• 제목/요약/키워드: Aging conductors

검색결과 9건 처리시간 0.029초

Aging Analysis and Reconductoring of Overhead Conductors for Radial Distribution Systems Using Genetic Algorithm

  • Legha, Mahdi Mozaffari;Mohammadi, Mohammad
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권6호
    • /
    • pp.2042-2048
    • /
    • 2014
  • In medium voltage electrical distribution networks, reforming the loss reduction is important, and in line with this, the issue of system engineering and use of proper equipment Expansion of distribution systems results in higher system losses and poor voltage regulation. Therefore, an efficient and effective distribution system has become more important. So, proper selection of conductors in the distribution system is crucial as it determines the current density and the resistance of the line. Evaluation of aging conductors for losses and costs imposed in addition to the careful planning of technical and economic networks can be identified in the network design. In this paper the use of imperialist competitive algorithm; genetic algorithm; is proposed to optimal branch conductor selection and reconstruction in radial distribution systems planning. The objective is to minimize the overall cost of annual energy losses and depreciation on the cost of conductors to improve productivity given the maximum current carrying capacity and acceptable voltage levels. Simulations are carried out on 69-bus radial distribution network using genetic algorithm approaches to show the accuracy as well as the efficiency of the proposed solution technique.

주상변압기 열적 특성 향상을 위한 복합절연 시스템 적용 (The Study on Application of Hybrid Insulation System for Thermally Upgraded Distribution pole Transformers)

  • 이병성;송일근;이재봉;김동명;한상옥
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 C
    • /
    • pp.1896-1898
    • /
    • 2002
  • In this paper, to developing thermally and mechanically upgraded ones, we dismounted pole transformers used in the fields for over 13 years and conducted aged oil analysis. Also, when the cellulose and aramid papers in test cell were aging with oil at $130^{\circ}C$ for 3000 hours, with the testing period cellulose paper deteriorated more rapidly than the others. For example dielectric strength and dissipation factor of papers deteriorated with aging time. For evaluation of thermal aging characteristics, a mineral oil-immersed transformer was constructed with hybrid insulation system comprised of aramid paper and cellulose insulation. A Hybrid system has economic advantages. Cellulose materials are confined to cooler regions of the transformer winding. And aramid papers are served to insulate contact parts of hot conductors.

  • PDF

산불에 의한 가공송전선의 열화거동 (The Aging Behavior of Overhead Conductor due to Forest Fire)

  • 김병걸;김상수;한세원;김진한
    • 한국전기전자재료학회논문지
    • /
    • 제20권12호
    • /
    • pp.1105-1111
    • /
    • 2007
  • Because forest fire can give a serious damage to overhead conductors, the thorough understanding about aging behavior of burned conductor is very important in maintaining the transmission line safely. Therefore, a systematic investigation was carried out by heating method. As the heating temperature increases, drastic change of tensile strength of Al wire due to the softening of Al wire occurred. When Al wire is exposed to the flame(about $800\;^{\circ}C$) during only 13 seconds, the remained tensile strength of Al wire showed under 90 %. The detailed results will be given in the text.

산불에 의한 가공송전선의 열화거동 (The Aging Behavior of Overhead Conductor due to Forest Fire)

  • 김병걸;김상수;전완기;한세원
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 하계학술대회 논문집 Vol.8
    • /
    • pp.534-535
    • /
    • 2007
  • Because forest fire can give a serious damage to overhead conductors, the thorough understanding about aging behavior of burned conductor is very important in maintaining the transmission line safely. Therefore, a systematic investigation was carried out by heating method. As the heating temperature increases, drastic change of tensile strength of Al wire due to the softening of Al wire occurred. When Al wire is exposed to the flame(about $800^{\circ}C$) during only 13 seconds, the remained tensile strength of Al wire showed under 90%. The detailed results will be given in the text.

  • PDF

환경적 요인에 의한 노후 가공송전선의 특성변화 (Change of Properties by Environment Conditions in Aged ACSR Overhead Conductor)

  • 김상수;김병걸;장태인;강지원;이동일;민병욱
    • 한국전기전자재료학회논문지
    • /
    • 제19권3호
    • /
    • pp.287-291
    • /
    • 2006
  • This paper describes mechanical and electric properties of ACSR $410\;mm^2$ conductor from many of older overhead conductor. Samples of conductors itemized two division according to operation sector, green area, salt and pollution area. Samples of conductors operated various environment conditions have undergone laboratory metallurigical investigation and tensile strength torsional ductility and electrical performance. The steel core were found to have retained their original properties to a large degree in both tensile strength and the number of turns to failure. On the other hand the aluminum conductor showed reductions in tensile strength. To determine the remaining useful life of aged conductor, an unacceptable deterioration level has to established for each diagnostic procedure.

산불이 가공송전선의 온도에 미치는 영향 (The Effect of Forest Fire on Temperature of Overhead Conductor)

  • 김병걸;김상수;전완기;한세원
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 하계학술대회 논문집 Vol.8
    • /
    • pp.523-524
    • /
    • 2007
  • Forest fire can give a serious damage to overhead conductors. Therefore, the definite understanding about aging behavior of burned conductor is very important in maintaining the transmission line safely. It is sure that the temperature of conductor itself will be affected by the distance apart from flame. From this point of a view, we monitored the conductor's temperature with distance from flame. As a result, the conductor's temperature decreased as the flame goes away from the conductor gradually. The temperature of conductor was reached up to 55~65% level of its atmospheric temperature. The detailed results will be presented in the text.

  • PDF

산불에 의해 가열된 가공송전선의 이도거동 (The SAG Behavior of Overhead Conductor due to Forest Fire)

  • 김병걸;김상수;전완기;한세원;김진한
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 추계학술대회 논문집
    • /
    • pp.516-517
    • /
    • 2007
  • Because forest fire can give a serious damage to overhead conductors, the thorough understanding about sag behavior of burned conductor is very important in maintaining the transmission line safely. Therefore, a systematic investigation was carried out by heating method. As the heating temperature increases, drastic change of tensile strength of Al wire due to the softening of Al wire occurred. When Al wire is exposed to the flame(about $800^{\circ}C$) during only 13 seconds, the remained tensile strength of Al wire showed under 90%. and then sag of overhead conductor become deteriorated. The detailed results will be given in the text.

  • PDF

STACIR/AW 410SQmm 가공송전선의 경년열화와 이도거동(III) (Sag Behavior of STACIR/AW 410SQmm Overhead Conductor in accordance with the Aging)

  • 김상수;김병걸;신구용;이동일;민병욱
    • 한국전기전자재료학회논문지
    • /
    • 제19권3호
    • /
    • pp.280-286
    • /
    • 2006
  • As a way to expand electric capacity in conductor with electric power demand, STACIR/AW (Super Thermal-resistant Aluminum-alloy Conductors Aluminum-clad Invar-Reinforced) conductor which has high electric current and heat resistance characteristics have been developed. STACIR/AW power line is mechanical composite wire composed of steel cores for dip control and aluminum conductors for sending electric current. Recently, to ensure stable operation and prediction of wire life span of STACIR/AW conductor, a heat property of STACIR/AW conductor have been investigated. In the present work, a change of essential property with long term-heat exposure of STACIR/AW conductor and its structure material, INVAR wire and Al conductor, have been investigated. INVAR/AW is approximately $3.2\;{\mu}m/m^{\circ}C$. thermal expansion coefficient of INVAR/AW wire increases with time of heat exposure. the thermal expansion coefficient of INVAR/AW is markedly influenced by heat and mechanical treatment. creep rate(0.242) of STACIR/AW $410\;mm^2$ conductor at room temperature is much higher than that(0.022) at $210\;^{\circ}C$ STACIR/AW $410\;mm^2$ conductor has minimum creep rate at operating temperature. To lower creep rate with increase temperature is more unique characteristics in STACIR/AW. It is expected that STACIR/AW turned its tension to INVAR/AW at the transition temperature. at room temperature, the tension apportionment of INVAR/AW in STACIR/AW is about $50\;\%$. but whole tension of STACIR/AW is placed on the INVAR/AW alone of core metal above transition temperature.

경년열화가 증용량 저이도 송전선의 기계적특성에 미치는 영향 (II) (Effect of Mechanical Properties by a Long Term Operation in High Capacity and Low Sag Conductor ( II ))

  • 김상수;김병걸;신구용;이동일;민병욱
    • 한국전기전자재료학회논문지
    • /
    • 제19권1호
    • /
    • pp.100-106
    • /
    • 2006
  • Today, restricted energy sources, environmental considerations and the high cost of transporting fuel have limited the number and location of available power plant sites. The pressures resulting from these conditions have tended to require the construction of long, high-capacity, high-voltage power lines. it's used to adapt to STACIR/AW(Super Thermal-resistant Aluminum alloy Conductors, aluminum-clad Invar-Reinforced) conductor for coping with these situations. STACIR/AW conductor was formed by the combination of INVAR/AW as the core for low sag and super thermal-resistant aluminum alloy conductor for current capacity increase. increase of temperature by current capacity and long span lines make the susceptible to the deterioration of thermo-mechanical properties(conductivity, tensile strength, E-modulus and twist property et al). In the present work, changes of thermo-mechanical properties with aging have been studied in STACIR/AW $410 mm^2$ conductor with forms of single wire and strand wire.