply facilities as a result of unsynchronized reclosure. In order to prevent this phenomenon, various anti-islanding methods have been studied. Even though the slip mode frequency shift(SMS) method has been regarded as a highly effective anti-islanding method, the analytical design method of that was not cleared. This paper proposes a modeling of the SMS method using non-detection tone(NDZ) and evaluation of the method according to the test conditions of IEEE Std. 929-2000. The SMS method is derived analytically through modeling and verified visually by simulation and experiment.

  • PDF

A Novel Method for Anti-Islanding Using Reactive Power (무효전력 제어를 이용한 새로운 독립운전 방지 기법)

  • Choi, Bong-Joo;Jeong, Jin-Beom;Kim, Hee-Jun;Baek, Soo-Hyun;Lee, Ju;Ahn, Kang-Soon
    • Proceedings of the KIEE Conference
    • /
    • 2004.10a
    • /
    • pp.203-206
    • /
    • 2004
  • An islanding occurs when the utility grid is removed but distributed sources continuo to operate and provide power to local loads and grid. This can cause a significant risk to safety and equipment. This report present a novel anti-islanding method to prevent an islanding phenomenon. The proposed method changes the reactive power of the load. Therefore the phase difference between output voltage and current is periodically changed within decided value. When the utility-grid is removed, the frequency of output voltage and current will increase or decrease. And the proposed system will detect the change of frequency and shut down the distributed source. While the conventional methods have some difficulties in detecting particular islanding condition such as a small change in loading, the proposed method can detect most conditions. The performance was verified through experiments.

  • PDF

Islanding Detection by Harmonic Current Injection Method for Utility Interactive Photovoltaic System (고조파 주입에 의한 계통연계형 태양광발전시스템의 고립운전 검출)

  • 고재석;채영민;강병희;최규하
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.8 no.2
    • /
    • pp.199-210
    • /
    • 2003
  • In this paper, the new Islanding detection method is studied for utility interactive photovoltaic system(UIPVS). It describes the brief of UIPV system and the features of islanding phenomenon. The new islanding detection method for improving the detection characteristics, HCIM(Harmonic Current Injection Method), is proposed and analyzed. The impedance curve of AC load is derived from the complex power equation for testing Islanding detection features. The proposed detection method and the derivation of islanding condition we verified by the simulation with ACSL and the laboratorial experiments.

Improved RPV(reactive-power-variation) anti-islanding method for grid-connected three-phase PVPCS (3상 계통연계형 태양광 PCS의 단독운전검출을 위한 개선된 무효전력변동기법)

  • Lee, K.O.;Jung, Y.S.;So, J.H.;Yu, B.G.;Yu, G.J.;Choi, J.Y.;Choy, I.
    • Proceedings of the KIEE Conference
    • /
    • 2006.07b
    • /
    • pp.1159-1160
    • /
    • 2006
  • As the grid-connected photovoltaic power conditioning systems (PVPCS) are installed in many residential areas, this has raised potential problems of network protection on electrical power system. One of the numerous problems is an Island phenomenon. There has been an argument that because the probability of islanding is extremely low it may be a non-issue in practice. However, there are three counter-arguments: First, the low probability of islanding is based on the assumption of 100% power matching between the PVPCS and the islanded local loads. In fact, an island can be easily formed even without 100% power matching (the power mismatch could be up to 30% if only traditional protections are used, e.g. under/over voltage/frequency). The 30% power-mismatch condition will drastically increase the islanding probability. Second, even with a larger power mismatch, the time for voltage or frequency to deviate sufficient to cause a trip, plus the time required to execute the trip (particularly if conventional switchgear is required to operate), can easily be greater than the typical re-close time on the distribution circuit. And, third, the low-probability argument is based on the study of PVPCS. Especially, if the output power of PVPCS equals to power consumption of local loads, it is very difficult for the PVPCS to sustain the voltage and frequency in an island. Unintentional islanding of PVPCS may result in power-quality issues, interference to grid-protection devices, equipment damage, and even personnel safety hazards. So the verification of anti-islanding performance is strongly needed. In this paper, the authors propose the improved RPV method through considering power quality and anti-islanding capacity of grid-connected three-phase PVPCS in IEEE Std 1547 ("Standard for Interconnecting Distributed Resources to Electric Power Systems"). And the simulation and experimental results are verified.

  • PDF

Performance Improvement of an Anti-Islanding Algorithm using the Variation of Reactive Power with an Improved DFT Method (개선된 DFT을 이용한 무효전력변동 단독운전 검출기법의 성능 개선)

  • Kang, Duk-Hong;Choi, Dae-Keun;Lee, Kyo-Beum
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.15 no.3
    • /
    • pp.179-187
    • /
    • 2010
  • This paper proposes a new anti-islanding method for single-phase grid-connected photovoltaic (PV) systems using Goertzel algorithm. The proposed scheme is based on inducing increases or decreases of frequencies of load voltage and current that is in the form of existences or periodical variations of the reactive power components. The frequency detection is needed to apply this power variation method to the grid-connected power converter. The proposed method is able to get a fast detection for anti-islanding without the effect of harmonics and noises. The simulation and experiment results validate the effectiveness of the proposed method.

An Analysis and Design of RPV and AFD Method for Anti-Islanding of Single-Phase UIPV System under The Test Condition Recommended by IEEE 929-2000 (IEEE 929-2000 단독운전 시험조건 하에서 단상 계통연계형 PV 시스템의 Anti-Islanding을 위한 RPV 방식 및 AFD방식의 해석 및 설계)

  • Kim, Hong-Sung;Kim, Han-Goo;Choe, Gyu-Ha;Kim, Jae-Chul;Choi, Yung-Ho
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.12 no.1
    • /
    • pp.37-49
    • /
    • 2007
  • To detect islanding mode when the grid is being tripped is a major safety issue in utility interactive PV(UIPV) system. Widely used techniques among various active methods to detect islanding mode are Reactive power variation (RPV)method and Active frequency drift(AFD) method. In this paper, analytical design method is suggested for AFD and RPV method under IEEE recommended islanding test condition. And in order to show the validity of proposed method, EMTP based simulation was done for UIPV system with RPV method and AFD method. Results shows proposed method is very useful.

A Study on Anti-Islanding Evaluation of Grid-Connected Power Conditioning System for Fuel Cell System in Parallel Operation (병렬 연결된 계통연계형 연료전지 전력변환장치의 단독운전방지 평가 연구)

  • Choi, Young-Joo;Oh, Gun-Woo;Kim, Min-Woo;Lee, Seung-Kuk;Park, Ga-Woo
    • Journal of the Korean Institute of Gas
    • /
    • v.22 no.5
    • /
    • pp.124-132
    • /
    • 2018
  • The supply of renewable energy has become more vigorous due to Paris Agreement. In Korea, supply policies of renewable energy is being promoted with priority given to public buildings, so, the supply of fuel cell system that are relatively easy to install in buildings is expected to expand, so it is important that study on anti-islanding evaluation of grid-connected power conditioning system(PCS) for fuel cell. In this study, we consider that KGS AB934 PC53 in domestic certification standard of PCS for fuel cell correspond with abroad standard and analyze anti-islanding evaluation that important safety performance when connected grid. Additionally, we constructed a prototype for anti-islanding evaluation of PCS for fuel cell connected in parallel and carried out the demonstration evaluation, so, we have conducted ways that ensure safety performance in accordance with the circumstances where several fuel cell systems are installed.

Analytical comparison of AFD and RPV methods for Anti-Islanding (단독운전방지를 위한 AFD 와 RPV 방식의 비교 분석)

  • Ba, Yasgalan;Lee, Young-Jin;Jeong, Byong-Hwan;Kim, Hong-Sung;Choe, Gyu-Ha
    • Proceedings of the KIPE Conference
    • /
    • 2008.10a
    • /
    • pp.64-67
    • /
    • 2008
  • To detect islanding mode when the grid is being tripped is a major safety issue in the Utility Interactive Distributed Generation (UIDG) system. In this paper, analytical design method is suggested for AFD & RPV method under IEEE929-2000 recommended islanding test condition. We have discussed that there is a same point. we injected reactive component of the current by AFD & RPV methods, but the current reference generated is other waveform. Possible if amount of reactive components in this methods are same each method, there is happened same rates frequency variation. To verify the validity of the analytical comparison, this paper presents simulation and experimental results from single phase, 3[kW] inverter for the transformerless UIDG system.

  • PDF